Technical data
Power supply
Operating voltage
24 V AC/DC ± 10%, 50/60 Hz, Class 2 48 VA max
Power consumption
Max. 1,0 VA
Power backup for real time clock
Super cap, keeps clock running for 24 h without
power
Electrical
connection
Terminal connectors,
wire 0,34-2,5 mm
2
(AWG 22…13)
Signal inputs
Analog input
0..10 VDC
Signal outputs
Analog outputs
Output signal
Resolution
Maximum load
DC 0...10 VDC
9.76 mV (10 Bit)
2 mA or 5
kΩ
Environment
Operation
Climatic conditions
Temperature
Humidity
To IEC 721-3-3
class 3K5
0...50 ° C (32...122 ° F)
< 95% RH non-condensing
Transport & storage
Climatic conditions
Temperature
Humidity
Mechanical conditions
To IEC 721-3-2 and IEC 721-3-1
class 3K3 and class 1K3
-
25…70 °C (
-
13…158 °F)
< 95% RH non-condensing
class 2MT2
Standards
Degree of protection
Wall mounted:
IP40 acc. EN 60529
Not installed:
IP00 acc. EN 60529
Safety class
III (IEC 60536)
General
Housing material:
Fireproof ABS+PC plastic (UL94 class V-0)
Dimensions (H x W x D)
including packaging
120 x 120 x 70 mm (4,7
” x
4,7
” x
2,8
”)
Weight (incl. packaging)
150 g (5.3 oz)
Product testing and certification
Declaration of
Conformity
Information on the conformity of our products can be found on our website
on the corresponding product page under "Downloads".
Dimensions mm (in)
The MZ3-FA-V11 is so designed that it can be incorporated into a commercially available flush box (Feller EDIZIOdue
®
frame and mounting plate are included).