Control Functions (Code 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Control configuration 

Parameter  Description 

Range 

Default 

CP 00 

Minimum set point limit in heating mode 

0-60 °C (32-160 °F)  16 °C (61 °F) 

CP 01 

Maximum set point limit in heating mode 

0-60 °C (32-160 °F)  30 °C (86 °F) 

CP 02 

Minimum set point limit in cooling mode 

0-60 °C (32-160 °F)  18 °C (65 °F) 

CP 03 

Maximum set point limit in cooling mode 

0-60 °C (32-160 °F)  30 °C (86 °F) 

CP 04 

Economy (unoccupied) Mode temperature shift: 
The comfort (occupied) set point is shifted by the value set 

with parameter. If heating is active the comfort set point will 
be decreased, if cooling is active, the set point will be 

increased. (Enable with UP06.) 

0-100 °C (200 °F) 

5.0 °C (10 °F) 

CP 05 

Dead Zone Span(TCY-MT4 only): 
The Dead Zone Span lies between the heating and the cooling 

set point. The output is off while the temperature is within the 

dead zone span. A negative dead zone is not possible. 

0-100 °C (200 °F) 

1.0 °C (2 °F) 

CP 06 

Heat/Cool Changeover Delay (TCY-MT4 only): 

A demand to switch between heating and cooling must persist 

for the length of time set with this parameter before the 

controller switches. Prevents activation of a sequence during a 
short-term change in temperature in order to protect 

equipment(with control overshoot for example) 

0-255 min 

5 min 

CP 07 

P-band heating X

PH

 

0-100 °C (200 °F)  2.0 °C (4.0 °F) 

CP 08 

P-band cooling X

PC

 

0-100 °C (200 °F)  2.0 °C (4.0 °F) 

CP 09 

K

IH

, Integral gain heating, in 0.1 steps, (TI is fixed to 4s) 

0 disables ID part 

low value = slow reaction 

high value = fast reaction 

0…25.5 

0.0 

CP 10 

K

IC

, Integral gain cooling, in 0.1 steps, 0 disables I part 

0…25.5 

0.0 

CP 11 

Configuration of operation mode 
0 = TCY-MT2-W01 = Cooling mode Y

C1 

1 = TCY-MT2-W02 = Heating mode: Y

H1 

2 = TCY-MT2 = Heating and Cooling (2 pipe system), Y

H1

 + Y

C1 

3 = TCY-MT4 = Heating and Cooling (4 pipe system), Y

H1

 + Y

C1 

TCY-MT2: 0 - 2 

TCY-MT4: 0 – 3 

TCY-MT2-W01: 0 

TCY-MT2-W02: 1

 

TCY-MT2: 2 

TCY-MT4: 3 

 

Proportional control(P-band)  

The proportional control function calculates the output based on the difference between set point and measured value. 

The proportional band (P-band) defines the difference between set point and measured value which will result in a 

100% output. For example, with a heating or reverse 0-10v control sequence, and a 2.0°C (4.0°F) P-band value, at 
10v the controller will be 2.0°C (4.0°F) below set point. This is the working range of the proportional control 

sequence. 

Setting the proportional band to 0 disables proportional control. 

 

 

Integral and Differential control

 

Proportional control is a very stable control mode. The flaw of proportional control alone, however, is that the set 

point is normally not reached. As the measured value gets closer to the set point, the output reduces until it reaches 

a point, a fraction above or below the set point, where the output equals the load. To reach the set point and achieve 

a higher level in comfort the Integral/Differential function should be activated. 

Integral Gain (KI) 

dynamically increases the output by the selected KI value until the set point is reached. The 

challenge, however, is to prevent hunting, where the output increases too fast, the temperature overshoots the set 

point, the output goes to 0, the temperature undershoots the set point, and the cycle repeats itself. Hunting may 

result if the integral gain is too high. Each system is different. It is recommended to start with a KI value of 0.5 for 

water based systems and 1.0 for air based systems. Reduce this value if the measured value overshoots the set point 

by more than 1 °C (2 °F). Increase the value if the output takes too long to reach the set point. Air based systems 

react faster than water based systems.  

Setting the integral gain to 0 disables integral and differential control.  

 

 

Содержание TCY-MT Series

Страница 1: ...es and current inputs and outputs the TCI product range is recommended The TCY MT can be configured using the standard operation terminal No special tool or software is required Name Ordering Item Nam...

Страница 2: ...122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non conden...

Страница 3: ...rect sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers...

Страница 4: ...connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY MT may display the following error condition Err1 The connection to the tempera...

Страница 5: ...WN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediatel...

Страница 6: ...Cooling mode YC1 1 TCY MT2 W02 Heating mode YH1 2 TCY MT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY MT4 Heating and Cooling 4 pipe system YH1 YC1 TCY MT2 0 2 TCY MT4 0 3 TCY MT2 W01 0 TCY MT2 W...

Страница 7: ...MT4 heating output 0 100 0 CP 14 Max output for AO1 TCY MT4 heating output 0 100 100 CP 15 Min output for AO2 TCY MT4 cooling output 0 100 0 CP 16 Max output for AO2 TCY MT4 cooling output 0 100 100...

Страница 8: ...on detectors for offices CP18 2 Switching Energy Hold OFFand Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridde...

Отзывы: