background image

 

SRC-C1  

 

Doc: 70-07-0220, V1.2, 20170131, Subject to alteration, ©Vector Controls GmbH, Switzerland, www.vectorcontrols.com 

Page 3 

 

 

Mechanical Design and Installation 

The unit consists of two parts: (a) The mounting plate and (b) the cover with the transmitter. 

Mounting Location 

Mount the transmitter on a flat interior wall of the room to be controlled. Do avoid obstructions such as shelves, curtains and 

recesses. Do not place near heat sources, draft channels. Do not expose to direct sunlight.  

Mounting instruction 

See installation sheet no. 70-000572 (www.vectorcontrols.com). 

Configuration 

Output signal configuration 

The analog output signal type may be configured with a jumper for 0-10 VDC or 0-

20 mA control signals. The jumpers are located next to the terminal connector of 

each analog output. See table below for jumper placement. The factory setting is 

to 0-10 VDC. 

 

The signal range may be set with JP2 for both analog outputs. JP2 will only operate 
if the output range specified with OP01 and OP02 is left at the default position of 

0…100%. With any other setting the position of JP2 has no influence and the range 

defined with the output parameters applies.  

Jumper settings 

 

 

 

 

Signal type 

JP1 

0 – 10 V 

(1-2) 

0 – 20 mA 

(2-3) 

Signal range 

JP2 

0 – 10 V, 0 – 20 mA 

(1-2) 

2 – 10 V, 4 – 20 mA 

(2-3) 

JP1 Signal type 

JP2 Signal range 

U1:  

0-10V 

I1:  

0-20mA 

 
U1:  

2-10V 

I1:  

4-20mA 


 

 



 

 

U1 
0-10V, 2-10V 
 
I1 
0-20mA, 4-20mA 


 

 



 

 

Status LED 

LED indicates status 

No light: no power or unit damaged 

5 sec blinking: Normal  

Constant light: Error mode 

 

Alternate in 2 sec. intervals with air 

quality LED: Calibration is active. 

Calibration end: Constant light for 

10s. Success is shown on air quality 

led: Green blinking: OK,  

Red blinking: failed. Device enters 

error mode.   

OPU-S 

2  3 

JP1 

 

 

JP2 

 

 

STATUS 

G

 

24

V

 

G

0

 

0V

 

U1/

 I1

 

A

CO2

  

Air Quality 

Air quality LED 

LED indicates status 

No light : no power or unit damaged  

Green   : Low CO2 level  

Orange  : Medium CO2 level 

Red 

: High CO2 level 

Red blinking: 0ppm calibration 

Green blinking: 400ppm calibration 

Отзывы: