Operating manual
Document nr. : 022091
Version : V2.3
MC 785-SC
Client : General
Page : 17 of 32
P-Nr
Description
Range
Unit
De-
fault
P410
P411
P412
P413
P414
Condenser-8
type:
0 = Not present
1 = On/off
2 = 2-speed (0-50%-100%)
On/off relay Condenser-8
Relay for 50% 100%
Relay is active at 100% drive
Analog output Condenser-8 (0-10V)
Failure input Condenser-8
0..2
-- .. 4 7
-- .. 4 7
-- .. 4 4
-- .. 4nc6
-
-
*
-
*
-
$
-
#
0
--
--
--
--
Parameters for external setpoints
P500
P501
P510
P511
P520
P521
External compressors setpoint input-1
External compressors setpoint-1
External compressors setpoint input-2
External compressors setpoint-2
External compressors setpoint input-3
External compressors setpoint-3
-- .. 4nc6
-1.0..50.0
-- .. 4nc6
-1.0..50.0
-- .. 4nc6
-1.0..50.0
-
#
Bar
-
#
Bar
-
#
Bar
--
0.0
--
0.0
--
0.0
Parameters for Network
P800
P801
Network number
Log interval
1..250
1..120
-
Minute
s
15
Parameters Software/Series number etc.
P991
P992
P993
P999
Software version no.
Serial number
Production date (year/week)
Password
(0000 = password not active)
-
-
-
0000..9999
-
-
-
-
-
-
-
1234
Key to symbols:
*) = See table of assignment of relay outputs
#) = See table of assignment of digital inputs
$) = See table of assignment of analog outputs
Remarks about P13 to P15:
Whit P13 it is possible to enter a limit for switching on the first compressor. As soon as the
pressure is higher then P13 the first compressor will switch on without delay. The minimal off
time (P20) will still be valid.
If the value from P15 is lower then the value of P14 then the value of P14 will be used. If
another step has to switch on, the value of P15 will be used.
Remarks about P500 to P521:
When one or more inputs are closed the input with the lowest setpoint will be active as setpoint
for the compressors!
During the readout of the setpoint a flashing ‘c’ will indicate that an input is active. In this mode
the set point CANNOT be changed.