background image

 

MZ3-FA-V11

 

 

Doc: 70-00-0836 V2.2, 20210628 

© Vector Controls GmbH, Switzerland 

Page 2 

Subject to alterations 

www.vectorcontrols.com 

 Technical data  

Power supply 

Operating voltage 

24 V AC/DC ± 10%, 50/60 Hz, Class 2 48 VA max 

Power consumption 

Max. 1,0 VA 

Power backup for real time clock 

Super cap, keeps clock running for 24 h without 
power 

Electrical 

connection

 

Terminal connectors,  
wire 0,34-2,5 mm

2

 

(AWG 22…13)

 

Signal inputs 

Analog input 

0..10 VDC 

Signal outputs 

Analog outputs 

Output signal 

Resolution 

Maximum load 

 

DC 0...10 VDC 

9.76 mV (10 Bit) 

2 mA or 5 

kΩ

 

Environment 

Operation 
Climatic conditions 

Temperature 

Humidity 

To IEC 721-3-3 
class 3K5 

0...50 ° C (32...122 ° F) 

< 95% RH non-condensing 

Transport & storage 

Climatic conditions 

Temperature 

Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 

class 3K3 and class 1K3 

-

25…70 °C (

-

13…158 °F)

 

< 95% RH non-condensing 

class 2MT2 

Standards 

Degree of protection 

Wall mounted:  

IP40 acc. EN 60529 

Not installed:  

IP00 acc. EN 60529 

Safety class 

III (IEC 60536) 

General 

Housing material: 

Fireproof ABS+PC plastic (UL94 class V-0) 

 

Dimensions (H x W x D)  

including packaging 

120 x 120 x 70 mm (4,7

” x 

4,7

” x 

2,8

”) 

 

 

Weight (incl. packaging) 

150 g (5.3 oz) 

Product testing and certification 

 

Declaration of 

Conformity 

Information on the conformity of our products can be found on our website 

www.vectorcontrols.com

 on the corresponding product page under "Downloads". 

Dimensions mm (in) 

The MZ3-FA-V11 is so designed that it can be incorporated into a commercially available flush box (Feller EDIZIOdue

®

 

frame and mounting plate are included). 

 

Содержание MZ3-FA-V11

Страница 1: ...s the positioner may be configured to work for most of the standard ventilation applications The device is pre configured according to this documentation Settings such as switching levels of the control curve and ventilation strengths for each Level may be adjusted The configuration may be performed using the programming device called OPA S This device may be used as well to visualize measuring va...

Страница 2: ...nsing Transport storage Climatic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3K3 and class 1K3 25 70 C 13 158 F 95 RH non condensing class 2MT2 Standards Degree of protection Wall mounted IP40 acc EN 60529 Not installed IP00 acc EN 60529 Safety class III IEC 60536 General Housing material Fireproof ABS PC plastic UL94 class V 0 Dimensions H x W x D in...

Страница 3: ... of the device to keep fan running in minimal volume in OFF mode If JP1 in position 1 2 the output is off in OFF mode Ventilation switches off If JP1 in position 2 3 or removed the output stays in OFF mode in Level 0 minimum air volume View back part when front plate removed New with V2 0 Parameter copy It is now possible to copy settings to an accessory AEC PM2 and to copy them back to other MZ3 ...

Страница 4: ...or the highest level boost mode IP08 defines a reset time after which the unit returns to automatic operation once placed into manual Setting this time to 0 prevents the automatic reset Software configuration The MZ3 FA V11 is designed to work for most comfort ventilation applications It is however possible to fine tune it to fit perfect into the application at hand The parameters can be changed d...

Отзывы: