16

ATG EDIM Comm Port Setup

The ATG EDIM Comm port settings must be configured for Insite360 Connect operation. At the console’s front 
keypad press the MODE key until the display reads 

Diag Mode

 in the display. 

Press FUNCTION until you see the message:

Press STEP until you see the message:

Press ENTER to display the message:

The first two characters in this display ‘X1’ indicate the DIM type in Comm slot 1: ‘M’ for MDIM module; ‘E’ for any 
other DIM type. You are looking for the EDIM Comm board (an E type DIM) so If this is not the Comm board to 
which you connected the Insite360 Connect, press TANK/SENSOR until the correct Comm board displays, e.g., 
if the Insite360 Connect is connected to the EDIM in slot 3 (3rd from left), then you press TANK/SENSOR until 
you see E3:)

Press STEP until you see the message: 

The correct selection depends on the BIR reporting units for your site and if your site has a Gilbarco Protocol or 
VR Protocol DIM. See Table 3 below for the correct EDIM Data String entry for Insite360 Connect. Table 4 is for 
reference and defines the letters used in EDIM Data String entries.

SYSTEM DIAGNOSTIC

PRESS <STEP> TO CONTINUE

DIM DIAGNOSTIC DATA

PRESS <ENTER>

X1:SWARE#XXXXXX-XXX-X

CREATED - YY-MM-DD-HH-MM

DISP. MODULE DATA STRING

EDIM X: 

Содержание FUELQUEST Insite360 Connect

Страница 1: ...Manual No 577014 326 Revision B Insite360 Connect Installation And Setup Manual ...

Страница 2: ...ed No part of this publication may be photocopied reproduced or translated to another language without the prior written consent of Veeder Root This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired...

Страница 3: ...Ports And LEDs 3 Figure 2 Scenario 1 Insite360 Connect Hookup TLS 350 With DB9 Serial Port Connection 6 Figure 3 Scenario 1 Insite360 Connect Hookup TLS 300 350 With DB25 Serial Port Connection 7 Figure 4 Scenario 2 Insite360 Connect Hookup TLS 350 With EDIM Connection To POS 9 Figure 5 Scenario 3 Insite360 Connect Hookup TLS 3XX With DB25 Serial Comm Port And POS 11 Figure 6 Scenario 3 Insite360 ...

Страница 4: ...precautions that must be followed when installing the equipment described herein Related Manuals 576013 623 TLS 3XX Setup Manual 577013 776 TCP IP Interface Module Installation Guide CAUTION Indicates a hazardous situa tion which if not avoided could result in minor or moder ate injury READ ALL RELATED MANUALS Knowledge of all related procedures before you begin work is important Read and understa...

Страница 5: ... Description 330020 833 Insite360 Connect cables and mounting fasteners for ATG with no POS connection 330020 834 POS Upgrade kit additional cables and adapters for ATG with POS connection Ethernet Port Charging electronic devices with the Insite360 Connect s unused USB ports could cause overheating and equipment damage DO NOT charge electronic devices with these unused USB ports USB 1 To ATG USB ...

Страница 6: ...ots in back of the unit onto mounting screws 1 and slide down 2 3 Install wall anchors 1 2 2 Remove the paper cover from the adhesive side of one of the self fastening strips and press it onto the cleaned wall surface 1 Open one alcohol packet from the kit and clean the back of the Insite 360 Connect and the wall surface where you want to attach the unit 3 Remove the paper cover from the adhesive ...

Страница 7: ...USB to Serial Adapter cable connected to either the DB9 female DB9 male 6 cable Figure 2 or the DB9 female DB25 male 6 cable Figure 3 depending on the ATG s available serial port connector type The USB to Serial Adapter cable s thumb screws need to be fully threaded into the 6 cable s standoffs and the 6 cable s thumb screws need to be fully threaded into the RS232 serial port 2 Connect the Ethern...

Страница 8: ...LS 5792 GALS 4792 GALS 4194 GALS 41 02 INCHES 0 GALS 0 00 INCHES 65 0 DEG F 9038 GALS 962 GALS 0 GALS 8950 GALS 81 37 INCHES 28 GALS 1 37 INCHES 74 9 DEG F ATG TLS 350 POS 9 pin to 9 pin Null modem cable NOTICE To ensure successful communication for consoles with an available DB9 RS232 port do not connect the USB to Serial adapter cable directly to the console s serial port NOTICE Ethernet Power U...

Страница 9: ...4208 GALS 5792 GALS 4792 GALS 4194 GALS 41 02 INCHES 0 GALS 0 00 INCHES 65 0 DEG F 9038 GALS 962 GALS 0 GALS 8950 GALS 81 37 INCHES 28 GALS 1 37 INCHES 74 9 DEG F ATG TLS 300 or TLS 350 POS To TLS 350 DIM Requires optional BIR USB to Serial adapter cable 9 pin to 25 pin Null modem cable Local Area Network Ethernet Power USB 2 USB 1 USB 4 USB 3 MODEL P N 330020 833 DEVICE S N MAC Address GVR FMS Si...

Страница 10: ...fs 3 Connect the DB9M end of the USB to Serial Adapter cable 330020 834 kit to the DB25 female DB9 female mini gender changer adapter connected to the POS cable The USB to Serial Adapter cable s thumb screws need to be fully threaded into the gender changer adapter s standoffs 4 Connect the USB end of the USB to Serial Adapter cable to the Insite360 Connect s USB port 2 5 Connect the Insite360 Con...

Страница 11: ... GASOLINE VOLUME ULLAGE 90 ULLAGE TC VOLUME HEIGHT WATER VOL WATER TEMP 4208 GALS 5792 GALS 4792 GALS 4194 GALS 41 02 INCHES 0 GALS 0 00 INCHES 65 0 DEG F 9038 GALS 962 GALS 0 GALS 8950 GALS 81 37 INCHES 28 GALS 1 37 INCHES 74 9 DEG F POS USB to Serial adapter cable ATG TLS 350 Local Area Network Ethernet Power USB 2 USB 1 USB 4 USB 3 MODEL P N 330020 833 DEVICE S N MAC Address GVR FMS Site ID Con...

Страница 12: ...are included in the 330020 834 kit The POS cable s thumb screws if equipped need to be fully threaded into the gender changer adapter s standoffs 3 Connect the DB9M end of the USB to Serial Adapter cable 330020 834 kit to the DB9 female end of the mini gender changer adapter connected to the POS cable The USB to Serial Adapter cable s thumb screws need to be fully threaded into the gender changer ...

Страница 13: ...ASOLINE VOLUME ULLAGE 90 ULLAGE TC VOLUME HEIGHT WATER VOL WATER TEMP 4208 GALS 5792 GALS 4792 GALS 4194 GALS 41 02 INCHES 0 GALS 0 00 INCHES 65 0 DEG F 9038 GALS 962 GALS 0 GALS 8950 GALS 81 37 INCHES 28 GALS 1 37 INCHES 74 9 DEG F POS USB to Serial adapter cable ATG TLS 300 or TLS 350 Local Area Network Ethernet Power USB 2 USB 1 USB 4 USB 3 MODEL P N 330020 833 DEVICE S N MAC Address GVR FMS Si...

Страница 14: ...LS 4194 GALS 41 02 INCHES 0 GALS 0 00 INCHES 65 0 DEG F 9038 GALS 962 GALS 0 GALS 8950 GALS 81 37 INCHES 28 GALS 1 37 INCHES 74 9 DEG F POS USB to Serial adapter cable ATG TLS 350 Local Area Network NOTICE To ensure successful communication for consoles with an available DB9 RS232 port do not connect the USB to Serial adapter cable directly to the console s serial port NOTICE MINI GENDER CHANGER E...

Страница 15: ...m device activation If the activation does not complete automatically as indicated by the status LEDs please contact Insite360 FuelQuest Fuel Management Services at 800 997 7725 If the GVR FMS Site ID number on the Insite360 Connect s label is blank indicating the device has not already been commissioned for your site See Figure 7 please contact Insite360 FuelQuest Fuel Management Services at 800 ...

Страница 16: ... ATG communication Check connection between Insite360 Connect and ATG 3 blink pattern No POS communication Check connection between Insite360 Connect and POS 4 blink pattern Insite360 Connect not registered Check label on front of Insite360 Connect for correct GVR FMS Site ID and address Call 800 997 7725 if missing 5 blink pattern Insite360 Connect software download in progress The blinking patte...

Страница 17: ...ssage The system labels the communications module in the leftmost slot as COMM BOARD 1 If this is not the Comm board to which you connected the Insite360 Connect press TANK SENSOR until the Insite360 Connect connected Comm board displays The correct Baud Rate for Insite360 Connect is 9600 If the rate shown on the display is 9600 press STEP If the Baud Rate is incorrect press CHANGE until you see t...

Страница 18: ...oose the correct Stop Bit setting press CHANGE and press ENTER to confirm your choice The system displays the message Press STEP to continue The choices are 7 or 8 The correct Data Length selection for Insite360 Connect is 7 If the Data Length shown in the message is 7 press MODE to exit the System Setup mode To choose the correct Data Length press CHANGE and press ENTER to confirm your choice The...

Страница 19: ...t the Comm board to which you connected the Insite360 Connect press TANK SENSOR until the correct Comm board displays e g if the Insite360 Connect is connected to the EDIM in slot 3 3rd from left then you press TANK SENSOR until you see E3 Press STEP until you see the message The correct selection depends on the BIR reporting units for your site and if your site has a Gilbarco Protocol or VR Proto...

Страница 20: ...d into a VR protocol EDIM Press Mode to exit the System Setup mode Table 3 EDIM Data String Entries For Insite360 Connect EDIM Protocol EDIM Data String Selection For U S Units For Metric Units For Imperial Units VR Protocol G No entry leave blank I Gilbarco Passport B9OHVG B9OHV B9OHVI Table 4 DIM Parameter Definitions Reference Baud Parity Stop Bits Data Bits Conversion String Rate String Type S...

Страница 21: ...he Insite360 Connect using an Ethernet crossover cable not provided Power up the Insite360 Connect and use a browser to connect to the static IP address http 192 168 101 1 8888 for the Insite360 Connect For a successful connection because you are directly connecting two devices the Insite360 Connect and a laptop you must use an Ethernet crossover cable not provided The following settings are avail...

Страница 22: ... information to the cloud it should be replaced with a similar device that has been pre configured and registered with the GVR Cloud in the same way the original device was Any information recorded on the old device that was not sent to the Cloud may be lost or duplicate data may be sent to the GVR Cloud Veeder Root Baud Rate 9600 Data Bits 7 Parity Odd Stop Bits 1 Save Network POS Default BIR Pro...

Страница 23: ...in desired location Drill two pilot holes at center of two marks for two mounting screws or drywall anchors as required Weight of unit and related cables adaptors is less than 1 pound Appendix A Insite360 Connect Mounting Screw Hole Template Cut along line to remove Template 1 6 40mm Ref 1 25 32mm Ref ...

Страница 24: ...For technical support sales or other assistance please visit www veeder com ...

Отзывы: