background image

1

Troubleshooting Guide

HydrX

TM

 Fuel Conditioner

Waste Water Tank

Draining Instructions

Notice and Disclaimer

• VEEDER-ROOT SHALL NOT BE LIABLE FOR ERRORS CONTAINED HEREIN OR FOR ANY TYPE OF DAMAGES 

IN CONNECTION WITH THE FURNISHING, PERFORMANCE, OR USE OF THIS PUBLICATION.

• Veeder-Root makes no representation or warranty about the information in this publication. A qualified professional is 

required for service of the components addressed in this publication. 

• The information in this publication cannot be used as a substitution for the knowledge and experience of a qualified 

professional.

• The information contained in this publication is merely for the consideration of a qualified professional, which should make 

their own determination of how to address any issues based on the situation.

• Veeder-Root reserves the right to change system options or features, or the information contained in this publication, at any 

time without notice.

• This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this 

publication may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-

Root.

• Contact TLS Systems Technical Support for additional troubleshooting information at 800-323-1799.

CONTRACTOR CERTIFICATION REQUIREMENTS

Veeder-Root requires the following minimum training certifications for contractors who will install and setup the equipment 

discussed in this manual:

Service Technician Certification (Previously known as Level 2/3):

 Contractors holding valid Technician Certifications are 

approved to perform installation checkout, startup, programming and operations training, system tests, troubleshooting and 

servicing for all Veeder-Root Series Tank Monitoring Systems, including Line Leak Detection.

TLS-4xx Technician Certification:

 Contractors holding valid TLS-450 Technician Certifications are approved to perform 

installation checkout, startup, programming and operations training, troubleshooting and servicing for all Veeder-Root TLS-450 

Series Tank Monitoring Systems, including Line Leak Detection and associated accessories.

Warranty Registrations

 may only be submitted by selected Distributors.

SAFETY WARNINGS AND PRECAUTIONS

FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PRECAUTIONS COULD RESULT IN 

SERIOUS INJURY OR DEATH, AND/OR CAUSE DAMAGE TO PROPERTY, AND THE ENVIRONMENT.
THIS SYSTEM OPERATES NEAR HIGHLY COMBUSTIBLE FUEL STORAGE TANKS.
EXPLOSIVE: 

Fuels and their vapors are extremely explosive if ignited.

FLAMMABLE:

 Fuels and their vapors are extremely flammable.

READ ALL RELATED MANUALS:

 Knowledge of all related procedures before you begin work is important. Read and 

understand all manuals thoroughly. If you do not understand a procedure, ask someone who does.

USE SAFETY BARRICADES:

 Unauthorized people or vehicles in the work area are dangerous. Always use safety cones or barricades, 

safety tape, and your vehicle to block the work area

.

APPROVED CONTAINER: 

Use a nonbreakable, clearly marked container, suitable for collecting and transporting hazardous 

fuels during service.

NOTICE: 

Indicates information considered important, but not hazard-related.

WARNING:

 Indicates a hazardous situation that, if not avoided, could result in death or serious injury.

GENERAL PRECAUTIONS

To ensure proper installation, operation, and continued safe use of this product:
1. Read and follow all instructions in this manual, including all safety procedures, local and federal guidelines.
2. Have equipment installed by a contractor trained in its proper installation and in compliance with all applicable codes 

including: National Electrical Codes 70 and 30A; federal, state, and local codes; and other applicable safety codes.

3. Substitution of components may impair intrinsic safety.
4. Do not modify or use service parts other than those provided by Veeder-Root.

Reference Documents: 

Manual 577014-466, 577014-446, 577014-492, 577014-493

Suggested Equipment:

 V-R kit# 330020-880 and approved 5-gallon container to receive fuel contaminated waste water.

Manual No:

 

577014-474 

l

 

Revision:

 

B

Отзывы: