VDH ALFA(NET) 31 Скачать руководство пользователя страница 3

3

* Parameters ALFA(NET) 31.

PARA-
METER

DESCRIPTION PARAMETER

RANGE

STANDARD
VALUE

01

02

03

04

Switching differential

Minimum setpoint

Maximum setpoint

Offset temperature sensor

1..15

C

0..+100

C

0..+100

C

-15..+15

C

3

0

+100

0

10

11

Startup delay after power failure

Relays on at sensor failure

0..99 min.

0 = No

1 = Yes

0

0

15

16

17

18

19

20

Function cooling or heating

Switch on delay relays   1)

Switch off delay relays  1)

Parameter 16/17 in sec. or min.

Minimum on-time relays

Minimum off-time relays

0 = Cool

1 = Heat

0..99

0..99

0 = sec.

1 = min.

0..99 min.

0..99 min.

0

0

0

0

0

0

90

95

96

97

98

99

Network number

Software version

Production year

Production week

Serial number (x1000)

Serial number (units)

1..250

0..255

00..99

1..52

0..255

0..999

1

-

-

-

-

-

1) On active delay led 'on' blinks.

* Function Diagram.