Mag Probe Installation

UST Installation - Vapor Extractor Riser W/ Coupling Adapter

13

3.

Make sure there is a minimal amount of slack between the probe and cap, then tighten the cord grip nut until 
the cable is held firmly. Push the end of the cable through the field J-box cord grip, then tighten that cord grip 
nut as well. Splice and seal the wires in the J-box.

AST RISER CAP ATTACHMENT

1.

If you are using the one piece cap (see Figure 6 on page 9), push the end of the probe cable through the cap 
and cord grip bushing, leaving a minimal amount of slack between the probe and cap. Discard the cord grip 
nut and attach the adapter Nut from the AST kit to the cap (see Figure 3 on page 6). Tighten the adapter Nut 
until the cable is held firmly. Go to Step 3.

2.

If you are installing the metal cap and ring (see Figure 7 on page 10), screw the ring onto the 4” riser until the 
gasket contacts the pipe, then use a pipe wrench to tighten it an additional 3/4 turn. Using UL-classified pipe 
sealant (suitable for the fuels involved), screw the cord grip fitting into the tapped hole and tighten. Place the 
cord grip bushing in the fitting. Discard the cord grip nut and loosely screw the adapter Nut from the AST kit 
onto the cord grip fitting (see Figure 3 on page 6). Push the cable through the metal cap, bushing, and 
adapter nut, then clamp the cap onto the ring. Make sure there is a minimal amount of slack between the 
probe and cap, then tighten the adapter Nut until the cable is held firmly.

3.

Next assemble the liquidtight connectors on both ends of the flexible conduit as shown in Figure 3. Push the 
cable through the flexible conduit assembly and into the J-box. Connect the flexible conduit assembly to the 
adapter Nut on one end and the J-box on the other.

4.

Tighten the fittings until snug. Splice and seal the wires in the J-box.

UST Installation - Vapor Extractor Riser W/ Coupling Adapter

This type installation is usually a retrofit and is usually connected to the console via direct burial cabling. The site 
should already be prepped (all digging, saw cutting, and jackhammering done) prior to probe installation (see 
Figure 12). A piece of flex conduit should be in place as shown to protect the cable.

Figure 12.  Vapor Extractor Cabling Entry 

1.

Remove any existing hardware from the Vapor Extractor Riser so that it’s 4” NPT riser threads are exposed.

4" Riser

probes\verprep.eps

Manhole Cover

(Backfill)

(Concrete)

Flex Conduit

Sawcut trench for
Direct Burial Cable

Jackhammered entry to 
bottom of manhole

Содержание TLS-450

Страница 1: ...Manual No 577013 934 Revision E Site Prep Certification Manual TLS 450 TLS 450PLUS Consoles...

Страница 2: ...ur Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Contact Veeder Root Customer Service at 800 873 3313 with the specific part numbers and quantities that were missing or received damaged 2 Fax...

Страница 3: ...ng Adapter 7 Vapor Extraction Riser Kit W O Coupling Adapter 8 Riser Cap Kit for Mag Probe Installations 9 Cap and Cord Grip Kit 9 Metal Cap and Ring Kit 9 Mag Probe Installation UST AST Tank Dedicate...

Страница 4: ...beneath the metal cap and adapter ring 12 Figure 12 Vapor extractor cabling entry 13 Figure 13 Mag probe vapor extractor riser installation w coupling adapter 15 Figure 14 Mag probe vapor extractor r...

Страница 5: ...Descriptive System IECEx Descriptive System UL cUL Control Drawing Document No Document No Document No Associated Apparatus TLS 450 TLS 450PLUS 331940 006 331940 106 331940 008 Intrinsically Safe Appa...

Страница 6: ...such as Carol C2534 or Belden 88760 8760 8770 or similar Note Throughout this manual when mentioning any cable or wire being used for probe and sensor to console wiring it will be referring to shielde...

Страница 7: ...o the mounting surface using the hole pattern shown in Figure 1 Up to 1 4 diameter screws may be used Mount the console to the mounting surface using the four mounting flanges on the back of the unit...

Страница 8: ...35 BOTTOM VIEW tlsng dim eps Mounting flanges w 1 4 x 3 8 slotted hole typ 4 places 3 1 8 1 2 TYP 5 925 0 65 4 5 8 3 1 8 3 1 8 3 1 8 TOP VIEW Conduit entries to Module bay 3 4 1 I P S knockouts typ 4...

Страница 9: ...ious injury or death Routing conduit for power wires into the intrinsically safe compartment can result in fire or explosion resulting in serious injury or death OFF L1 N L2 L1 G L2 To 240 Vac breaker...

Страница 10: ...ag Probe AST Installation Kit Table 1 Mag Probe AST Installation Kit Part No 312020 984 Quantity Description Part Number 5 feet 3 8 Flexible Conduit 576008 294 1 3 8 Adapter Nut 329972 002 2 3 8 Strai...

Страница 11: ...o 846500 001 Quantity Description Part Number 2 Wire Nut 576008 461 1 Cable Tie 576008 482 1 Splice Enclosure 514100 357 1 Splice Kit Instructions Manual 576013 861 1 PG7 1 4 Cord Grip Fitting 576008...

Страница 12: ...oupling Adapter Installation Kit Table 3 Vapor Extraction Riser Kit W O Coupling Adapter Part No 846500 002 Quantity Description Part Number 2 Wire Nut 576008 461 1 Cable Tie 576008 482 1 Splice Enclo...

Страница 13: ...screws onto the 4 NPT riser Figure 6 The cap comes drilled and tapped with a cord grip Figure 6 Cap And Cord Grip Kit METAL CAP AND RING KIT This riser cap kit contains an adapter ring which screws o...

Страница 14: ...rip fitting P N 331028 001 as follows 1 Remove the cap to a non hazardous location 2 Drill and tap the cap for a 1 2 14 NPT cord grip thread Figure 8 Figure 8 Modifying An Existing Metal Riser Cap 1 C...

Страница 15: ...he cord grip bushing and nut on the cap leaving a minimal amount of slack between the probe and cap Screw the cap onto the riser by hand until the gasket first contacts the pipe Then lightly tap the c...

Страница 16: ...5 45 ft lbs Loosen the cord grip nut and push the cable through the metal cap and cord grip then clamp the cap onto the ring see Figure 11 Figure 11 Installing A Riser Adapter Beneath The Metal Cap An...

Страница 17: ...nut and loosely screw the adapter Nut from the AST kit onto the cord grip fitting see Figure 3 on page 6 Push the cable through the metal cap bushing and adapter nut then clamp the cap onto the ring M...

Страница 18: ...additional 3 4 turn 9 Test pull the cable to insure that it is free of spring and that the probe is resting on the bottom of the tank Make sure there is some slack in the cable 10 Slip the PG7 cord gr...

Страница 19: ...floats spacer rings and cable as per the Mag Probe Assembly Manual 5 Gently slide the float s to the bottom of the probe shaft Important Handle probes carefully Striking or dropping the probe will re...

Страница 20: ...on System you now need to consider another form of overfill protection i e TLS console alarm a drop tube with overfill protection valve or some other accepted means Figure 14 Mag Probe Vapor Extractor...

Страница 21: ...plicing all sump sensor wires together to run one wire back to console Use single lengths of wire with no splices to ensure optimum signal strength Figure 15 Example Probe Wiring Run In Buried Rigid C...

Страница 22: ...g using an abrasive wheel a 1 4 to 3 8 wide by 1 1 4 deep groove adding 1 4 of depth for each additional cable in the pavement surface laying Veeder Root supplied direct burial cable down in the botto...

Страница 23: ...ve sys or dispenser 120 240 Vac Output Relay Connections Pump Sense Pump In Pump Return NO C Dispenser Control Connections External Input Connections NO C SWITCH HOOK STP CONTROL w RJ Relay Control Bo...

Страница 24: ...DIM L1 N NC NC P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 120 VAC INPUT RATING 120 VAC MAX 0 30 AMP MAX White 934 2 eps Black 115 Vac Line BLK Neutral WHT Barrier P N 7859 769780 008 Pulse Transmitter 120...

Страница 25: ...ition Common Pulser 12 PetroVend System 2 PV270 Pump Relay Board LVDIM LOW VOLTAGE DISPENSER INTERFACE MODULE 12 11 10 9 5 6 7 8 1 2 3 4 SOURCE INPUT RATING 30 VDC MAX 0 1 AMP MAX 934 1 eps Micon 200...

Страница 26: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: