Vac System Field Wiring - TLS-450PLUS Console
Connecting Pump Control to TLS-450PLUS Console
5-2
FOR SITES WITHOUT PLLD LEAK DETECTION
An IOM module is required in the TLS Console for Vac Sensor pump control if there is no PLLD. Refer to Figure 5-
2 for Red Jacket pump control wiring and to Figure 5-3 for non-Red Jacket pump control wiring.
Figure 5-2.- Red Jacket STP Control And Pump Sense Inputs
Pu
m
p I
n
Pu
m
p Retu
rn
WARNING
OFF
DISCONNECT, LOCK OUT, AND TAG POWER
TO THE STP/SELF SERV SYS./DISPENSER
AT THE POWER PANEL BEFORE CONNECTING
WIRING TO THIS EQUIPMENT.
WARNING
OFF
Powe
r
Pa
n
el
110 Vac
AC Ne
u
tr
a
l
Self-Se
r
ve Syste
m
o
r
Dispe
n
se
r
switched
hot 120 Vac
P
um
p Co
n
t
r
ol
Powe
r
Pa
n
el
F
r
o
m
Beake
r
Pa
n
el
Pu
m
p Powe
r
To
Sub
m
e
r
sible
Pu
m
p
P
r
oduct
Relay
Red Jacket
Remote Control Box
M2 M1 N L1 L2
S
2
Ri
g
id Co
n
duit (e
n
te
r
s Co
n
sole
th
r
ou
g
h a Powe
r
Bay k
n
ockout)
RTN
12V
1
2
3
4
1
2
3
4
5
1
2
3
4
5
RTN
12V
RTN
12V
RTN
12V
Maximum A
C
Input Ra
tings
120/24
0 V
ac, 0.10 A
Maximum Relay Contact Ra
tings
120/24
0 V
ac 5A, 3
0
V
dc 5A
Fuse Ra
tings 5A, 25
0 V
ac T
ype T (Slo-Blo)
Maximum External Contact
Closure Circuit Ra
tings
12 V
dc, 0.0
15 A