Setting of parameters 

The TLC3-FCR is an 

intelligent 

controller and can be adapted to fit perfectly into your fan coil application. The control 

operation is defined by parameters. The parameters are set during operation by using the standard operation terminal.  
The parameters are password protected. There are two levels of parameters: User operation parameters for access 

control settings and Expert parameters for control functions and unit setup. The passwords for user levels and expert 

levels are different. Only control experts should be given the control parameter password.  
The parameters can be changed as follows: 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display will indicate the firmware version in 

the upper large digits and the revision in the lower small digits. Pressing any key will show: CODE. 

2.

 

Select a password using UP or DOWN buttons. Select 009 in order to get access to the user parameters, 241 

for controls parameters.  

Press OPTION after selecting the correct password.  

3.

 

Once logged in, the parameter is displayed immediately 

4.

 

Select the parameters with the UP/DOWN keys. Change a parameter by pressing the OPTION key. The MIN 

and MAX symbols show up and indicate that the parameter may be modified now. Use UP and DOWN key to 

adjust the value. 

5.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

6.

 

Press the POWER key again so as to leave the menu. The unit will return to normal operation if no key is 

pressed for more than 5 minutes. 

User Parameters 

Parameter  Description 

Range 

Standard 

UP 00 

Enable change of operation modes  

ON, OFF 

ON (Enabled) 

UP 01 

Enable change of set points 

ON, OFF 

ON (Enabled) 

UP 02 

Enable manual control of fan speeds 

ON, OFF 

ON (Enabled) 

UP 03 

Enable change of heating/cooling mode 

ON, OFF 

W00: ON (Enabled) 
W01: OFF 
(Disabled) 

UP 04 

Enable access to Time programs 

ON, OFF 

ON (Enabled) 

UP 05 

State after power failure:  
0 = Switched OFF, 1 = Switched ON, 2 = state before power failure 

0, 1, 2 

UP 06 

Enable Economy (unoccupied) Mode.  
Shift the set point to a lower temperature in winter or higher temperature 
in summer in order to save energy. Economy mode may be activated 
through the POWER button, or with the external input (typically for key 
card switches in hotel rooms or motion detectors for meeting rooms.) 

ON, OFF 

ON (Economy ) 

UP 07 

Celsius or Fahrenheit, Select ON for Fahrenheit, OFF for Celsius 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibration value of temperature sensor . This value is calibrated at 
manufacturing of the thermostat. If required it is possible to shift the 
temperature 

–10° to +10° in 0.1° K steps.  

-

10…10 

UP 09 

Enable Frost Protection.  
Activates the output independent of operation mode when the control 
temperature drops below 5°C or 41°F. The controller returns to normal 
operation when the temperature increases above 10°C or 50°F. 

ON, OFF 

W00 = ON  

(Frost Protection) 

W01 = OFF 

(No Frost Protection) 

UP 10 

Select contents of Large LCD display in standard mode: 
00 = OFF 
01 = Setpoint 
02 = Temperature Sensor 
03 = Output Fan Speed 
04 = Clock 

0…4 

02  

Temperature 

UP 11 

Select contents of small LCD display in standard mode 
(use table of UP 10) 

0…4 

04 Deluxe:  

show clock 

01 Standard:  

show setpoint 

UP 12 

Contents of vertical bar in standard mode 

OFF  

= Fan Speed 

ON  = Control output 

ON, OFF 

OFF (FAN) 

UP 13 

Deluxe only 

Clock display type:  
OFF  = Show 24hour clock 
ON   = Show 12hour clock (AM, PM) 

ON, OFF 

OFF (24h) 

UP 14 

Deluxe only 

Reset: applies when the unit is manually switched on, while in scheduled 
off mode. The unit will switch automatically back to the scheduled mode 
when the reset time expires.  

= Reset of override mode is not active.  

1…255 = delay in minutes to switch off device 

0…255 

60 (Min) 

 
 

Содержание TLC3-FCR

Страница 1: ...ngle duct systems with up to one binary output for auxiliary heating and cooling devices Air Water Systems Induction units fan coil units for 2 pipe systems with one binary output for a spring return valve General Description The TLC3 FCR is a stand alone electronic fan coil controller with one control loop The TLC3 FCR features 1 internal NTC temperature sensor and four binary outputs Relays A de...

Страница 2: ...3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls EN 60 730 1 EN 60 730 2 9 Electromagnetic compatibility for domestic sector Emissions EN 60 730 1 Immunit...

Страница 3: ... 2 off the surface of the mounting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight ...

Страница 4: ...kup function to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Error me...

Страница 5: ... d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One bar on the right side indicates the first switching event Press UP DOWN to select action for first switching event No switching event not active OFF switches unit off Reset UP17 active if switched to ON...

Страница 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to change stale...

Страница 7: ...oints ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time programs ON OFF ON Enabled UP 05 State after power failure 0 Switched OFF 1 Switched ON 2 state before power failure 0 1 2 2 UP 06 Enable Economy unoccupied Mode Shift the set point to a lower temperature ...

Страница 8: ...on in cooling mode 0 10 0 C 20 0 F 1 0 C 2 F FC 07 Switching Hysteresis is the difference between switching on and switching off A small hysteresis will increase the number of switching cycles and thus the wear on fan and relays contacts 0 10 0 C 20 0 F 0 5 C 1 F FC 08 Mold Protection In mold protection the fan keeps running independent of temperature as long as the unit is switched on ON OFF OFF ...

Отзывы: