WHHRM300DC & WHHR400DC 20
Chapter 6
Operation instructions
6.7.3 Adjustable settings table
For a description of these settings refer to section 6.2 and 6.3
IRU88DQGVHFWLRQIRU,,
7KHGHVFULSWLRQRISDUDPHWHUV33WKDWPD\EHGLVSOD\HG
are included in the installation instructions that come with the
option pcb.
User
Adjustable
parameter
Description
Setting range
Factory setting
Installer
U 1
Volume step 1
PD[
100
U 2
Volume step 2
PD[
M300DC 150
400DC 200
U 3
Volume step 3
50..300 (M300DC)
50..400 (400DC)
225 M300DC
300 400DC
U 4
Minimum atmospheric temperature
bypass
5 .. 20
10
U 5
Minimum indoor temperature bypass
18 .. 30
22
U 8
Not applicable
0.1
0 (off)
I 1
Fixed imbalance
0
I 2
No contact step
0,1,2,3
1
I 3
Not applicable
2.3
2
I 4
Switch line 1 step
0,1,2,3
1
I 5
Switch line 2 step
0,1,2,3
2
I 6
Switch line 3 step
0,1,2,3
3
I 7
Imbalance permissible
0.1
1 (Yes)
I 8
Bypass mode
0,1,2
1
I 9
Hysteresis bypass
0 .. 5
2
I10
Constant pressure switched off
0.1
0 (no)
I11
Preheater or postheater
0, 1, 2, 3
0
I12
Offset temperature preheater
0.5
I13
Filter message on/off
1.0
1 (on)
I14
Option pcb present
1.0
0 (no)
I15
+HDWUHFRYHU\FRQ¿JXUDWLRQ
0.1
0 (heat recovery)
I16
Fan off
1,2,3
1 (Output fan)
I17
Repeat time
1 .. 24
24 (hours)
I18
0LQLPXPVZLWFKRIIWLPHIDQV
1 .. 240
60 (seconds)
I19
0LQLPXPVZLWFKRIIWLPHIDQVDIWHU
switching on 230V.
1 .. 240
1 (second)
7KHXVHUDGMXVWDEOHSDUDPHWHUVDUHLQGLFDWHGZLWK³8´WKHLQ
VWDOOHUDGMXVWDEOHSDUDPHWHUVDUHLQGLFDWHGZLWK³,´EDVLFSFE
or “P”(option pcb).