VDH ALFA 75-MTT Скачать руководство пользователя страница 2

2

* Parameters ALFA 75-MTT.

Para-
meter

Description Parameter

Range

Default
value

01
02
03
04

Switching differential
Minimum adjustable set point
Maximum adjustable set point
Offset temperature sensor

0,1..15,0

C

0..+80

C

0..+80

C

-15,0..+15,0

C

0,5
0,0

15,0

0,0

10
11
12

Agitator interval time
Agitator runtime
Agitator delay time

0..60 Minutes
0..240 Seconds
0..900 Seconds

15

120
120

20
21
22
23
24
25
26
30

Minimum Alarm active
Maximum Alarm active
Minimum Alarm-set point 
Maximum Alarm-set point
Delay time maximum alarm 
Delay time minimum alarm
Cooling time alarm (See description)
Control delay after power up

0=No, 1=Yes
0=No, 1=Yes
0..80,0

C

0..80,0

C

0..99 Minutes
0..99 Minutes
90..240 Minutes
0..99 Minutes

1
1

0,5

15,0

45

0

120

15

31
32

Cooling on at sensor failure
Cooling off at minimum alarm

0=No, 1=Yes
0=No, 1=Yes

0
1

40

Function digital input cleaning
   0 = Active when closed (NO)
   1 = Active when opened (NC)

0..1

0

95
96
97
98
99

Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

0..255
00..99
1..52
0..255
0..999

-
-
-
-
-

* Sensor adjustment.

The temperature sensor can be adjusted by using the Offset control sensor (parameter 04).
Indicates a sensor e.g. 2

C too much, the according Sensor-offset parameter has to be decreased with 2

C.

* Error codes.

On the display from the 

ALFA 75-MTT

 can appear the following error codes:

E1

- Temperature sensor defect.

Solution 

E1

 failure:

- Check if sensor is connected correctly.
- Check sensor (1000

/25

C).

- Replace sensor..

EEE

- Adjustments are lost

Solution 

EEE

 failure:

  

- Re-program the adjustments.

LO

- Minimum alarm.

HI

- Maximum alarm.

AL

- Cooling time passed

-L-

- In case of sensor short-circuit the display alternates between error-code 

E..

  and 

-L-

, as indication for a short-circuit sensor.

-H-

- In case of open-circuit sensor the display alternates between error-code 

E..

 

 and 

-H-

, as indication for  a open circuit sensor.

* Alarm operation.

If a failure or alarm occurs an error message is shown in the display. The 

ALFA 75-MTT

 remembers it’s error

message, although it is already solved. The error message can be reset with the 

SET

 key.  

If after pressing the 

SET

 key (=reset alarm) the alarm still is not solved than the 

ALFA 55-MTT

 displays  the

temperature and the error message alternated, is the alarm solved, then the error message disappears and the
temperature is displayed normally.