background image

 

MZ3-FU-V01

 

 

Doc: 70-00-0842A V2.5, 20230220  

© Vector Controls GmbH, Switzerland  

Page 5-6 

Subject to alternation  

www.vectorcontrols.com 

Configuration 

Configuration of the output signal and jumper 

 

If JP1 is in position 1-

2, the output signal is 0…10 VDC

 

 

If JP1 is in position 2-

3, the output signal is 2…10 VDC

 

 

 

The jumper position can be seen in section "View of rear part, without front panel" page 3. 

 

Output configuration (AO) 

Parameter  Description 

Range 

Default 

OP00 

Output level 0 (MIN): 0…100 % = 0…10.0 VDC

 

0…100%

 

0% = 

0 V (

JP1 = 1-2

2 V (

JP1 = 2-3

OP01 

Output level 1 (MID): 0…100 % = 0…10.0 VDC 

 

Note: setting a level to 0 disables it 

0…100%

 

50% = 

5 V (

JP1 = 1-2

6 V (

JP1 = 2-3

OP02 

Output level 2 (MAX): 0…100 % = 0…10.0 VDC

 

Note: setting a level to 0 disables it 

0…100%

 

100% = 

10 V (

JP1 = 1-2

10 V (

JP1 = 2-3

OP03 

Automatic reset time of the lowest level to the level defined 

in OP05. The reset is deactivated with setting = 0 

0…255 min

 

0 min 

(deactivated) 

OP04 

Automatic reset time of the highest level to the level defined 

in OP05. The reset is deactivated with setting = 0 

0…255 min

 

0 min 

(deactivated) 

OP05 

Level after automatic reset. This level will be activated once 

the reset time defined in OP04 has expired.  

0…2

 

OP06 

- 0: Parameter copy successful; No action 

- 1: Start parameter copy to AEC-PM2 

- 7: Copy fail (no AEC-PM2 or communication error) 

0…1

 

 

7: display only 

 

 Setting the parameters 

The MZ3 is designed to work for most comfort ventilation applications. It is 

however possible to fine tune it to fit perfect into the application at hand. 

The parameters can be changed during operation through an operation unit 

called OPA-S. The operating unit OPA-S must be connected for the 

adjustment of the parameters with the MZ3. 

 

Carefully lift the front panel of the MZ3 and pull it away to the front. Plug the 

connecting cable of the OPA-S operating unit into the rear part of the MZ3. 

 

 

 

 

Important 

The MZ3 does not accept the new settings until the OPA-S parameter menu is exited. The connection must not be 
disconnected earlier than five seconds after the last keystroke! 

Copy parameters 

It is now possible to copy settings to an accessory (AEC-PM2) and to copy them back to 

other MZ3. For this, remove the front panel of the MZ3, insert AEC-PM2 in the 

designated plug. 

Copy parameters from MZ3 to AEC-PM2 

Connect OPA-S and copy parameters from MZ3 to AEC-PM2 by setting OP06 to 1. The 

"Data" LED of the AEC-PM2 lights up for 5 seconds after successful parameter copying 

and OP06 is set to 0. If parameter copying has failed, the LED flashes for 5 seconds and 

OP06 is set to 7. 

Copy parameters from AEC-PM2 to MZ3 

Copy the parameters from AEC-PM2 to MZ3 simply by pressing the "Copy" button on the 

AEC-PM2. The "Data" LED on the AEC-PM2 will light for 5 seconds after the parameters 

have been successfully copied. If the parameter copy failed, the LED will blink for 5 

seconds. 

 

 

 

Отзывы: