background image

 

 

Humidistat TCY-BH-U

 

 

Doc:70-07-0102, V1.1, Date: 20100504 

© Vector Controls GmbH, Switzerland 

Page 11 

Subject to alteration 

Configuration parameters for firmware version 1.1 

The TCY-BH-U can be adapted to wide variety of applications. The adaptation is done with parameters. The parameters can be 
changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware revision. It is therefore important to use a matching 
product version and parameter set. The firmware version is shown on the large LCD digits when pressing UP and DOWN 
buttons for more than 3 seconds simultaneously.  

Control Parameters (Access Code: 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Parameter Description 

Range 

Standard 

CP 00 

Minimum setpoint limit in humidification mode 

0…100% 

10% 

CP 01 

Maximum setpoint limit in humidification mode 

0…100% 

90% 

CP 02 

Minimum setpoint limit in de-humidification mode 

0…100% 

10% 

CP 03 

Maximum setpoint limit in de-humidification mode 

0…100% 

90% 

Controls configuration 

CP 04 

Economy humidity shift 

0…100% 

10% 

CP 05 

Dead zone between humidifying & de-humidifying set point X

DZ

 0…100% 

10% 

CP 06 

Delay on humidify – de-humidify change over 

0…255 min 

5 min 

CP 07 

Switching Hysteresis 

0…100% 

3% 

CP 08 

Delay OFF (Minimum running time) 

0…255s 

10s 

CP 09 

Delay ON (Minimum stopping time) 

0…255s 

10s 

CP 10 

Configuration of control mode 
0 = Both Humidification and de-humidification 
1 = W04 = Humidification only

 

2 = W05 = De-humidification only 

 

0 - 2 

TCY-BH:  

TCY-BH-W4:   1 
TCY-BH-W5: 2 

 

Output configuration 

CP 11 

Enable fan (only if CP 10 

 0) 

ON, OFF 

TCY-BH:  

OFF 

TCY-BH-W4:   ON 

TCY-BH-W5: ON 

CP 12 

Start delay for fan  
(Time the fan runs before control output starts) 

0…255 s 

10 s 

CP 13 

Stop delay for fan  
(Time the fan keeps running after control output stops) 

0…255 s 

90 s 

Temperature setback configuration 

CP 14 

Enable temperature setback 
OFF = Temperature setback is disabled 

ON = Temperature setback is enabled 

ON, OFF 

OFF 

CP 15 

Setpoint limit at full setback 

0…100% 

20% 

CP 16 

Lower temperature limit:  
Outside temperature with maximum setback 
The setpoint will be equal to the minimum setpoint limit 

-40…60°C 

-40…160°F 

-30°C (-22°F) 

CP 17 

Upper temperature limit:  
Outside temperature at begin of setback.  

-40…60°C 
40…160°F 

0°C  (32°F) 

Input signal configuration 

CP 18 

Number of seconds taken into account to calculate the 
averaging input signal. 

Low value = fast response 
High value = slow response 

0…100 10 

 

Содержание TCY-BH-U

Страница 1: ...ation humidifiers and dehumidifiers without fan support General Description The TCY BH U is a stand alone electronic binary humidity stat The TCY BH U features one internal humidity sensor one externa...

Страница 2: ...NTC Sxx Tn10 sensor 40 70 C 40 158 F Accuracy 40 0 C 40 32 F 0 5 K 0 50 C 32 122 F 0 2 K 50 70 C 122 158 F 0 5 K Signal Outputs Digital Switching Outputs Switching type Switching power DO1 DO2 Relays...

Страница 3: ...0 30 VDC RT Temperature input for setback NTC 10k 25 C 77 F CP10 1 YB1 Binary output 1 Humidify 0 24 VAC or 0 30 VDC YB2 Binary output 2 if CP11 ON Fan 0 24 VAC or 0 30 VDC RT Temperature input for se...

Страница 4: ...uipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 C...

Страница 5: ...meters and set points are memorized and don t need to be reentered Depending on UP 05 the unit will remain switched off switch on automatically or return to the operation mode it was in before the pow...

Страница 6: ...mode is used for rooms such as lecture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is activ...

Страница 7: ...in the large digits and CALH or CAL t in the small Pressing OPTION will reveal the current calibration value of the humidity sensor CALH or the temperature input CAL t Change the value with the UP DO...

Страница 8: ...pressing the OPTION button Three triangles will show up on the lower right and indicate that the parameter may be modified now Use UP or DOWN buttons to adjust the value 8 After you are done press OPT...

Страница 9: ...ll increase the number of switching cycles and thus the wear on associated equipment Delay OFF Prevents a too short running cycle for the control output by setting a minimum running time Delay ON Prev...

Страница 10: ...and the humidistat will first activate the fan wait the required start delay time CP12 and then activate the control output This will ensure stable air for humidification or de humidification The cont...

Страница 11: ...0 10 CP 05 Dead zone between humidifying de humidifying set point XDZ 0 100 10 CP 06 Delay on humidify de humidify change over 0 255 min 5 min CP 07 Switching Hysteresis 0 100 3 CP 08 Delay OFF Minimu...

Отзывы: