Operating manual
Document nr. : 010346
Version :
V1.4
MC 785-DF KLIMA ALFANET
Client : General
Page :
9 of 20
Nr
Description
Range
Unit
Default
P 40
P 41
P 42
P 43
P 44
P 45
P 46
P 47
P 48
Type temperature alarm
0 =
No alarm
1 =
Absolute alarm
2 =
Relative to setpoint
Minimum alarm temperature
Maximum alarm temperature
Minimum alarm delay
Maximum alarm delay
Temperature control-off at minimum alarm
Temperature control-off at maximum alarm
Humidity control-off at min. temp. alarm
Humidity control-off at max. temp. alarm
0..2
-40..+50
-40..+50
0..99
0..99
0 = no, 1 = yes
0 = no, 1 = yes
0 = no, 1 = yes
0 = no, 1 = yes
-
E
C
E
C
minutes
minutes
-
-
-
-
1
-40.0
+50.0
0
0
0
0
0
0
P 50
P 51
P 52
P 53
P 54
P 55
P 56
Type RH alarm
0 =
No alarm
1 =
Absolute alarm
2 =
Relative to setpoint
Minimum RH alarm
Maximum RH alarm
Minimum alarm delay
Maximum alarm delay
RH control-off at minimum alarm
RH control-off at maximum alarm
0..2
-100..100
0..100
0..99
0..99
0 = no, 1 = yes
0 = no, 1 = yes
-
% RH
% RH
minutes
minutes
-
-
1
0
100
0
0
0
0
P 60
P 61
P 62
P 63
P 64
P 65
P 66
P 67
Function analog CH-1
0 =
Measured temperature
1 =
Measured RH
2 =
Temperature setpoint
3 =
RH setpoint
4 =
P(I) cooling
5 =
P(I) heating
6 =
P(I) dehumidifying
7 =
P(I) humidifying
0 V output at
10 V output at
Proportional range
Offset proportional range
Interval value
(999 give only P)
As puls/pauze
Puls/pause cycle time
0..7
-100..+100
-100..+100
0.1..15
-15..+15
1..999
0 = no, 1 = yes
5..240
-
-
-
-
-
minutes
-
seconds
0
-40.0
+50.0
1.0
0.0
999
0
20