 Installation

Console Wiring Precautions

10

4.

Do 

NOT

 terminate shield or drain wire in the field junction box. Ground shield and drain wires at console only.

5.

Place the bag with the resin sealed wiring connections in the junction box. Replace and tighten the junction 
box cover.

DIRECT BURIAL CABLE

When using direct burial cable for sensor-to-console wiring runs, the sealing materials and procedure are 
completely different. Refer to the Direct Burial Cable Installation Manual 576013-858.

Figure 5.  Epoxy Sealing Probe And Sensor Field Connections

Console Wiring Precautions

IMPORTANT - You must read and understand this information prior to wiring devices to console.

During programming, the devices wired to each connector are identified and stored in 
system memory. If a device is later removed and reconnected to a different set of con-
nectors, the system will not properly recognize the data being received. Once a device 
has been wired to certain connectors on a USM or I/O Module and the system has 
been programmed, the wires from that device may not be relocated to other connec-
tors without reprogramming that device.

8

79-

38

.ep

s

To con

s

ole

Tie wr

a

p

Wire n

u

t

s

From pro

b

e,

s

en

s

or, or

tr

a

n

s

d

u

cer

A

C

B

M

a

ke 

su

re th

a

the end

s

 of c

ab

le 

s

he

a

thing 

a

re 

sub

-merged in 

s

e

a

l

a

nt

nttt

nt

In

s

truction

s

:

NOTE: When temper

a

t

u

re i

s

 

b

elow 50°F (10°C), keep 

re

s

in in 

a

  w

a

rm pl

a

ce prior to mixing (e.g., in 

a

in

s

ide pocket next to 

b

ody).

1. Open epoxy 

s

e

a

l

a

nt p

a

ck

a

ge, 

a

nd remove re

s

in p

a

k.

2. Holding re

s

in p

a

as

 

s

hown in A, 

b

end p

a

a

long 

long length.

3

. A

s

 

s

hown in B, firmly 

squ

eeze the RED 

S

IDE of the 

re

s

in, forcing it thro

u

gh the center 

s

e

a

a

nd into 

BLACK 

S

IDE. 

4. Mix  thoro

u

ghly to 

a

 

u

niform color 

b

squ

eezing 

content

s

 

ba

ck 

a

nd forth 25-

3

0 time

s

.

5. 

Squ

eeze mixed, w

a

rm re

s

in into one end of 

ba

a

nd 

c

u

toff other end.

6. 

S

lowly in

s

ert wiring connection

s

 into 

s

e

a

ling p

a

ck 

u

ntil they fit 

s

n

u

gly 

a

g

a

in

s

t the oppo

s

ite end 

as

 

s

hown in C.

7. Twi

s

t open end of 

ba

a

nd 

us

e tie wr

a

p to clo

s

e it off 

a

nd po

s

ition the tie wr

a

pped end 

u

u

ntil the re

s

in 

jell

s

.

CAUTION: 

Epoxy 

s

e

a

l

a

nt i

s

 irrit

a

ting to eye

s

, re

s

pir

a

tory 

s

y

s

tem, 

a

nd 

s

kin. C

a

n c

aus

a

llergic 

s

kin re

a

ction. Cont

a

in

s

: epoxy re

s

in 

a

nd Cyclo

a

liph

a

tic epoxyc

a

r

b

oxyl

a

te. 

Precaution

s

:

 We

a

su

it

ab

le protective clothing, glove

s

, eye, 

a

nd 

f

a

ce protection. U

s

e only in well ventil

a

ted 

a

re

as

. W

as

thoro

u

ghly 

b

efore e

a

ting, drinking, or 

s

moking.

NOTICE

Содержание DEF

Страница 1: ...Manual No 577014 344 Revision C Installation Manual DEF Recirculation Control...

Страница 2: ...f any damages and or shortages within 30 days of receipt of the shipment as stated in our Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Fax Bill of Lading to V R Customer Service at 800 234 5...

Страница 3: ...ensor Field Wiring 9 Sealing Field Connections 9 Wiring Run Through Rigid Conduit 9 Direct Burial Cable 10 Console Wiring Precautions 10 Connecting Sensor Wiring To The Console 11 Figures Figure 1 DEF...

Страница 4: ...dependently or concurrently with the DEF pump Figure 1 DEF Fluid Temperature Monitoring Components DEF Dispenser DEF Dispenser Heat Trace manufacturer required GFI EPD circuit breaker per NEC Article...

Страница 5: ...install intrinsically safe apparatus use the specific control drawing that appears on the nameplate of the applicable associated apparatus ATG Console The control drawings contain information related...

Страница 6: ...Operator s Manual CLASS I Division 1 Group D CLASS 1 Zone 0 Hazardous Location Intrinsically Safe Apparatus DEF Temperature Sensor Intrinsically Safe Wiring White Brown Black Black I S Rigid Conduit...

Страница 7: ...o alert you to important safety hazards and precautions GENERAL Ensure that all local council and regulations are complied with Also ensure that all recognized safety codes are followed EXPLOSIVE Fuel...

Страница 8: ...energy limited system This system makes the sensors suitable for use in hazardous locations Sensor wiring is intrinsically safe only when connected to the TLS console All sensor wiring must be contai...

Страница 9: ...service this equipment in accordance with these codes regulations and standards may lead to legal citations with penalties or affect the safe use and operation of the equipment ISO STANDARD FOR DEF Th...

Страница 10: ...must be observed Keep fluid away from the motor cable Follow internal instructions Wear protective clothing face and breathing protection protective gloves etc De ploy safety barricades around work a...

Страница 11: ...d install it into the bushing 4 Loosen the nut on the tube fitting and insert the temperature sensor into the tube fitting enough but not more than 6 to ensure the 1 4 diameter section of the sensor i...

Страница 12: ...ugh the seal off box the conduit attaching the junction box to the seal off box and into the junction box 2 Using wire nuts connect the two wires from the sensor to the two wires coming from the conso...

Страница 13: ...nec tors without reprogramming that device 879 38 eps To console Tie wrap Wire nuts From probe sensor or transducer A C B Make sure that the ends of cable sheathing are sub merged in sealant nt t t nt...

Страница 14: ...sensor is NOT grounded 3 Write in the device name for each wire connection on the connector block in the module s wiring label attached to the inside of the door 4 Make sure that you loop the wire nea...

Страница 15: ...m Relay Contact Ratings 120 240 Vac 5A 30 Vdc 5A Fuse ratings 5A 250 Vac Type T Slo Blo TLS 450PLUS TLS XB TLS4 Control Of DEF Piping Heat Trace Circuitry If Required HV Relay Outputs Control Of DEF P...

Страница 16: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: