background image

Refer to veeder.com for additional product information.

Technical Support Notification

TLS4 Series Programming – Email Setup & Troubleshooting

Overview

The TLS4 series consoles allow the user to send out emails with a range of reports from daily inventory readings to tank 

or line testing history. This technical support notification explains how to program the console to send out emails and 

provides troubleshooting steps for when emails are not received.  

The instructions below are intended to be used in conjunction with the 

TLS-450PLUS/TLS4 Operator's Manual (577014-110)

.

Programming

Ethernet Port

Menu 

Setup 

Communication 

Ethernet Port

Confirm a CAT5 cable is connected to the correct 

ethernet port.

Confirm the ethernet port is working by checking 

the port for lights. No lights or a red light can 

indicate a bad port.

For static IP addresses, confirm the IP Default 

Gateway is set to enabled. Only one port can use 

the default gateway, which allows outside 

network access. 

Confirm there is a Primary and Secondary DNS.

Requirements

Ethernet Port – Primary/Secondary DNS

Address Book

Autoconnect Task

SMTP Relay 

(not always required)

Programming Requirements:

Troubleshooting Requirements:

Laptop 

Cat5 Cable

Access to a network jack 

(router/switch)

Access to the web portal

Note

Google’s public DNS servers are 

8.8.8.8

and 

8.8.4.4

.

Front of 

Console

Отзывы: