VEAB EA Series Скачать руководство пользователя страница 5

Specification

Type

EA 6

EA 9

EA 14

EA 21

EA 30

Rated voltage

400V3N~ 50Hz

400V3N~ 50Hz

400V3N~ 50Hz

400V3N~ 50Hz

400V3N~ 50Hz

Rated power

6 kW

9 kW

14 kW

21 kW

30 kW

Reduced power

3 kW

6 kW

7 kW

14 kW

20 kW

Rated current

8,7 A

13,0 A

20,3 A

30,4 A

43,5 A

A

157 mm

157 mm

220 mm

220 mm

220 mm

B

425 mm

425 mm

600 mm

600 mm

600 mm

W

390 mm

390 mm

555 mm

555 mm

555 mm

H

450 mm

450 mm

600 mm

600 mm

600 mm

D

270 mm

270 mm

375 mm

375 mm

465 mm

Master EA heater

#1 slave EA heater 1

#2 slave EA heater

# n slave

12

EA

Slave controlling several heaters

One EA heater can slave control several other EA heaters. The Master EA can be controlled either by the 

OCC4/OCD4, TG-R430 or by a 0...10VDC (2...10VDC) excitation voltage. The slave heaters are cascaded 

by the 0...10VDC voltage and the excitation cable length, from one heater to another, must not exceed 16m.

1.   The  EA heater series are approved for fixed installation in dry, damp or wet rooms but not in 

  environments where there is risk for fire or explosion.

2.  The heater must be connected to the mains supply with a fixed installed round cable, 

  which ensures that the electrical protection class of the heater is retained.

3.  An all phase breaker with a contact gap of at least 3mm must be included in the fixed installation.

4.  The installation must be carried out by an authorized electrician.

5.   The heater is S-marked, CE-marked, EMC-marked and designed in accordance with the following standards 

  EN 60335-1 / EN 60335-2-30 / EN 61000-6-4 / EN 61000-6-1 / EN 61000-6-2 / EN 61000-6-3.

6.  The heater must not be located immediately below a socket outlet.

Mounting

1.   The heater brackets are to be fastened to the wall or to the ceiling with screws. 

  The distances shown in the above sketch are minimum. Distances less then shown may cause fire.

2.  The connection box must always be positioned upwards.

3.  The heater must not be covered or tampered with, to avoid overheating, fire or electric shock.

Maintenance

No maintenance is required except a periodic functional test and cleaning.

Overheatig

The heater is thermally protected by an overheat cut-out with manual reset, with the the reset button placed 

on the lid of the connection box.