ALFA(NET) 71 PI -10/+90°C
Doc.no.: 151043 version 1.1
Pagina 5 van 8
Para-
meter
Description Parameter
Range
Default
value
25
Minimum adjustable setpoint
-10.0 .. +90.0°C
-10.0
26
Maximum adjustable setpoint
-10.0 .. +90.0°C
+90.0
27
Readout in whole degrees
0 = No, 1 =Yes
0
30
Alarm type
0 = None
1 = Absolute
2 = Relative
0 .. 2
1
31
Minimum alarm setpoint
-10.0 .. +90.0°C
-10.0
32
Maximum alarm setpoint
-10.0 .. +90.0°C
+90.0
33
Time delay minimum alarm
0 .. 99 Minutes
0
34
Time delay maximum alarm
0 .. 99 Minutes
0
35
Function alarm relay
0 = Watch alarm
1 = Control alarm
0 .. 1
0
36
Reset alarm relay after recovering alarm
0 = No, 1 =Yes
0
37
Reset alarm relay after manual reset
0 = No, 1 =Yes
0
40
Start-up delay after power failure *
0 .. 99 Minutes
0
41
Forced relay function at sensor failure
0 = None
1 = Cool
2 = Heat
0 .. 2
0
90
Network number
(only at ALFANET)
1..250
1
95
Software version
-
-
96
Production year
-
-
97
Production week
-
-
98
Serial number (x1000)
-
-
99
Serial number (units)
-
-
*) These parameters are only applied to relays with function cool or heat.