Appendix B
Datalogger Site Connection and Initialization
B-6
Figure B-4. Ethernet Port Setup
8.
Click on “Serial Port Setup” (1) and in the “Device” field, select “SERIAL 2:”. Use this connection for the
connection to the POS, and enter “POS” for the Label. Set the correct communications parameters for the
POS using the drop down menus. Click the “Save” button to keep these settings (see example in Figure B-5).
.
Figure B-5. Serial Port Setup, SERIAL 2-POS
9.
Go to the “DLSetup” application by clicking on white arrow in blue circle top center of screen (see Figure B-
6), and under “System Setup”, click on “ATG Commands (1 in Figure B-6)”. Then click on the “+ Add New
Command” text at top right of screen (2 in figure). When the Add Command dialog box appears enter the
command “i@C300”, add the Description “DIM_EVENTS”, set the Repeat Interval to “60” (3 in figure) and
click Save (4 in figure).
Click this arrow to switch between the
GeneralSetup and DLSetup applications
1
2
3
ETH 1
Select EDIM
Recommended Baudrate
1
Select SERIAL 2
POS
Select POS