* Parameters ALFANET 53

Para-
meter

Description Parameter

Range

Default

01

02
03

Function Relay 1
 0 = Non
 1 = Minimum Control alarm
 2 = Maximum Control alarm
 3 = Minimum Fail safe alarm
 4 = Maximum Fail safe alarm
 5 = Minimum Fail safe alarm
     + Sensor failure
 6 = Maximum Fail safe alarm
     + Sensor failure
 7 = Sensor failure
Function Relay 2
Function Relay 3

0..7

0..7
0..7

1

2
0

05

Offset temperature sensor

-15.0..+15.0

C

0.0

10
11
12
13
14
15

Switching differential Relay 1
Switching offset Relay 1
Switching differential Relay 2
Switching offset Relay 2
Switching differential Relay 3
Switching offset Relay 3

0.1..15.0

C

-15..+15

C

0.1..15.0

C

-15..+15

C

0.1..15.0

C

-15..+15

C

0.5
0.0
0.5
0.0
0.5
0.0

20
21

Minimum adjustable set point
Maximum adjustable set point

-50.0..+50.0

C

-50.0..+50.0

C

-50
+50

30
31
32

33

Time delay minimum alarm
Time delay maximum alarm
Reset alarm relay after recovering 
 alarm
Reset alarm relais after manual
 reset

0..99 Minutes
0..99 Minutes
0= No
1= Yes
0= No
1= Yes

0
0
0

0

40

Control delay after power failure

0..99 Minutes

0

90
95
96
97
98
99

Network number
Software version
Production year
Production week
Serial number (x1000)
Serial number (Units)

1..255
0..255
00..99
1..52
0..255
0..999

1
-
-
-
-
-

* Address.