TLR-D5 Engineering Manual

 

Doc: 70-00-0095 20081223 

©2008 Vector Controls 

Page 14 

Control Parameters (Access Code: 241) 

Setpoint limitations 

Parameter 

Description

 

Range Default 

FC 00 

Minimum setpoint limit in Heating mode 

-40…215° 

16°C (61°F) 

FC 01 

Maximum setpoint limit in Heating mode 

-40…215° 

24°C (76°F) 

FC 02 

Minimum setpoint limit in Cooling mode 

-40…215° 

18°C (65°F) 

FC 03 

Maximum setpoint limit in Cooling mode 

-40…215° 

30°C (87°F) 

Fan control sequence 

Parameter Description 

Range Default 

FC 04 

Economy temperature shift 

0…10.0K (20°F) 

5.0°C (10°F) 

FC 05 

Switching Span Heating,  

Setting this value to 0 disables the auto fan speed function in heating 
mode 

0…10.0K (20°F) 

0.9°C (1.8°F) 

FC 06 

Switching Span Cooling 

Setting this value to 0 disables the auto fan speed function in cooling 

mode 

0…10.0K (20°F) 

0.7°C (1.4°F) 

FC 07 

Fan Switching Hysteresis 

0…10.0K (20°F) 

0.5°C (1°F) 

FC 08 

Mold Protection: OFF = Disabled, ON = Enabled 

ON, OFF 

OFF 

FC 09 

Delay OFF (Minimum running time) 

0…255 s 

10s 

FC 10 

Delay ON (Minimum stopping time) 

0…255 s 

10s 

FC 11 

2-pipe or 4-pipe system: OFF = 2-pipe, ON = 4-pipe system 

ON, OFF 

OFF 

FC 12 

Dead zone between heating & cooling set point X

DZ

 

0…100°C (200°F) 

1.0°C (2°F) 

FC 13 

Delay on Heat/Cool change over 

0…255 min 

5 min 

Output configuration 

Parameter Description 

Range Default 

FC 14 

Output setting, Binary or 3-point:  
OFF = Binary (DO4 Heating, DO5 Cooling) 

ON = 3-point output (DO4 OPEN, DO5 CLOSE) 

ON, OFF 

OFF 

FC 15 

Reversing valve in binary mode 
0 = no reversing valve (DO4 Heating, DO5 Cooling) 

1 = reversing valve while heating  (DO4 R.Valve, DO5 comp.) 
2 = reversing valve while cooling  (DO4 Comp, DO5 R. valve) 

0...2 0 

FC 16 

Running Time in 3-point mode 

0…255 s 

90 s 

Input configuration 

Parameter Description 

Range Default 

FC 17 

External input:  
0 = No external input 

1 = External temperature sensor 

2 = Occupation sensor – Comfort / Economy 

3 = Occupation sensor – Comfort / Off 
4 = Heat / Cool change by open contact. Contact open = Heat 

5 = Heat / Cool change by open contact. Contact open = Cool 

6 = Auto-changeover based on supply temperature 

7 = Auto-changeover based on outside temperature 
8 = Key card with alternative setpoint 

0…8 0 

FC 18 

Activation delay (Minutes) = the time the binary input needs to be open 

before economy/off mode is activated. 

0…255 min 

FC 19 

Auto-changeover limit cooling for supply temperature FC17 = 6 

Auto-changeover limit heating for outside temperature FC17 = 7 
or economy setpoint in heating mode if FC17 = 8 

-40…60°C (160°F) 

16°C (61°F) 

FC 20 

Auto-changeover limit heating for supply temperature FC17 = 6 

Auto-changeover limit cooling for outside temperature FC17 = 7 

or economy setpoint in cooling mode if FC17 = 8 

-40…60°C (160°F) 

28°C (83°F) 

 

 

Subject to alteration 

SUNSTAR传感与控制 http://www.sensor-ic.com/ TEL:0755-83376549 FAX:0755-83376182 E-MAIL:[email protected]

SUNSTAR自动化 http://www.sensor-ic.com/ TEL: 0755-83376489 FAX:0755-83376182 E-MAIL:[email protected]

Содержание TLR-D5

Страница 1: ...ree Celsius or Fahrenheit Deluxe Version o Clock and time schedule functions with special options for schools and universities o Clock keeps running for 48h in case of power failure o Display with blu...

Страница 2: ...W1 40 11 00xx 1 Cooling only Accessories AER D5 24 40 11 0017 Base unit only 24V AER D5 230 40 11 0018 Base unit only 230V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20...

Страница 3: ...ransport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conf...

Страница 4: ...r if unclear Do not connect directly motors larger than 1kW Connection diagram Connection diagram Power supply L Power supply L Connection terminals Connection terminals RTEXT 0V AC N 2 1 FAN 1 3 Heat...

Страница 5: ...not stand out more than 5 mm of the surface of the mounting plate 2 Connect the wires of the terminals to the communication wires according wiring diagram 3 Slide the two latches located on the top of...

Страница 6: ...after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will...

Страница 7: ...nit is manually switched on while in scheduled off mode The unit will switch automatically off when the reset time defined in UP13 expires Setting UP13 to 0 disables the override reset A blinking cloc...

Страница 8: ...e Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The...

Страница 9: ...ivated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand Clock settings The remote controlle...

Страница 10: ...he menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Range Default UP 00 Enable access to operation modes ON OFF ON En...

Страница 11: ...r the fan and heating or cooling stages by setting a minimum running time Delay OFF applies to all heating and cooling stages Delay ON Prevents a too short stopping cycle for fan and heating or coolin...

Страница 12: ...cannot be overridden by using the terminal or time schedules Connecting the external temperature input to GND returns control of the operation mode to the terminal and time schedule This function may...

Страница 13: ...s can be changed on the unit without the need of additional equipment Identifying the firmware version The parameters and functionality of controller depend on its firmware version and revision It is...

Страница 14: ...r 3 point OFF Binary DO4 Heating DO5 Cooling ON 3 point output DO4 OPEN DO5 CLOSE ON OFF OFF FC 15 Reversing valve in binary mode 0 no reversing valve DO4 Heating DO5 Cooling 1 reversing valve while h...

Отзывы: