3

* Setting internal parameters.

Next  to  the  adjustment  of  the  setpoint,  some  other  internal  settings  are  possible,  like  differential,
sensor-offset, setpoint range.
By pushing the 

DOWN

 key more than 10 seconds, you enter the 'internal programming menu'. In

the  left  display  the  upper  and  lower  segment  are  blinking.  With  the 

UP

  and 

DOWN

  keys  the

required  parameter  can  be  selected  (see  table  for  the  parameters).  If  the  required  parameter  is
selected,  the  value  can  be  read-out  by  pushing  the 

SET

  key.  Pushing  the 

UP

  and 

DOWN

  keys

allows you to change the value of this parameter.
If after 20 seconds no key is pushed, the 

ALFA(NET) 13

 changes to it's normal operation mode.

* Parameters ALFA(NET) 13.

PARA-
ME-
TER

DESCRIPTION PARAMETER

RANGE

STANDARD
VALUE

02
03
04

Minimum setpoint
Maximum setpoint
Offset temperature sensor

0/+100

C

0/+100

C

-15/+15

C

0

+100

0

10
11

Startup delay after power failure
Relay on at sensor failure

0..99 Minutes
0 = No, 1 = Yes

0
0

21
22
23
24
25
26
27

28

Differential maximum alarm
Differential minimum alarm
Time delay maximum alarm
Time delay minimum alarm
Offset setpoint High (Max.)
Offset setpoint Low (Min.)
Relay alarm function

(0=watchdog 1=regulated alarm)

Auto reset alarm after temperature recovering

(0=hold)

1..15

C

1..15

C

0..99 Minutes
0..99 Minutes
0/+20

C

-20/0

C

0 = No, 1 = Yes

0 = No, 1 = Yes

1
1
0
0
0
0
0

0

90
95
96
97
98
99

Network number
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

1..250
0..255
00..99
1..52
0..255
0..999

1

-
-
-
-
-

* Function diagram.

Содержание ALFA 13

Страница 1: ... a self test function is started As this test is finished the measured temperature appears in the display The relay is normally activated and with an alarm it is deactivated and the led alarm will light up in the display Control The ALFA NET 13 alarm thermostat can be controlled by three push buttons on the front SET view change setpoints and reset of alarm UP increase a setpoint DOWN decrease a s...

Страница 2: ...erature will recover within the delay time no alarm occurs If an alarm will continue after the delay time the led alarm burns continuously and the display alternates between the temperature and H for high alarm max or L for low alarm min to indicate the alarm To reset an alarm press the SET key Adjustment sensor The sensor can be adjusted by using the Sensor Offset parameter 04 Indicates the ALFA ...

Страница 3: ...l operation mode Parameters ALFA NET 13 PARA ME TER DESCRIPTION PARAMETER RANGE STANDARD VALUE 02 03 04 Minimum setpoint Maximum setpoint Offset temperature sensor 0 100 C 0 100 C 15 15 C 0 100 0 10 11 Startup delay after power failure Relay on at sensor failure 0 99 Minutes 0 No 1 Yes 0 0 21 22 23 24 25 26 27 28 Differential maximum alarm Differential minimum alarm Time delay maximum alarm Time d...

Страница 4: ...4 Dimensions Connections Address VDH Products BV Tel 31 0 50 30 28 900 Produktieweg 1 Fax 31 0 50 30 28 980 9301 ZR Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Отзывы: