* Parameters ALFA 59

Para-
meter

Description Parameter

Range

Default
Value

01

02

03

Function Relays 1

Function Relays 2

Function Relays 3

1=Humidify
2=Dehumidify
3=Alarm
1=Humidify
2=Dehumidify
3=Alarm
1=Humidify
2=Dehumidify
3=Alarm

1

2

3

05

Offset Humidity sensor

-15..+15%RH

0

10
11
12
13
14
15

Switching differential relay 1
Switching offset relay 1
Switching differential relay 2
Switching offset relay 2
Switching differential relay 3
Switching offset relay 3

1..15%RH
-15..+15%RH
1..15%RH
-15..+15%RH
1..15%RH
-15..+15%RH

1
0
1
0
1
0

20
21

Minimum set point
Maximum set point

0..100%RH
0..100%RH

0

100

30

31
32
33
34
35

36

37

Alarm mode

Minimum alarm set point
Maximum alarm set point
Time-delay minimum alarm
Time-delay maximum alarm
Function alarm relay

Auto reset alarm after failure
recovering 
Manual reset alarm relay with set key

0= None
1= Absolute
2= Relative
0..100%RH
0..100%RH
0..99 min.
0..99 min.
0= fail safe al.
1= control al.
0= No
1= Yes
0= No
1= Yes

1

0

100

0
0
0

0

0

40
41

Control-delay after power failure
Forced relay function at sensor failure

0..99 min.
0= None 
1= Humidify
2= Dehumidify

0
0

95
96
97
98
99

Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

0..255
00..99
1..52
0..255
0..999

0
0
1
0
0