 OPA2-VC Operation Terminal 

Technical Data

 

  

Doc: 70-00-0196A, V1.3, 20220222  

© Vector Controls GmbH, Switzerland  

Page 2-4 

Subject to alterations  

www.vectorcontrols.com 

Technical Specification 

Power Supply 

Operating voltage 

10-30VDC, 10-26V AC 

 

Power consumption 

Max 0.5 VA 

 

Electrical Connection 

Terminal Connectors,  

wire 0.34…2.5 mm

2

 

(AWG 24…12)

 

Temperature Input 

Type 

NTC 10kΩ @ 25°C (77°F)

 

 

Range 

0…50 °C (32…122 °F)

 

 

Accuracy 

0.2 K 

Communication 

Communication Type 

Protocol 

RS485, Peer to peer,  

VCPP: Vector Controls Proprietary Protocol 

 

Cabling 

Impedance 

Nominal capacitance 

Nominal velocity 

Shielded Twisted Pair (STP), CAT5 or CAT6.  

balanced 100 to 120 ohm  

50 pF/m 16pF/ft or lower 

65% or higher 

Environment 

Operation 

Climatic Conditions 

Temperature 
Humidity 

To IEC 721-3-3 

class 3 K5 

0…50 °C (32…122 °F)

 

<95 % r.H. non-condensing 

 

Transport & Storage 

Climatic Conditions 

Temperature 

Humidity 

Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 

class 3 K3 and class 1 K3 

-25

…7

0 °C (-13

…158 °F)

 

<95 % r.H. non-condensing 

class 2M2 

Standards 

Pollution Class 

Normal acc. to EN 60 730 

 

Degree of Protection 

IP30 to EN 60 529 

 

Safety Class 

III 

General 

OPA Dimensions (H x W x D) 

88 x 88 x 30 mm (3.5” x 3.5” x 1.1”)

 

 

Housing Material 

Fire proof ABS plastic 

 

Mounting Plate 

Zinc coated steel 

 

Standard Color 

White RAL 9003 

 

Weight (including package) 

185 g (6.5 oz) 

Product testing and certification 

 

Declaration of conformity 

Information about the conformity of our products can be found on our website 

www.vectorcontrols.com on the corresponding product page under "Downloads" 

Connection Diagram 

 

Installation 

See installation sheet no: 

OPA2-VC 

 

70-000113 ( 

www.vectorcontrols.com

 

 

OPA2-VC 

 OP1 

 OP2 

 OP3 

 OP4 

CAT5/CAT6 

+V 

 

Description 

1   OP1 

V+ Power supply 

2   OP2 

   Power supply 

3   OP3 

RS485 

4   OP4 

RS485 

Содержание OPA2-VC

Страница 1: ...ll the operation terminal on an easy accessible interior wall approx 1 5 m above the floor in an area of average temperature Avoid direct sunlight or other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are use...

Страница 2: ...50 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards Pollution Class Normal acc to EN 60 730 Degree of Protection IP30 to EN 60 529 Safety Class III General OPA Dimensions H x W x D 88 x 88 x 30 mm 3 5 x 3 5 x 1 1 Housin...

Страница 3: ...al This operation terminal works with the latest generation X2 control devices Detailed operating instructions for all devices equipped with this operating system can be downloaded here http www vectorcontrols com products x2 Also available are programming instructions for technicians and an application database Left POWER Press 2 sec Toggle STANDBY COMFORT mode or switch from OFF to ON Press 2 se...

Страница 4: ...96A V1 3 20220222 Vector Controls GmbH Switzerland Page 4 4 Subject to alterations www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorcontrols com www vectorcontrols com ...

Отзывы: