* Adjusting the sensor.

The temperature sensor can be adjusted by using the Offset control sensor (parameter 04).
Indicates a sensor e.g. 2

C too much, the according Sensor-offset parameter has to be decreased with

2

C.

* Error codes.

On the display from the 

ALFA(NET) 31 BS

 can appear the following error codes:

ES

 

- Set point wrong adjusted, action relay off. 

(On and off set point are on the wrong side of each other) 

Er

- Sensor defect.  Solution:

- Check if sensor is connected correctly.
- Check sensor (1000

/25

C).

- Replace sensor..

EE

- Adjustments are lost.  Solution:

- Reprogram the adjustments.

* Technical details.

Type

: ALFA(NET) 31 BS Heater Thermostat

Range

: -50/+50

C, read out  per 1

C

Supply

: 230 Vac 50/60Hz

Relay

: SPDT 250V/16A(C-NO), 8A(C-NC) (cos 

=1)

Communication

: RS 485 Netwok (2xtwisted pair shielded) only on ALFANET models.

Control

: Through pushbuttons on the front.

Front

: Polycarbonate IP65

Sensor

: SM 811/2m.

Dimensions

: 31 x 77 x 71,5mm (hwd)

Panel cut out

: 28 x 70mm (hw)

- Provided with memory protection during power failure.
- Equipped with self-test function and sensor-failure detection.
- Connection with screw-terminals.
- Special version on request available.

* Adjusting internal parameters.

Next to the adjustment of the set point, some internal settings can be made like differentials, sensor
offset and alarm functions.

By pushing the 

DOWN

 key for more than 10 seconds, you enter the  'internal programming menu'. 

On the left display the upper and the lower segments are flashing. Over the 

UP

 and 

DOWN

 keys the

required parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing the

UP

 and 

DOWN

 keys allows you to change the value of this parameter.

If no key is pushed for 20 seconds, the 

ALFA(NET) 31 BS

 changes to it’s normal operation mode.