* Setting internal parameters.
Next to the adjustment of the setpoint, some internal settings are possible like differential, sensor-
offset, set point range and the function humidify or dehumidify.
By pushing the
DOWN
key more than 10 seconds, you enter the 'internal programming menu'. In the
left display the upper and lower segment are blinking. Over the
UP
and
DOWN
keys the required
parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the
SET
key. Pushing the
UP
or
DOWN
keys together with the
SET
key allows you to change the value of this parameter.
If after 20 seconds no key is pushed, the
ALFA(NET) 19
changes to it's normal operation mode.
* Parameters ALFA(NET) 19.
PARA-
METER
DESCRIPTION PARAMETER
RANGE
STANDARD
VALUE
01
02
03
04
Switching differential
Minimum set point
Maximum set point
Offset humidiy sensor
1..15 %RH
0..100 %RH
0..100 %RH
-15..+15 %RH
3
0
100
0
10
Startup delay after power failure
0..99 Minutes
0
15
16
17
18
19
20
Function hygrostat
Switch on delay relay
1)
Switch off delay relay
1)
Parameter 16/17 in sec. or min.
Minimum on-time relay
Minimum off-time relay
0 = Dehumidify
1 = Humidify
0..99
0..99
0 = Seconds
1 = Minutes
0..99 Minutes
0..99 Minutes
0
0
0
0
0
0
90
95
96
97
98
99
Network number
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)
1..250
0..255
00..99
1..52
0..255
0..999
1
-
-
-
-
-
1) If delay is active, the led will flash
*
Address.