HydrX System Wiring
FCC & FC Power Wiring Connections To TLS-450Plus
25
FCC & FC Power Wiring Connections To TLS-450Plus
Figure 26 through Figure 31 illustrate example HydrX power wiring connections between the Fuel Conditioning
Controller, Fuel Conditioner and TLS-450PLUS console.
Figure 26. Wiring Using Red Jacket Isolation
Sump
Disconnect, lock out,
and tag power at the
power panel before
wiring the pump.
WARNING
OFF
Maximum Exter
nal Contact
Closur
e Cir
cuit Ratings
12 Vdc, 0.015A
3
2
1
4
Maximum Relay Contact Ratings
120/240 V
ac, 5A 30 Vdc, 5A
Fuse Ratings 5A, 250 V
ac T
ype T (Slo-Blo)
2
1
5
3
4
Maximum AC
Input Ratings
120/240 V
ac, 0.10A
4
3
2
1
5
TN
2V
TN
2V
TN
2V
RTN
12V
I/O Module
TLS-450PLUS
Unused
AT
G
AC Neutr
al
Inlet V
alve
N
Outlet V
alve
N
Pump Request
N
AC Line
Inlet V
alve
L
Outlet V
alve
L
Pump Request
L
11
10
9
8
7
6
5
4
3
2
1
FUEL CONDITIONING CONTROLLER (FCC) BOX
RED JACKET ISOTROL
Junction Box
in Sump
120 Vac
120 Vac
FC Outlet
Valve
NOTICE
• AC line on the FCC box, I/O module,
hook isolation box and dispenser inputs all need to
be on the same electrical phase.
• All conductors #14 THHN
• Switched neutral breaker required for source power
• Make ground connection in accordance with local codes.
If an E-stop is required by national or local codes or a local authority having jurisdiction, the HydrX
Fuel Conditioning Controller (FCC) power must be supplied by a 15 amp circuit that can be
interrupted by the same E-Stop as the FCC pump.
WARNING
FC Inlet
Valve
Pump Control Breaker
Neutral Bar
Ground Bar
15A Switched Neutral
SHUNTED FUEL PANEL
OR
LOAD SIDE OF E-STOP SYSTEM
PC1
Pump control breaker
Neutral bar
G
ro
und bar
I/O module contact load
I/O module coil power
15A switched neutral L1
Inlet valve Hydrx
Outlet valve Hydrx
Isotrol dispenser input hot
15A switched neutral N
Inlet valve neutral
Outlet valve neutral
Isotrol dispenser input neutral
Unused
I/O module LV input RTN
I/O module LV input 12V
I/O module contact line side
I/O module coil neutral
Hydrx system ground
Isotrol ‘S’ terminal
Isotrol ‘ATG’ terminal
Hydrx controller #1
Hydrx controller #2
Hydrx controller #3
Hydrx controller #4
Hydrx controller #5
Hydrx controller #6
Hydrx controller #7
Hydrx controller #8
Hydrx controller #9
Hydrx controller #10
Hydrx controller #11
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
PC1
PC2
PC3
PC4
NEUTRAL
DISPENSER INPUTS
HOT
1A
TB2
TB1
PHASE ON L1 MUST BE SAME AS DEVICE
CONNECTED TO ATG TERMINAL
1
ATG
S
N
L1
L2
M2
M1
2 3
4
5
6
7
8
PC4
PC4
208 TO 240V
TO PUMP
(RELAY
VERSION
ONLY)
FROM SUPPLY
PANEL
(NOTE: L2
TERMINAL
CONNECTS TO
NEUTRAL OF
SUPPLY PANEL
FOR 2-WIRE
MODELS
CASE
Dispenser #1 (Supply & Neutral)
Typical wiring for all dispensers
PC3
PC2