background image

 

 

Temperature PID controller TCY-MT-U 

 

 

Temperature PID controller TCY- MT-U 

 

 

Temperature PID controller TCY- MT-U 

 

Doc: 70-00-0177-20, V1.2 20160119 

© Vector Controls GmbH, Switzerland 

Subject to alterations 

Configuration parameters for firmware version 1.2 

The TCY-MT-U is preset to work for most applications. For special requirements it can be fine tuned to work 
ideal with a simple parameter setup routine. The parameters can be changed on the unit without the need of 
additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware version and revision. It is therefore 
important to use a matching product version and parameter set. The Firmware version and revision version 
can be found when pressing simultaneously the 

 and

 keys during several seconds. On the upper 7 

segment display, the firmware version can be found, on the lower 7 segment display the current revision 
index (or “sub-version”).  

Setting of user parameters 

The TCY-MT-U can be adapted to fit perfectly into your application. The control operation is defined by 
parameters. The parameters are set during operation by using the control buttons.  
The parameters may only be accessed by entering a code. There are two levels of parameters: User 
operation parameters for access control settings, and Expert parameters for control functions and unit setup. 
The codes for user levels and expert levels are different. Only control experts should be given the control 
parameter code.  
The parameters can be changed as follows: 
 

1. 

Press UP and DOWN button simultaneously for three seconds. The display shows the software 
version in the large digits and the product code in the small digits.  

2. 

Pressing the OPTION button will indicate CODE on the small digits and 000 on the large digits. 

3. 

The code for accessing the user parameters is 009 

4. 

Select this using UP or DOWN buttons. 

5. 

Press OPTION button after selecting the correct code.  

6. 

Once logged in, the parameter is displayed immediately. 

7. 

Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION 
button. Three triangles will show up on the lower right and indicate that the parameter may be 
modified now. Use UP or DOWN buttons to adjust the value. 

8. 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button 
is pressed for more than 5 minutes. 

User parameters (Password 09) 

Parameter  Description 

Range 

Default 

UP 00 

Enable access to operation modes 

ON, OFF 

ON 

UP 01 

Enable access to set points 

ON, OFF 

ON 

UP 02 

Not used 

ON, OFF 

OFF 

UP 03 

Enable manual change of Heating/Cooling Mode.  
No influence on TCY-MT2-U-W01 (cooling only) or  
TCY-MT2-U-W02 (heating only) 

ON, OFF 

TCY-MT2-W01:  OFF 
TCY-MT2-W02:  OFF 

TCY-MT2:  

ON 

TCY-MT4:  

ON

 

UP 04 

Not used 

ON, OFF 

OFF 

UP 05 

State after power failure:  
0 = off, 1 = on, 2 = state before power failure 

0, 1, 2 

UP 06 

Enable Economy (unoccupied) Mode.  
Shift the set point to a lower temperature in winter or 
higher temperature in summer in order to save energy. 
May be activated through the POWER button, or with 
the external input (typically for key card switches in hotel 
rooms or motion detectors for meeting rooms.)  

ON, OFF 

ON 

UP 07 

ON = Fahrenheit, OFF = Celsius 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibrate internal temperature sensor 
–10° to +10° in 0.1° steps. (Sensor is factory calibrated; 
use this feature for field adjustment only as required.) 

-

10…10 

UP 09 

Enable Frost Protection. 
Activates the output independent of operation mode 
when the control temperature drops below 5°C or 41°F. 
The controller returns to normal operation when the 
temperature increases above 10°C or 50°F. 

ON, OFF 

TCY-MT2-W01:   OFF 
TCY-MT2-W02:   ON

 

TCY-MT2:  

ON 

TCY-MT4:  

ON 

Control parameters (Access code: 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Parameter 

Description 

Range 

Default 

CP 00 

Minimum set point limit in Heating mode 

0…60°C (32..160°F) 

16°C (61°F) 

CP 01 

Maximum set point limit in Heating mode 

0…60°C (32..160°F) 

30°C (86°F) 

CP 02 

Minimum set point limit in Cooling mode 

0…60°C (32..160°F) 

18°C (65°F) 

CP 03 

Maximum set point limit in Cooling mode 

0…60°C (32..160°F) 

30°C (86°F) 

Controls configuration 

CP 04 

Economy (unoccupied) Mode temperature shift: 
The comfort (occupied) set point is shifted by the value set 
with parameter. If heating is active the comfort set point will 
be decreased, if cooling is active, the set point will be 
increased. (Enable with UP06.)  

0…100°C (200°F) 

5.0°C (10°F) 

CP 05 

Dead Zone Span (TCY-MT4-U only):  
The Dead Zone Span lies between the heating and the 
cooling set point. The output is off while the temperature is 
within the dead zone span. A negative dead zone is not 
possible. 

0…100°C (200°F) 

1.0°C (2°F) 

CP 06 

Heat/Cool Changeover Delay (TCY-MT4-U only): 
A demand to switch between heating and cooling must 
persist for the length of time set with this parameter before 
the controller switches. Prevents activation of a sequence 
during a short-term change in temperature in order to 
protect equipment (with control overshoot for example)  

0…255 min 

5 min 

CP 07 

P-band heating X

PH

 

0…100°C (200°F) 

2.0°C (4.0°F) 

CP 08 

P-band cooling X

PC

 

0…100°C (200°F) 

2.0°C (4.0°F) 

CP 09 

K

IH

, Integral gain heating, in 0.1 steps, (TI is fixed to 4s) 

0 disables ID part 
low value = slow reaction 
high value = fast reaction 

0…25.5 

0.0 

CP 10 

K

IC

, Integral gain cooling, in 0.1 steps, 0 disables I part 

0…25.5 

0.0 

CP 11 

Configuration of operation mode 
0 = TCY-MT2-U-W01 = Cooling mode Y

C1 

1 = TCY-MT2-U-W02 = Heating mode: Y

H1 

2 = TCY-MT2-U = Heating and Cooling (2 pipe system) 
3 = TCY-MT4-U = Heating and Cooling (4 pipe system)

 

TCY-MT2: 0 - 2 

TCY-MT4: 0 

– 3 

TCY-MT2-W01:  0 
TCY-MT2-W02:  1

 

TCY-MT2:  

TCY-MT4:  

 

Proportional control (P-band)  

The proportional control function calculates the output based on the difference between set point and 
measured value. The proportional band (P-band) defines the difference between set point and measured 
value which will result in a 100% output. For example, with a heating or reverse 0-10v control sequence, and 
a 2.0°C (4.0°F) P-band value, at 10v the controller will be 2.0°C (4.0°F) below set point. This is the working 
range of the proportional control sequence. 
Setting the proportional band to 0 disables proportional control. 

 

 

Integral and differential control

 

Proportional control is a very stable control mode. The flaw of proportional control alone, however, is that the 
set point is normally not reached. As the measured value gets closer to the set point, the output reduces 
until it reaches a point, a fraction above or below the set point, where the output equals the load. To reach 
the set point and achieve a higher level in comfort the Integral/Differential function should be activated. 

Integral Gain (KI)

 dynamically increases the output by the selected KI value until the set point is reached. 

The challenge, however, is to prevent hunting, where the output increases too fast, the temperature 
overshoots the set point, the output goes to 0, the temperature undershoots the set point, and the cycle 
repeats itself. Hunting may result if the integral gain is too high. Each system is different. It is recommended 
to start with a KI value of 0.5 for water based systems and 1.0 for air based systems. Reduce this value if 
the measured value overshoots the set point by more than 1°C (2°F). Increase the value if the output takes 
too long to reach the set point. Air based systems react faster than water based systems.  

Setting the integral gain to 0 disables integral and differential control.  

Output configuration 

Parameter 

Description 

Range 

Default 

CP 12 

Manual Override Mode:  
Allows manual control of the analog outputs for using the 
controller as positioned, or during commissioning.  

ON, OFF 

OFF 

CP 13 

Min output for AO1 (TCY-MT4-U = heating output) 

– 100 % 

20% 

CP 14 

Max output for AO1 (TCY-MT4-U = heating output) 

– 100 % 

100% 

CP 15 

Min output for AO2 (TCY-MT4-U = cooling output) 

– 100 % 

20% 

CP 16 

Max output for AO2 (TCY-MT4-U = cooling output) 

– 100 % 

100% 

CP 17 

Maximum Output in Economy (unoccupied)Mode 
Reduces the load on the system when is the space is 
unoccupied.  

– 100 % 

50% 

Input configuration 

CP 18 

Configuration of remote control input (X1) 

0 = Control input if temperature sensor connected 
1 = Occupation sensor 

– Comfort / Standby  

2 = Remote enable 

– Comfort / OFF 

3 = Keycard function: fixed set point 

0…3 

CP 19 

Activation delay (Minutes) = the time the binary input needs 
to be open before standby/off mode is activated. 

0…255 min 

CP 20 

Fixed set point for key card function in heating mode 

0…60°C 

(32..160°F) 

17°C (63°F) 

CP 21 

Fixed set point for key card function in cooling mode 

0…60°C 

(32..160°F) 

27°C (81°F) 

CP 22 

For TCY-MT2-U only: Enable Auto changeover 

ON, OFF 

OFF 

CP 23 

For TCY-MT2-U only: Auto-changeover limit heating 

0…60°C 

(32..160°F) 

30°C (86°F) 

CP 24 

For TCY-MT2-U only: Auto changeover limit cooling 

0…60°C 

(32..160°F) 

15°C (59°F) 

 

Configuring the function of the external input X1 

The external input X1 may be configured for several functions: 

 

CP18 = 0 

External control 
input 

The control input is provided by the external input. The 
internal input will not be used.  

CP18 = 1 

Switching Economy 
and Comfort modes 

Economy (unoccupied) and Comfort (occupied) modes 
are controlled through an external contact by connecting 
X1 through a dry contact to signal common. This function 
may be used together with key card switches for hotels or 
motion detectors for offices.

 

CP18 = 2 

Switching Energy 
Hold OFF and 
Comfort modes 

Opening the external temperature input will force the unit 
into the OFF operation mode. The operation mode cannot 
be overridden by using the terminal. Connecting the 
binary input to GND returns control of the operation mode 
to the terminal. This function may be used as window 
contact to prevent loss of energy.  

CP18 = 3 

Key card function 

As with CP18 = 1, the key card function switches 
economy (unoccupied) and comfort (occupied) modes. 
Instead of using the set point shift, the set points in 
unoccupied mode are defined by parameter CP20 and 
CP21.  

CP18 = 4 

Output enable 

This may be used for a dew point sensor input. Output will 
switch off if contact opens. 

 

Configuring auto changeover input X2 (TCY-MT2-U only):  

The auto changeover function automatically changes heating and cooling mode based on supply 
media temperature or outdoor temperature. The difference between the two is in the values of the 
changeover limits CP23 and CP24. See table below for recommended settings. 

Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all 
signal ground levels of involved controllers must be the same in case more than one controller is 
switched.  

 

Recommended settings for CP23 and CP24: 

Change over mode 

Relation CP23 to 
CP24 

Example 
CP23 

Example: 
CP24 

Supply media 

CP23 > CP24 

25°C (77F) 

18°C (64F) 

Outside temperature 

CP23 < CP24 

15°C (59F) 

25°C (77F) 

Dry contact: Heating if contact closed 

CP23 > CP24 

25°C (77F) 

15°C (59F) 

Dry contact: Cooling if contact closed 

CP23 < CP24 

15°C (59F) 

25°C (77F) 

 

Отзывы: