background image

POS App Guide

DIM Installation Examples

30

Gilbarco SmartCrind Dispenser Systems

TLS CONSOLE SOFTWARE REQUIREMENTS

TLS-350R with BIR Software Requirements
• System software Version 17 (or higher)

• DIM software 349806-001 (or higher)

TLS-450/TLS-450PLUS with BIR Software Requirements
• TLS-450 System software Version 2.X (or higher)

• TLS-450PLUS System software Version 6.X (or higher)

• BIR option required (TLS-450)

VEEDER-ROOT HARDWARE REQUIREMENTS (REF. TABLE 2)

The following equipment is required to interface the TLS to the SmartCrind network:
• One TCP/IP (TDIM) Interface Module 

• Ethernet cable 

SYSTEM LIMITATIONS

• Up to Gilbarco single product or blending fueling positions are supported.

• Only Gilbarco SmartCrind dispensers are supported.

INSTALLATION NOTES

Example wiring diagrams are shown in Figure 11 below.

Figure 11.   SmartCrind Installation

401-16.ep

s

PC (e.g., 

ba

ck office)

Pl

u

g

s

 into PC

Ethernet c

a

rd

Ethernet c

ab

le

Ethernet

c

ab

le

TL

S

 Con

s

ole

Pl

u

g

s

 into RJ45 

connector

in TDIM mod

u

le

H

ub

Do not

us

u

plink

connector!

X

Содержание TLS-350R

Страница 1: ...Manual No 577013 401 Revision K Application Guide TLS Consoles Point of Sale POS ...

Страница 2: ...tal or consequential damages in connection with the furnishing performance or use of this publication The information contained in this publication may be subject to change without notice This publication contains proprietary information which is protected by copyright All rights reserved No part of this publication may be photocopied reproduced or translated to another language without the prior ...

Страница 3: ... Module TDIM TLS 350R 6 TCP IP DIM TDIM TLS 450 TLS 450PLUS 6 DIM And Installation Kit Ordering Guide 7 DIM Installation Examples Bennett POS System 16 Veeder Root Software Requirements 16 Veeder Root Hardware Requirements Ref Table 2 16 Bennett System Limitations 16 Installation Notes 16 Gilbarco TCRG TCRG2 T 11 and T 12 POS Systems 18 TLS Console Software Requirements 18 Veeder Root Hardware Req...

Страница 4: ...ware Requirements 37 Installation Notes 37 GasBoy CFN Systems 40 TLS Console Software Requirements 40 Veeder Root Hardware Requirements Ref Table 2 40 GasBoy System Requirements for BIR Interface 40 Connecting to the Site Controller II 40 BIR Protocol DIM 42 POS System Requirements and Limitations 42 Mechanical Dispensers 43 TLS 350 MDIM Applications 43 TLS 450 TLS 450PLUS MDIM Applications 43 LVD...

Страница 5: ...97 Series Pulse Transmitters And Required Barriers 43 Figure 25 Wiring Diagram Of TLS 450 TLS 450PLUS MDIM Using Two 1871 7697 Series Pulse Transmitters Required Barriers 44 Figure 26 Mechanical Dispenser Applications Using 7874 Series Pulser Totalizer 45 Figure 27 TLS 350 Meter Stand Application Using 1871 7697 Series Pulser Totalizer 46 Figure 28 TLS 450 TLS 450PLUS Meter Stand Application Using...

Страница 6: ...Capabilities TLS 350R WITH BIR ONLY AND TLS 350R WITH BIR AND ISD Support up to 36 fueling positions Support up to 6 meters hoses per fueling position Support manifolded tanks Support blending dispensers that separately meter each product prior to blending Gilbarco Tokheim and Wayne electronic blending dispensers are supported Do not support dispensers that blend fuel prior to the metering process...

Страница 7: ...nstallation kits vary for each DIM and include all required adapter boxes and cables IN STATION DIAGNOSTICS TLS 350R with ISD option ECPU2 board with 325 or later software and a NVMEM203 board A Mag 1 0 1 gph magnetostrictive standard or Mag Plus probe is required for each gasoline tank The Mag 1 probe for alternative fuels is also supported Dispenser Interface Module For electronic dispensers one...

Страница 8: ... interface to most Gilbarco Wayne and 3rd Party POS systems that implement the VR BIR Protocol ALLIED ANDI EXCENTUS BENNETT For electronic dispensers one DIM is required for each TLS 450 Up to 3 DIMs can be installed to support sites with multiple POS systems DIM installation kit One installation kit may be required for each DIM ref Table on page 7 The installation kits vary for each DIM and inclu...

Страница 9: ...tantly evaluating and supporting new applications If your application is not listed in this guide contact your Veeder Root Sales Representative Bennett 92D X Mechanical Mechanical noncomp or Mechanical V R meter CFN2 Petrovend ANDI X X X Table 1 Supported POS Systems Continued Manufacturer POS Dispensing System TLS 350R TLS 450 TLS 450PLUS ...

Страница 10: ...50PLUS console installs in comm slots 1 or 2 Factory installed in TLS4 console TLS 450 and TLS 450PLUS require module kit P N 330020 665 Various CDIM monitoring applications include current loop RS 232 and RS 422 More than one CDIM can be installed in combination with other DIM types CDIMs have three RJ 45 modular connectors TLS 350R or 2 to 3 RJ 45 modular connectors TLS 450 TLS 450PLUS CDIMs can...

Страница 11: ...sole system software Version 15 or higher Version 21 or higher is recommended Network connection to a PC requires a hub Connecting to a hub requires a straight CAT 5 cable Direct connection to a PC requires an Ethernet crossover cable Connection to a LAN or WAN There are 2 LEDs on the PC board of this module Green LED indicates that the TDIM module is transmitting information to the TLS Red LED in...

Страница 12: ...er version 2 0 or later is required A Gasboy junction box Gasboy part C05020 should be ordered for installa tion No Blending Net work POS Required ANDI ALLIED ANDI ALLIED NEXTGEN 330280 001 Standard In Gauge None required Y Y Y Allied ANDI Gilbarco dispenser with T 14 Australia PEC with 8850 POSTEC with RCC Wayne with Mar keter 2000 Sweden CFN1 331001 002 None 331088 XXX Y N N This is a TLS 350 RS...

Страница 13: ...Y To support this DIM and the TLS 350R the G site must be upgraded to include the EMC interface Uses Controller types C2 C15 486 and Pen tium Site controllers Passport Passport EDH Y Y Y Verify BIR protocol is in version of Passport software used at cus tomer s site Storemas ter 330404 020 330020 665 848741 XXX Y Y Y One Gilbarco Dis penser Distribution Box PA0133000 should be available Up to 12 H...

Страница 14: ...No Blending Wayne Nucleus 330404 200 330020 665 848722 XXX Y Y Y Wayne Nucleus POS with Gilbarco Dispens ers Radiant 330280 001 Standard In Gauge None Y Y Y Radiant Systems Series P1550 set up on the TLS must have a DIM string pro grammed in The DIM string is B9DNHG and needs to be pro grammed in DIM Diag nostics You will need to use a twisted pair RJ 11 cable to the port on the POS with the pin o...

Страница 15: ...ter Petrovend 331214 001 330020 800 None Y Y Y One or more pulser totalizer kits are needed PN 787491 003 Each mech DIM supports up to 4 mech dispensers Up to 8 may be installed in the high power compart ment of the TLS 350R Other modules installed will reduce the number of slots avail able Table 2 Dispenser DIM and Installation Kits Dispenser Dispenser Controller POS Type TLS 350R DIM P N w Conso...

Страница 16: ...stralia PEC with 8850 POSTEC with RCC Wayne with Mar keter 2000 Sweden Radiant 330280 001 Standard In Gauge None Y Y Y Radiant Systems Series P1550 set up on the TLS must have a DIM string pro grammed in The DIM string is B9DNHG and needs to be pro grammed in DIM Diag nostics You will need to use a twisted pair RJ 11 cable to the port on the POS with the pin outs of 2 3 7 Table 2 Dispenser DIM and...

Страница 17: ...ms Series P1550 set up on the TLS must have a DIM string pro grammed in The DIM string is B9DNHG and needs to be pro grammed in DIM Diag nostics You will need to use a twisted pair RJ 11 cable to the port on the POS with the pin outs of 2 3 7 Table 2 Dispenser DIM and Installation Kits Dispenser Dispenser Controller POS Type TLS 350R DIM P N w Console TLS 450 DIM P N w Console TLS 450PLUS DIM P N ...

Страница 18: ...0 POSTEC with RCC Wayne with Mar keter 2000 Sweden 67 A 98 331354 001 None 331391 XXX Y N N Tokheim controller only 67 B 848744 XXX Columbus 330280 001 Standard in Gauge None Y Y Y For Rockport cable kits order Quantity 2 320449 18 from Tokheim For Digi Star gate order Quantity 2 320449 9 Cable kits from Tokheim Radiant 330280 001 Standard in Gauge None Y Y Y Radiant Systems Series P1550 set up on...

Страница 19: ...d in Gauge None Y Y Y TCPIP interface for Wayne IDPOS dis pensers only Radiant 330280 001 Standard in Gauge None Y Y Y Radiant Systems Series P1550 set up on the TLS must have a DIM string pro grammed in The DIM string is B9DNHG and needs to be pro grammed in DIM Diag nostics You will need to use a twisted pair RJ 11 cable to the port on the POS with the pin outs of 2 3 7 Verifone Com mander 33028...

Страница 20: ...allation manual Figure 1 Simplified DIM Connections To Various Dispensing Systems Mechanical Dispenser Dispenser Controller Network Junction Box Distribution Box Cable Adaptor Box CDIM LVDIM MDIM EDIM LDIM IFSF TDIM Dispenser Dispenser Electronic or Mechanical Dispenser Comm Bay installed DIMs TLS 350 Power Bay installed DIMs TLS 450 Model Bay installed DIMs Barrier 401 6 eps TLS Console TLS 350 o...

Страница 21: ...BIR and TLS 350R with BIR and ISD Only non blending type 92D dispensers with Orpak controllers are supported TLS 350R with ISD All type 92D dispensers with Orpak controllers are supported INSTALLATION NOTES The interface to Bennett dispensing equipment requires one CAB per dispenser current loop for up to 6 fueling positions and one Bennett DIM installation kit for every 2 current loops Typically ...

Страница 22: ...CURRENT LOOPS BENNETT PUMP INTERFACE BOX 17 1 2 3 4 5 6 7 8 9 11 12 13 14 15 18 19 20 21 Dispenser Terminal Block 22 16 GRN GROUND YEL DATA ORG DATA YEL DATA ORG DATA GRN CONDUIT shield shield White Black Shield 401 7 eps Disconnect orange wire from terminal 17 and connect to white wire from CAB with wire nut Attach black wire from CAB to terminal 17 Connect cable shield to terminal block ground c...

Страница 23: ...d per current loop The following POS consoles are supported Transac 1e1 PA0132 PA0141 Transac 12 PA0134 PA0142 Transac 12A PA0151 PA0152 Transac 12B PA0173 Transac 12C PA0188 Transac 12G PA0203 TCRG PA0180 121 TCRG2 PA0180 121 Excentus Reward Fuel ControllerTM Gilbarco Dispenser Interface V1 0 160 SPECIFIC LIMITATIONS Only Gilbarco electronic dispensers are supported Also dispensers that feature a...

Страница 24: ...GRAM FOR A TRANSAC CURRENT LOOP INTERFACE A PA0133 distribution box is shown in Figure 3 below Other box models are slightly different Figure 3 Transac Series Current Loop Interface Shielded 2 Wire Flying Lead Cable Connects to CDIM TLS Console 401 8 eps ...

Страница 25: ...entus Interface Box POS Controller VR CAB P N 330591 00X Gilbarco Distribution Box TLS Console Connects to CDIM Set sw to RUN CONSOLE COMM PUMP COMM RUN BYPASS P N S N Environmental Products VEEDER ROOT RJ 45 RJ 45 RJ 45 RJ 45 RJ 45 RJ 45 RJ 45 VR CDIM Adaptor Cable P N 330592 XXX VR 6 foot 2 conductor DIM Assembly Cable P N 331105 001 WHT WHT BLK BLK 3 2 1 401 9 eps 3 numbered items contained in ...

Страница 26: ...r distribution box PA02420000000 Gilbarco dispenser distribution box PA02610000010 Gilbarco dispenser distribution box PA02610000020 Gilbarco pump controller model PA02410000000 Gilbarco Transac System 1000 Console model PA0240000000 Gilbarco Transac System 1000 Console model PA02400001010 Excentus Reward Fuel Controller Gilbarco Dispenser Interface V1 0 160 Excentus P N 080 Veeder Root Kit is req...

Страница 27: ...POS App Guide DIM Installation Examples 22 Figure 5 Universal Distribution Box Interface PAM or Transac 1000 Site Controller cab dim vrgbts eps CDIM connection TLS Console 401 10 eps ...

Страница 28: ...ositions are supported by the TLS 350R and up to 72 fueling positions are supported by the TLS 450 TLS 450PLUS In dispenser credit card readers CRINDS are supported To support a DIM and the TLS 350R the G Site must be upgraded to include EMC interface capability This has been released in the following G Site versions EMC Interface capability will be released into the Generic G Site version 6 Exxon...

Страница 29: ...5 Adapter Q13180 03 331138 001 G Site C 2 G SITE Tank Gauge Connect RJ 45 plug into 25 pin D RJ 45 Adapter 331138 002 Connect RJ 45 plug into 25 pin D RJ 45 Adapter 331138 001 Connect RJ 45 plug into 25 pin D RJ 45 Adapter 331138 001 Connect 25 pin D RJ 45 Adapter 331138 002 to Tank Guage port RJ45 Modular Cable Diagram A Diagram B Connect RJ 45 plug directly to Tank Mon port TLS Console TLS Conso...

Страница 30: ...ilbarco Dispenser Distribution Box PA0281XXXXXX0 An AutoGas 507 controller is required with the AutoGas Storemaster POS SYSTEM LIMITATIONS Up to 36 Gilbarco single product or blending fueling positions are supported Only Gilbarco dispensers are supported The Gilbarco current loop dispenser interface module does not support Gilbarco G Site applications The Cable Adaptor Box install kits are designe...

Страница 31: ...urrent Loop Interface Communications Cable Y cable 2 9 pin D Style connectors POS 401 12 eps Universal Distribution Box AutoGas 510 CRIND Controller with Current Loop Dispenser Interface Module CRIND Loop Current Loop CRIND Loop Current Loop Cable Adapter Box Connects to CDIM TLS Console ...

Страница 32: ... With Serial Interface Communications Cable Y cable 2 9 pin D Style connectors 401 13 eps Universal Distribution Box AutoGas 510 CRIND Controller with Serial Interface CRIND Loop Current Loop Cable Adapter Box PAM Serial Data Current Loop CRIND Loop POS Connects to CDIM TLS Console ...

Страница 33: ...D Controller Communications Cable Y cable 2 9 pin D Style connectors Generic POS 401 14 eps Universal Distribution Box AutoGas 510 CRIND Controller CRIND Loop Current Loop Current Loop Cable Adapter Box Serial or Current Loop Data CRIND Loop Connects to CDIM TLS Console ...

Страница 34: ...ations Cable 401 15 eps Universal Distribution Box AutoGas 507 CRIND Controller CRIND Loop Current Loop Cable Adapter Box To Cable Adapter Box To Controller UDB Storemaster POS CRIND Loop Computer Connection Connects to CDIM TLS Console PUMP CONTROLLER POINT OF SALE CONSOLE COMM DB9 M DB9 M ...

Страница 35: ... VEEDER ROOT HARDWARE REQUIREMENTS REF TABLE 2 The following equipment is required to interface the TLS to the SmartCrind network One TCP IP TDIM Interface Module Ethernet cable SYSTEM LIMITATIONS Up to Gilbarco single product or blending fueling positions are supported Only Gilbarco SmartCrind dispensers are supported INSTALLATION NOTES Example wiring diagrams are shown in Figure 11 below Figure ...

Страница 36: ...0 default setting for serial port J4 Version 5 rev 6 dated 11 1989 or later The Tokheim DHC itself can be Standalone and used with a third party POS or An internal component of a Tokheim Vision 100 Vision 200 MEMS IV or MEMS V Console SPECIFIC LIMITATIONS Only Tokheim dispensers are supported Tokheim electronic blenders are supported The dispensers may feature electronic card readers Mechanical bl...

Страница 37: ...G F 9038 GALS 962 GALS 0 GALS 8950 GALS 81 37 INCHES 28 GALS 1 37 INCHES 74 9 DEG F To Dispensers To Third Party POS Connects to EDIM TLS 350R Console 25 Pin D P N 330408 XXX ALARM WARNING POWER T1 PREMIUM UNLEADED VOLUME ULLAGE 90 ULLAGE TC VOLUME HEIGHT WATER VOL WATER TEMP T1 REGULAR GASOLINE VOLUME ULLAGE 90 ULLAGE TC VOLUME HEIGHT WATER VOL WATER TEMP 4208 GALS 5792 GALS 4792 GALS 4194 GALS 4...

Страница 38: ...08 GALS 5792 GALS 4792 GALS 4194 GALS 41 02 INCHES 0 GALS 0 00 INCHES 65 0 DEG F 9038 GALS 962 GALS 0 GALS 8950 GALS 81 37 INCHES 28 GALS 1 37 INCHES 74 9 DEG F Cable connects to J7 or J8 on rear panel CAB RJ 45 RJ 45 Dispenser Controller Dispenser Interface Box Tokheim 67A Tokheim 67B Tokheim 98 DB9 Barrel Connectors DB9 Barrel Connectors P N 330902 XXX P N 331394 001 for Tokheim 67A or 98 P N 33...

Страница 39: ...to the Wayne site controller The dispensers may feature electronic card readers TDIM Installations Wayne IDPOS dispenser software 2 29 TLS 350R and TLS 450 SUPPORTED WAYNE SYSTEMS Wayne 186 System with Site Controller model 880179 001 and Dispenser Data Box CAB model DD SY2400 08 Wayne 386 System with Site Controller model WP SC and Dispenser Data Box CAB model WP DD SUPPORTED WAYNE POS TERMINALS ...

Страница 40: ...ayne Nucleus Data Box Figure 15 Wayne Dispenser Data Box Current Loop TLS 350R and TLS 450 Figure 16 Wayne IDPOS Dispensers TLS 350R and TLS 450 POS 401 20 eps Cable P N 330592 XXX Cable P N 330592 XXX Cable P N 331105 001 Wayne Nucleus Data Box Pump Distribution Box Wayne Site Controller Connect to CDIM TLS Console CAB Left CAB Right Left Current Loop Right Current Loop 401 16 eps PC e g back off...

Страница 41: ...t TB6 1 2 3 4 5 6 Data In Data Out To CAB marked Left To CAB marked Right Left Current Loop Right Current Loop Set adjacent toggle switch to right Auto position Set adjacent toggle switch to right Auto position Wht Blk Wht Blk Alternative Left CAB connections see text Alternative Right CAB connections see text Wayne Data Box PC board cover plate removed 401 21 eps ...

Страница 42: ...upported by this DIM In dispenser credit readers are supported by the Schlumberger DIM Blending of any type is not supported by the Schlumberger DIM not a restriction for ISD only applications MICROMAX ALLIED HARDWARE REQUIREMENTS An Allied Protocol Box PCB or an Allied Station Site Controller SSC box Schlumberger MicroMax POS console other POS terminals are not supported Schlumberger Gilbarco Way...

Страница 43: ...quired 1 2 3 4 To Cable Adaptor Box To MicroMax POS Schlumberger MicroMax 3000 or Equivalent TB1 Note These two 25 pin D connectors are only to be used with Allied Station Site Controller Box Two Conductor Wire Supplied By Contractor Maximum of 2 feet Connects to CDIM TLS 350R Console ALARM WARNING POWER Communications Cable 401 24 eps Cable Adapter Box RJ 45 RJ 45 POS CONTROLLER XPIC or SAM PORT ...

Страница 44: ...lumberger MicroMax Cable Adapter Box RJ 45 RJ 45 POS CONTROLLER 25 Pin D Tokheim DHC Port 2 Port 5 POS Connects to CDIM TLS 350R Console ALARM WARNING POWER 401 26 eps Cable Adapter Box POS POS CONTROLLER SAM Port 1 Port 2 25 pin female to 9 pin female D connector 9 pin male to 25 pin male D connector 9 pin D male connector 9 pin D female connector 6 foot cable 9 pin D male connector Communication...

Страница 45: ...m One Gasboy Dispenser Interface Module One installation kit GASBOY SYSTEM REQUIREMENTS FOR BIR INTERFACE Console must be Site Controller II version 2 0 or later and have Send All Messages feature GasBoy junction box P N C05020 All Profit Point Broadcast messaging enabled Non blended dispensers not a restriction for ISD only applications CONNECTING TO THE SITE CONTROLLER II The TLS 350R must be co...

Страница 46: ...ble Supplied by Gasboy SITE CONTROLLER II To Console or other Junction Boxes ALARM WARNING POWER GND BLUE WHITE STRIPE WHITE BLUE STRIPE ORANGE WHITE STRIPE WHITE ORANGE STRIPE 401 27 eps To Plug In Connector on LDIM 1 2 3 4 5 TX GND TX TX RX RX 1 2 3 4 5 TX RX RX GND Terminal block inside RS 422 junction box Gasboy P N C05020 Cable shield C05020 Junction Box TLS 350R Console ...

Страница 47: ...inventory protocol commonly used by POS and other systems to collect inventory data from Veeder Root TLS Consoles Table 3 lists POS systems known to have implemented the Veeder Root protocol and thus support BIR protocol DIM Table 3 POS Systems Supporting BIR Protocol DIM Manufacturer System TLS 350R TLS 450 TLS 450PLUS Allied Station Site Controller SSC NextGen X X Gilbarco T 14 Australia X X PEC...

Страница 48: ...per system are supported Requires a pulser totalizer or pulse transmitter and a safe barrier device for each fueling position Only Veeder Root mechanical dispensers are supported Typical Wiring to Mechanical Dispensers Figure 24 Wiring Diagram Of TLS 350 MDIM Using Two 1871 7697 Series Pulse Transmitters And Required Barriers MECHANICAL DISPENSER INTERFACE MODULE 401 28 eps Barrier P N 7859 Barrie...

Страница 49: ...1 eps Barrier P N 7859 Barrier P N 7859 769780 012 Pulse Transmitter 769780 012 Pulse Transmitter Blue Black Orange Orange Blue Black Orange Blue Orange Blue Orange White 120 Vdc 120 Vdc White Orange Note Barriers may come with a 2 position connector MDIM MECHANICAL DISPENSER INTERFACE MODULE L1 N NC NC P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 120 VAC INPUT RATING 120 VAC MAX 0 15 AMP MAX Not used ...

Страница 50: ...POS App Guide DIM Installation Examples 45 Figure 26 Mechanical Dispenser Applications Using 7874 Series Pulser Totalizer 401 29 eps ...

Страница 51: ...smitter Metal Divider Plate Barrier No 7859 J Box Explosion Proof Low Voltage Area Orange White 401 30 eps Black 115 Vac Line BLK Metal Conduit V 0 0 0 0 0 14 AWG 7 x 36 Stranded Wires Gas Oil Resistant Meter Register Neutral WHT Typical Electric Wiring Trough MECHANICAL DISPENSER INTERFACE MODULE INPUT RATING 120 VAC 15 AMP MAX P1 P2 P3 P4 N L1 PULSER 120 VAC MDIM in Power Bay of TLS 350R Console...

Страница 52: ...1 N NC NC P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 120 VAC INPUT RATING 120 VAC MAX 0 15 AMP MAX GALLONS 769780 008 Pulse Transmitter Metal Divider Plate Barrier No 7859 J Box Explosion Proof Low Voltage Area Orange White 401 2 eps Black 115 Vac Line BLK Metal Conduit V 0 0 0 0 0 14 AWG 7 x 36 Stranded Wires Gas Oil Resistant Meter Register Neutral WHT Typical Electric Wiring Trough ...

Страница 53: ...e System 2 controller and thence to the pulsers see Figure 29 PetroVend 4 conductor shielded cable part no 12 1026 must be used to connect to pulsers or you must run 18 AWG gas oil and fire resistant wire in metal conduit separate from high voltage wiring to the pulsers Figure 29 TLS 350 LVDIM Installation With PetroVend System 2 Site Controller Set SW1 on underside of module s PC board to the EXT...

Страница 54: ...le s PC board to the EXTERNAL position Negative terminals not used w SW1 in the EXTERNAL position Common Pulser Hand Flow 12 PetroVend System 2 PV270 Pump Relay Board To Pulsers To Other PetroVend PV270 Relay Boards LVDIM LOW VO LTAG E D ISPEN SER I N TER FAC E MO DULE 12 11 10 9 5 6 7 8 1 2 3 4 SOURCE INPUT RATING 30 VDC MAX 0 1 AMP MAX 401 3 eps ...

Страница 55: ...the Micon 200 electronic dispenser head and thence to the pulsers Figure 31 TLS 350 LVDIM Installation Kraus Micon 200 Series Electronic Dispensers Not UL Approved 401 32 eps Blue 18 AWG Volume Pulser Output Micon 200 Electronic Dispenser Head Yellow 18 AWG Pulser Common Line Blue 18 AWG Volume Pulser Output Micon 200 Electronic Dispenser Head Yellow 18 AWG Pulser Common Line Not Connected Set SW1...

Страница 56: ...d Micon 200 Electronic Dispenser Head Yellow 18 AWG Pulser Common Line To Other Micon 200 Electronic Dispenser Heads LVDIM LOW VO LTAG E D IS P E N S E R I N TE R FAC E MODUL E 12 11 10 9 5 6 7 8 1 2 3 4 SOURCE INPUT RATING 30 VDC MAX 0 1 AMP MAX 401 4 eps Not used Set SW1 on module s PC board to the INTERNAL position Blue 18 AWG Volume Pulser Output ...

Страница 57: ...ule in metal conduit Figure 33 LVDIM Installation With GasBoy 9800 Or Tokheim 2600 Series Electronic Dispenser Head 401 33 eps GasBoy 9800 or Tokhiem 2600 Series Electronic Dispenser Head Pulse 1 Red NC Pulse 2 Grn DC Ground Wht DC Junction Box Not Connected Set SW1 on underside of module s PC board to the INTERNAL position LOW VOLTAGE DISPENSER INTERFACE MODULE INPUT RATING 30 VDC P1 P2 P3 P4 SOU...

Страница 58: ...TAG E D ISP E NS E R IN T E R FAC E MODULE 12 11 10 9 5 6 7 8 1 2 3 4 SOURCE INPUT RATING 30 VDC MAX 0 1 AMP MAX 401 5 eps GasBoy 9800 or Tokhiem 2600 Series Electronic Dispenser Head GasBoy 9800 or Tokhiem 2600 Series Electronic Dispenser Heads Not used Pulse 1 Red NC Pulse 2 Grn DC Ground Wht DC Junction Box Set SW1 on module s PC board to the INTERNAL position To Other ...

Страница 59: ...For technical support sales or other assistance please visit www veeder com ...

Отзывы: