Control Configuration for PWM – 3-point floating mode 

FC 14 

P – band heating X

PH

 

0-10.0°C (20.0°F) 

2.0°C (4.0°F) 

FC 15 

P – band cooling X

PC

 

0-10.0°C (20.0°F) 

2.0°C (4.0°F) 

 

Proportional control(P-band)  

The proportional control function calculates the output based on the difference between setpoint and measured 

value. The proportional band (P-band) defines the difference between setpoint and measured value which will 

result in a 100% output. Setting the proportional band to 0 disables proportional control. 

 

Output configuration 

FC 16 

Output setting, Binary, PWM or 3-point:  
0 = Binary or PWM (DO4 Heating, DO5 Cooling) 

1 = 3-point binary output (DO4 open, DO5 close) 

2 = 3-point floating output (DO4 open, DO5 close) 

0…2 

Binary / PWM 

FC 17 

Running Time in 3-point mode 

0…255 s 

90 s 

FC 18 

PWM cycle timeheating, 0 disables PWM mode 

0…100 min 

FC 19 

PWM cycle time cooling, 0 disables PWM mode 

0…100 min 

 

3-point floating:  

For floating point outputs the running time of the actuator used needs to be specified with FC17. Running time is 

defined as the time required for the actuator to run from fully open to fully closed and vice versa. Actuators with a 

fixed running time are recommended. Once fully open or fully closed the running time for the actuator is extended 

for a full run-time cycle. This will allow the actuator position to be synchronized in case it has been moved during 

off time or an actuator with variable running time was used.

 

 

Pulse With Modulation (PWM) 

In PWM mode the digital output will be switched on/off once per cycle. The on and off times are calculated 

according to the control sequence.

 

 

 

Содержание TLC3-FCR-2R

Страница 1: ...lves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2T is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC temperature sensor input and five binary outputs Three outputs control a fan with low medium and high fan speeds Two binary outputs may be used to control either two spring return or thermal valves or...

Страница 2: ...midity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls EN 60 730 1 EN 60 730 2 9 Electromagnetic compati...

Страница 3: ...ounting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance can be felt This...

Страница 4: ...ion to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Error messages Fo...

Страница 5: ...options d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One bar on the right side indicates the first switching event Press UP DOWN to select action for first switching event No switching eventnot active OFF switches unit off Reset UP17 active i...

Страница 6: ... the temperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be us...

Страница 7: ...d UP 01 Enable change of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time programs ON OFF ON Enabled UP 05 State after power failure 0 Switched OFF 1 Switched ON 2 state before power failure 0 1 2 2 UP 06 Enable Economy unoccupied Mode Shift the set...

Страница 8: ...F FC 05 Switching Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the auto fan speed function in cooling mode 0 10 0 C 20 0 F 1 0 C 2 F FC 07 Switching Hysteresis is the difference between switching on and switching off A small hysteresis will increase the number of swi...

Страница 9: ...inary output DO4 open DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle timeheating 0 disables PWM mode 0 100 min 0 FC 19 PWM cycle time cooling 0 disables PWM mode 0 100 min 0 3 point floating For floating point outputs the running time of the actuator used needs to be specified with FC17 Running time is defined...

Страница 10: ...TLC3 FCR 2T U Engineering Manual Doc 70 00 0203 V3 0 Date 20121119 Vector Controls GmbH Switzerlandmailto info vectorcontrols com Page 10 Subject to alteration Notes ...

Отзывы: