Temperature PI controller TCY- FT-U
Temperature PI controller TCY- FT-U
Temperature PI controller TCY- FT-U
Doc: 70-00-0130C, V1.3, 20141030
© Vector Controls GmbH, Switzerland
Subject to alterations
Configuration parameters for firmware version 1.3
The TCY-FT-U is preset to work for most applications. For special requirements it can be fine tuned to work
ideal with a simple parameter setup routine. The parameters can be changed on the unit without the need of
additional equipment.
Identifying the firmware version
The parameters and functionality of controller depend on its firmware version and revision. It is therefore
important to use a matching product version and parameter set. The Firmware version and revision version
can be found when pressing simultaneously the
and
keys during several seconds. On the upper 7
segment display, the firmware version can be found, on the lower 7 segment display the current revision
index (or “sub-version”).
Setting of user parameters
The TCY-FT-U can be adapted to fit perfectly into your application. The control operation is defined by
parameters. The parameters are set during operation by using the control buttons.
The parameters may only be accessed by entering a code. There are two levels of parameters: User
operation parameters for access control settings, and Expert parameters for control functions and unit setup.
The codes for user levels and expert levels are different. Only control experts should be given the control
parameter code.
The parameters can be changed as follows:
1.
Press UP and DOWN button simultaneously for three seconds. The display shows the software
version in the large digits and the product code in the small digits.
2.
Pressing the OPTION button will indicate CODE on the small digits and 000 on the large digits.
3.
The code for accessing the user parameters is 009
4.
Select this using UP or DOWN buttons.
5.
Press OPTION button after selecting the correct code.
6.
Once logged in, the parameter is displayed immediately.
7.
Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION
button. Three triangles will show up on the lower right and indicate that the parameter may be
modified now. Use UP or DOWN buttons to adjust the value.
8.
After you are done, press OPTION or POWER in order to return to the parameter selection level.
Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button
is pressed for more than 5 minutes.
User Parameters (Password 09)
Parameter Description
Range
Default
UP 00
Enable access to operation modes
ON, OFF
ON
UP 01
Enable access to set points
ON, OFF
ON
UP 02
Not used
ON, OFF
OFF
UP 03
Enable manual change of Heating/Cooling Mode.
No influence on TCY-FT2-U-W1 (cooling only) or
TCY-FT2-U-W2 (heating only)
ON, OFF
ON
UP 04
Not used
ON, OFF
OFF
UP 05
State after power failure:
0 = off, 1 = on, 2 = state before power failure
0, 1, 2
2
UP 06
Enable Economy (unoccupied) Mode.
Shift the setpoint to a lower temperature in winter or
higher temperature in summer in order to save energy.
May be activated through the POWER button, or with
the external input (typically for key card switches in hotel
rooms or motion detectors for meeting rooms.)
ON, OFF
ON
UP 07
ON = Fahrenheit, OFF = Celsius
ON, OFF
OFF (Celsius)
UP 08
Calibrate internal temperature sensor
–10° to +10° in 0.1° steps. (Sensor is factory calibrated,
use this feature for field adjustment only as required.)
-
10…10
0
UP 09
Enable Frost Protection.
Activates the output independent of operation mode
when the control temperature drops below 5°C or 41°F.
The controller returns to normal operation when the
temperature increases above 10°C or 50°F.
ON, OFF
TCY-FT2-W1: OFF
TCY-FT2-W2: ON
TCY-FT2:
ON
TCY-FT4:
ON
Control Parameters (Access Code: 241)
Warning! Only experts should change these settings! See user parameters for login procedure.
Parameter
Description
Range
Default
CP 00
Minimum setpoint limit in Heating mode
0…60°C (32..160°F)
16°C (61°F)
CP 01
Maximum setpoint limit in Heating mode
0…60°C (32..160°F)
30°C (86°F)
CP 02
Minimum setpoint limit in Cooling mode
0…60°C (32..160°F)
18°C (65°F)
CP 03
Maximum setpoint limit in Cooling mode
0…60°C (32..160°F)
30°C (86°F)
Controls configuration
CP 04
Economy (unoccupied) Mode temperature shift:
The comfort (occupied) setpoint is shifted by the value set
with parameter. If heating is active the comfort setpoint will
be decreased, if cooling is active, the setpoint will be
increased. (Enable with UP06.)
0…100°C (200°F)
5.0°C (10°F)
CP 05
Dead Zone Span (TCY-FT4-U only):
The Dead Zone Span lies between the heating and the
cooling setpoint. The output is off while the temperature is
within the dead zone span. A negative dead zone is not
possible.
0…100°C (200°F)
1.0°C (2°F)
CP 06
Heat/Cool Changeover Delay (TCY-FT4-U only):
A demand to switch between heating and cooling must
persist for the length of time set with this parameter before
the controller switches. Prevents activation of a sequence
during a short-term change in temperature in order to
protect equipment (with control overshoot for example)
0…255 min
5 min
CP 07
P-band heating X
PH
0…100°C (200°F)
2.0°C (4.0°F)
CP 08
P-band cooling X
PC
0…100°C (200°F)
2.0°C (4.0°F)
CP 09
K
IH
, Integral gain heating, in 0.1 steps, (TI is fixed to 4s)
0 disables ID part
low value = slow reaction
high value = fast reaction
0…25.5
0.0
CP 10
K
IC
, Integral gain cooling, in 0.1 steps, 0 disables I part
0…25.5
0.0
CP 11
Configuration of operation mode
0 = TCY-FT2-U-W1 = Cooling mode Y
C1
1 = TCY-FT2-U-W2 = Heating mode: Y
H1
2 = TCY-FT2-U = Heating and Cooling (2 pipe system)
3 = TCY-FT4-U = Heating and Cooling (4 pipe system)
TCY-FT2: 0 - 2
TCY-FT4: 0
– 3
TCY-FT2-W1: 0
TCY-FT2-W2: 1
TCY-FT2:
2
TCY-FT4:
3
Output configuration
Parameter
Description
Range
Default
CP 12
Manual Override Mode:
Allows manual control of the floating outputs for using the
controller as positioner or during commissioning.
ON, OFF
OFF
CP 13
Running time FO1 (TCY-FT4 = heating output)
The total time it takes for the actuator to run from fully open
to fully closed or from fully closed to fully open.
Setting this value to 0, converts the output to on/off control.
Open output will activate if there is demand; close output
will stay active if there is no demand. The p-band functions
as hysteresis.
0-255s
90s
CP 14
Minimum running time FO1 (TCY-FT4-U = heating output)
The minimum time the output runs once it starts. This
setting prevents frequent switches with very short running
times.
0-255s
3s
CP 15
Running time FO2 (TCY-FT4-U = cooling output)
The total time it takes for the actuator to run from fully open
to fully closed or from fully closed to fully open
Setting this value to 0, converts the output to on/off control.
Open output will activate if there is demand; close output
will stay active if there is no demand. The p-band functions
as hysteresis.
0-255s
90s
CP 16
Minimum running time FO2 (TCY-FT4-U = cooling output)
The minimum time the output runs once it starts. This
setting prevents frequent switches with very short running
times.
0-255s
3s
CP 17
Maximum Output in Economy (unoccupied) Mode
Reduces the load on the system when is the space is
unoccupied.
0
– 100 %
50%
Input configuration
CP 18
Configuration of remote control input (X1)
0 = Control input if temperature sensor connected
1 = Occupation sensor
– Comfort / Standby
2 = Remote enable
– Comfort / OFF
3 = Keycard function: fixed setpoint
0…3
0
CP 19
Activation delay (Minutes) = the time the binary input needs
to be open before standby/off mode is activated.
0…255 min
5
CP 20
Fixed setpoint for key card function in heating mode
0…60°C(32..160°F) 17°C (63°F)
CP 21
Fixed setpoint for key card function in cooling mode
0…60°C(32..160°F) 27°C (81°F)
CP 22
For TCY-FT2-U only: Enable Auto changeover
ON, OFF
OFF
CP 23
For TCY-FT2-U only: Auto-changeover limit heating
0…60°C(32..160°F) 30°C (86°F)
CP 24
For TCY-FT2-U only: Auto changeover limit cooling
0…60°C(32..160°F) 15°C (59°F)
Configuring the function of the external input X1
The external input X1 may be configured for several functions:
CP18 = 0
External control
input
The control input is provided by the external input. The
internal input will not be used.
CP18 = 1
Switching Economy
and Comfort modes
Economy (unoccupied) and Comfort (occupied) modes
are controlled through an external contact by connecting
X1 through a dry contact to signal common. This function
may be used together with key card switches for hotels or
motion detectors for offices.
CP18 = 2
Switching Energy
Hold OFF and
Comfort modes
Opening the external temperature input will force the unit
into the OFF operation mode. The operation mode cannot
be overridden by using the terminal. Connecting the
binary input to GND returns control of the operation mode
to the terminal. This function may be used as window
contact to prevent loss of energy.
CP18 = 3
Key card function
As with CP18 = 1, the key card function switches
economy (unoccupied) and comfort (occupied) modes.
Instead of using the setpoint shift, the setpoints in
unoccupied mode are defined by parameter CP20 and
CP21.
CP18 = 4
Output enable
This may be used for a dew point sensor input. Output will
switch off if contact opens.
Configuring auto changeover input X2 (TCY-FT2-U only):
The auto changeover function automatically changes heating and cooling mode based on supply
media temperature or outdoor temperature. The difference between the two is in the values of the
changeover limits CP23 and CP24. See table below for recommended settings.
Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all
signal ground levels of involved controllers must be the same in case more than one controller is
switched.
Recommended settings for CP23 and CP24:
Change over mode
Relation CP23 to
CP24
Example
CP23
Example:
CP24
Supply media
CP23 > CP24
25°C (77F)
18°C (64F)
Outside temperature
CP23 < CP24
15°C (59F)
25°C (77F)
Dry contact: Heating if contact closed
CP23 > CP24
25°C (77F)
15°C (59F)
Dry contact: Cooling if contact closed
CP23 < CP24
15°C (59F)
25°C (77F)