SRC-C1T1
CO2+T
EMPERATUR
T
RANSMITTER
/M
ONITOR
Doc: 70-00-0794A, V2.7, 20210310
© Vector Controls GmbH, Switzerland
Page 6-10
Subject to change without notice
www.vectorcontrols.com
Input configuration
Parameter Description
Range
Default
IP 00
TI1: Celsius or Fahrenheit, C = OFF, F = ON
ON, OFF
OFF
IP 01
TI1: Samples taken for averaging control signal
1)
1…255
10
IP 02
TI1: Calibration
-
10…10
0
IP 03
TI1: Minimum temperature range
(temperature when output is at its minimum)
-
40…215 °C
-
40…4
19 °F
-40 °C
-40 °F
IP 04
TI1: Maximum temperature range
(temperature when output is at its maximum)
-
40…215 °C
-
40…
419 °F
60 °C
140 °F
IP 05
CI1: Light intensity of air quality LED on front
0…10
8
IP 06
CI1: Samples taken for averaging control signal
1)
1…255
10
IP 07
CI1: Calibration
-
10…10%
0
IP 08
CI1: Minimum CO2 range ppm
2)
(CO2 level when output is at its minimum)
0…5000 ppm
0 ppm
IP 09
CI1: Maximum CO2 range ppm
2)
(CO2 level when output is at its maximum)
0…5000 ppm
2000 ppm
IP 10
CI1: CO2 level for medium CO2 indication
2)
0…5000 ppm
1000 ppm
IP 11
CI1: CO2 level for high CO2 indication
2)
0…5000 ppm
1600 ppm
IP 12
CI1: Enable ABC automatic CO2 background calibration
ON, OFF
ON
IP 13
CI1: Calibrate CO2 sensor
Note: For normal operation, calibration is not required. Only experts
should calibrate the sensor.
0 = No calibration (default)
1 = Calibrate to gas (0 ppm)
2 = Calibrate to fresh air (400 ppm)
0
…
2
0
1)
Sample interval: 1 sec.
2)
Changing this parameter affects the control of the air quality LEDs or relay as follows:
Air quality LED
Use of Parameters
Green
value
…
Green + Orange
Orange
value
…
Red
Red
value …
value
Output configuration
Parameter Description
Range
Default
OP 00
AO1 (CO2): Configuration of CO2 output signal:
0 = CO2 value
1 = Recorded minimum CO2 value
2 = Recorded maximum CO2 value
0
…
2
0
OP 01
AO1 (CO2): Minimum limitation of CO2 output signal
3) 4)
0
…100
%
0 %
OP 02
AO1 (CO2): Maximum limitation of CO2 output signal
3) 4)
0…
100 %
100 %
OP 03
AO2 (temperature): Configuration of temperature output signal:
0 = Temperature value
1 = Recorded minimum temperature value
2 = Recorded maximum temperature value
0…2
0
OP 04
AO2 (temperature): Minimum limitation of temperature output
signal
3) 4)
0
…
100 %
0 %
OP 05
AO2 (temperature): Maximum limitation of temperature output
signal
3) 4
0
…
100 %
100 %
3)
The Output signal will be scaled according to selected input range, selected limitation of output signal and the output
signal range selected by the jumper.
4)
If the default values are changed, the position of JP2 has no influence and the output signal range defined with the
parameters applies.
IP
= Input Parameter
OP = Output Parameter
CI
= CO2 Input
TI
= Temperature Input
AO = Analog Output