background image

1

User manual 
ALFA 15 and
ALFANET 15

Cool/Defrost Thermostat.

VDH doc. 061283

Version: v2.1

Date: 05-12-2007

Software: 043376_ALFA 15/25/35

File: Do061283.wpd

Range: -50/+50

C per 1

C

* Function.

The 

ALFA(NET) 15 

 is a digital thermostat for rail mounting. The thermostat controls  the cooling and

defrost. The temperature readout is in hole degrees Celsius. 
Defrost will be done by temporarily switching off the cooling (natural defrost). The defrost starts on
intervals or on compressor runtime. The defrost stops on time.
The 

ALFA

NET

 15

 has a RS 485 network connection so it can be read out and adjusted on the Alfanet.

* Installation.

On the connection diagram of the 

ALFA(NET) 15 

 you can see how the sensor, power supply and relay

have to be connected.
After connecting the 

ALFA(NET) 15 

 to the power supply, a self test function is started. As this test is

finished the measured temperature appears in the display.
When the relay is activated, the led 'on' will light-up in the display.

* Control.

The 

ALFA(NET) 15 

 thermostat can be controlled by three pushbuttons on the front. These keys are:

SET

 

- view / change the setpoint.

UP

 

- increase the setpoint.

DOWN

- decrease the setpoint.

* Viewing setpoint.

By pushing the 

SET

 key the setpoint appears in the display. The led 'set' starts blinking. A few seconds

after releasing the 

SET

 key the setpoint disappears and the measured temperature is shown in the

display.

* Changing setpoint.

Push the 

SET

 key and the setpoint appears in the display. Release the 

SET

 key. Now push the 

SET

key again and together with the 

UP

 or 

DOWN

 keys the setpoint can be changed. A few seconds after

releasing the keys the measured temperature is show in the display.

Отзывы: