Manual heat – cool change 

To manually change heating or cooling mode press the OPTION key for more than 2 seconds. Access to manual heat – 
cool change may be disabled by parameters. 

For standard models: Press OPTION > 2 sec. SEL and H-C is displayed.  
For deluxe models: Press OPTION > 2 sec. SEL and current time is displayed.  
 

Press UP key twice. SEL and H-C is displayed. 

Press OPTION again to toggle Heating, Cooling and Fan only modes.  

SEL 
  H-C 

 

 

 

Clock operation  

The deluxe model contains a quartz clock with battery back-up. Up to 4 time schedules with each 4 mode changes 
based on time and day of the week may be programmed. A blinking clock indicates that the time has not been set or if 
the unit was without power for longer than 48 hours. The time needs to be set to allow time schedules to operate.  

Clock setup 

Press OPTION > 2 sec. SEL and current time displayed 
Press OPTION < 2 sec. to change time, 

Minutes blink: UP/DOWN to changes, OPTION to save,  
Hours blink: UP/DOWN to changes, OPTION to save,  

Press OPTION to save time, 

DAY1 blinks: UP/DOWN to change, OPTION to save 

SEL 
  00:00  
  DAY1 (Mon) 

 

Creating time schedules  

Step 1: Selection and enabling of time schedules 
Press OPTION > 2 sec. SEL and current time displayed 
Press UP:  

SEL and PRO displayed, clock symbol blinks 

Press OPTION:  

PRO1 shows with 1 blinking. UP/DOWN select time schedule group 

Press OPTION 

OFF/ ON blinks, UP/DOWN to change, OPTION to save  

SEL 
  PRO 

  

 

Pro1-Pro4 
  OFF/ON 

   

Step 2: Select weekdays 
This time schedule will be active during the selected weekdays  
Press UP/DOWN to step through available options:  

d1-7, d1-6, d1-5, d6-7, day1, day2, day3, day4, day5, day6, day7 
Day 1 stands for Monday, day 2 for Tuesday and so forth 

Press OPTION to save day selection 

   

Pro1 
  d1-7

  

Step 3: Selected action of first switching event  
One bar on the right side indicates the first switching event 
Press UP/DOWN to select action for first switching event: 

No =   switching event not active 

OFF =   switches unit off, Reset (UP17) active if switched to ON manually.  

Eco =   sets operation mode to On and Economy (Not occupied),  

  

reset (UP17) active if set to comfort manually 

On =   sets operation mode to On and Comfort (Occupied) 

Uni =   University mode, Reset (UP17) not active if manually activated 

Press OPTION to select switching time of first event 

  

Pr01 

    no 

 
 

 Step 4: Selected time of first switching event  
Press UP/DOWN to select switching time: 

Select switching time 00:00 to 23:45 in 15-minute steps  

Press OPTION to complete and select action of second switching event 

  

Pr01 

   08:00

 

Step 5: Select actions and time of switching event 2 - 4  
Repeat Step 3 and Step 4 for the remaining switching events.  

If a switching event is not needed, set it to “no” 
The bars on the right side indicate number of switching event 

After completing the 4

th

 switching event, the process returns to the selection of the time schedule on step 1.  

  

Pr01 

   08:00

 

 

Î

 

UNI: University mode: This switching mode is used for rooms such as lecture rooms and auditoriums that might 
be occupied during a certain time. During this time the reset is not active. The unit will not start itself when UNI 
mode is active. It still needs to be manually activated. This is to avoid unnecessary heating or cooling of such 
rooms while they are not occupied.  

Î

 

A blinking clock indicates that the time needs to be set. Time programs will not operate if the time is not defined. 
See chapter operation, advanced settings for instructions on how to set the time. 

Î

 

Access to time schedules may be disabled with UP-04 

Содержание TLC3-FCR-2

Страница 1: ...ndividual room control for hotel rooms meeting rooms etc PWM or On Off Control of 2 spring return valves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2 is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC temperature sensor input and five binary outputs Three outputs control a fan with low medium and high...

Страница 2: ...chanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls EN 60 730 1 EN 60 730 2 9 Electromagnetic compatibility fo...

Страница 3: ... Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance can be felt This is normal Do n...

Страница 4: ...cordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Error messages Following error con...

Страница 5: ...1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One bar on the right side indicates the first switching event Press UP DOWN to select action for first switching event No switching event not active OFF switches unit off Reset UP17 active if switched to ON m...

Страница 6: ...e changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to change stale air duri...

Страница 7: ...nge of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time programs ON OFF ON Enabled UP 05 State after power failure 0 Switched OFF 1 Switched ON 2 state before power failure 0 1 2 2 UP 06 Enable Economy unoccupied Mode Shift the set point to a lower ...

Страница 8: ...g Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the auto fan speed function in cooling mode 0 10 0 C 20 0 F 1 0 C 2 F FC 07 Switching Hysteresis is the difference between switching on and switching off A small hysteresis will increase the number of switching cycles an...

Страница 9: ...pen DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle time heating 0 disables PWM mode 0 100 min 0 FC 19 PWM cycle time cooling 0 disables PWM mode 0 100 min 0 Î 3 point floating For floating point outputs the running time of the actuator used needs to be specified with FC17 Running time is defined as the time re...

Страница 10: ...TLC3 FCR 2 Engineering Manual Doc 70 00 0202 V3 0 Date 20111027 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes ...

Отзывы: