background image

 

 

TLC3-FCR-2 Engineering Manual

 

 

Doc: 70-00-0202, V3.0 Date: 20111027 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

TLC3-FCR-2  
Intelligent Fan Coil controller 

Features 

 

The PWM and 3-point floating control option reduces room 
temperature fluctuations and energy consumption 

 

Low power energy consumption: < 1W per unit 

 

Temperature control for 2- and 4-pipe fan coil systems.  

 

Automatic fan control for three stage fans.  

 

Cost saving option with Economy functionality and set point 
limitations 

 

Control for single stage heating, cooling and fan only 
operation modes 

 

Password protected programmable user and control 
parameters 

o

 

Setpoint range limitation 

o

 

Access control for setpoints, fan speeds and mode 
change 

o

 

Access control for heat/cool change and time 
programs 

o

 

Select your display contents 

o

 

Selectable behavior after return from power failure 

 

Temperature display in Celsius or Fahrenheit 

Deluxe Version: 

 

Clock and time schedule functions with power failure protection 

 

Blue backlight for LCD 

 

Infrared remote controller option:  
With special features for Boost and delayed switching on or off 

Applications 

 

Air Only Systems:  

o

 

Constant Air Volume systems with three stage fans for single or dual duct systems 

 

Air/Water Systems:  

o

 

Fan Coil units for 2-pipe or 4-pipe systems  

o

 

radiator control, chilled ceiling 

 

Simple individual room control for hotel rooms, meeting rooms, etc.  

 

PWM or On-Off-Control of 2 spring return valves or 3-point on-off or floating control of one 3-point valve.  

General Description 

The TLC3-FCR-2 is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR-2 features 1 NTC 
temperature sensor input and five binary outputs. Three outputs control a fan with low, medium and high fan speeds. 
Two binary outputs may be used to control either two spring return or thermal valves or one three point floating valve.  
A detailed parameterization is possible with the use of a simple configuration routine. The TLC3-FCR-2 can be 
configured using the standard operation terminal. No special tools or software is required.  

Ordering 

Item Name 

Item code 

Variant 

Power 

Features 

TLC3-FCR-2-24 
TLC3-FCR-2-24-W01 

40-10 0130 
40-10 0130-01 

Standard 
Cooling only 

24VAC/DC 

Fan coil controller with:  
1 TI int 
3 DO (Relay) Fan control 
2 DO (Relay) Binary valve control 

TLC3-FCR-2-D-24 
TLC3-FCR-2-D-24-W01 

40-10 0135 
40-10 0135-01 

Deluxe 
Cooling only 

TLC3-FCR-2-D-230 
TLC3-FCR-2-D-230-W01 

40-10 0119 
40-10 0119-01 

Deluxe 
Cooling only 

230VAC 

Fan coil controller with:  
1 TI int 
3 DO (Relay) Fan control 
2 DO (TRIAC) Binary valve control 

TLC3-FCR-2-230 
TLC3-FCR-2-230-W01 

40-10 0118 
40-10 0118-01 

Standard 
Cooling only 

Selection of valve actuators and fans 

Binary auxiliary devices: E.g. fans and on/off valves.  Observe switching power as detailed under technical 
specifications! Do not connect more than one fan coil unit to one controller. 

Содержание TLC3-FCR-2

Страница 1: ...ndividual room control for hotel rooms meeting rooms etc PWM or On Off Control of 2 spring return valves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2 is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC temperature sensor input and five binary outputs Three outputs control a fan with low medium and high...

Страница 2: ...chanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls EN 60 730 1 EN 60 730 2 9 Electromagnetic compatibility fo...

Страница 3: ... Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance can be felt This is normal Do n...

Страница 4: ...cordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Error messages Following error con...

Страница 5: ...1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One bar on the right side indicates the first switching event Press UP DOWN to select action for first switching event No switching event not active OFF switches unit off Reset UP17 active if switched to ON m...

Страница 6: ...e changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to change stale air duri...

Страница 7: ...nge of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time programs ON OFF ON Enabled UP 05 State after power failure 0 Switched OFF 1 Switched ON 2 state before power failure 0 1 2 2 UP 06 Enable Economy unoccupied Mode Shift the set point to a lower ...

Страница 8: ...g Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the auto fan speed function in cooling mode 0 10 0 C 20 0 F 1 0 C 2 F FC 07 Switching Hysteresis is the difference between switching on and switching off A small hysteresis will increase the number of switching cycles an...

Страница 9: ...pen DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle time heating 0 disables PWM mode 0 100 min 0 FC 19 PWM cycle time cooling 0 disables PWM mode 0 100 min 0 Î 3 point floating For floating point outputs the running time of the actuator used needs to be specified with FC17 Running time is defined as the time re...

Страница 10: ...TLC3 FCR 2 Engineering Manual Doc 70 00 0202 V3 0 Date 20111027 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes ...

Отзывы: