User manual
ALFA 13 DP Pt100 and
ALFANET 13 DP Pt100

Min./Max. Alarm Thermostat.

VDH doc. 072376

Version: v2.0

Date: 12-11-2007

Software: 053308_ALFA 13/33DP

File: Do072376.wpd

Range: -10/+40

C per 0,1

C

* Function.

The 

ALFA(NET)  13  DP  Pt100

  is  a  digital  alarm  thermostat  for  rail  mounting.  The  thermostat

watches the minimum and maximum temperature. The temperature readout is in tenth of degrees
Celsius. The 

ALFA(NET) 13 DP Pt100

 has one relay for both alarms.

The 

ALFA

NET

 13 DP

 has a RS 485 network connection so it can be read out and adjusted on the

Alfanet. 

* Installation.

On the connection diagram of the 

ALFA(NET) 13 DP Pt100

 is shown how the sensor, power supply

and relay are connected.
After connecting the 

ALFA(NET) 13 DP Pt100

 to the power supply, a self-test function is started. As

this test is finished, the measured temperature appears in the display.
The relay is normally activated, and with an alarm it is deactivated, and the led 'set high' will be lit in
the display.

* Control.

The 

ALFA 13 DP Pt100

 alarm-thermostat can be controlled by three push buttons on the front;

SET

- view / change set points and reset of alarm.

UP

 

- increase a set point.

DOWN

- decrease a set point.

* Viewing set points.

Viewing set point of maximum alarm:

By  pushing  the 

SET

  key  first  and  then  the 

UP

  key  together  the  maximum  alarm  set  point

appears in the display. The led 'set high' starts blinking.

Viewing set point of minimum alarm:

By  pushing  the 

SET

  key  first  and  then  the 

DOWN

  key  together  the  maximum  alarm  set  point

appears in the display. The led 'set low' starts blinking.

A few seconds after releasing the keys the set point disappears and the measured temperature is
shown in the display.

Содержание ALFA 13 DP Pt100

Страница 1: ...he power supply a self test function is started As this test is finished the measured temperature appears in the display The relay is normally activated and with an alarm it is deactivated and the led set high will be lit in the display Control The ALFA 13 DP Pt100 alarm thermostat can be controlled by three push buttons on the front SET view change set points and reset of alarm UP increase a set ...

Страница 2: ...will recover within the delay time no alarm occurs If an alarm will continue after the delay time the led set high burns continuously and the display alternates between the temperature and H for high alarm max or L for low alarm min to indicate the alarm To reset an alarm press the SET key Adjustment sensor The sensor can be adjusted by using the Sensor Offset parameter 04 Indicates the ALFA NET 1...

Страница 3: ...ges to it s normal operation mode Parameters ALFA NET 13 DP Pt100 Para meter Description Parameter Range Standard Value 04 10 11 21 22 23 24 25 26 27 28 Offset temperature sensor Startup delay after power failure Relay on at sensor failure Differential maximum alarm Differential minimum alarm Time delay maximum alarm Time delay minimum alarm Offset setpoint High Max Offset setpoint Low Min Relay a...

Страница 4: ...4 Dimensions Connections Address VDH Products BV Tel 31 0 50 30 28 900 Produktieweg 1 Fax 31 0 50 30 28 980 9301 ZR Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Отзывы: