Installation

1.  Open the automatic control cabinet by undoing the 

screws that hold the lid, 28, together and the bottom 

section, 27. Undo the cables and the screws, 21, from 

the immersion heater.

2.  Separate the elements on the immersion heater a little 

before it is screwed in.

3.  Fill with water, vent and check that it is sealed.
4.  Screw the bottom section tightly to the immersion heater using the 

screws, 21. Before they are tightened, adjust the position of the 

automatic control cabinet. Tighten the screws well and check that 

the bottom section cannot slide against the head of the immersion 

heater.

5.  Straighten out capillary tubes to the sensors, 25 and 26, so they 

are as straight as possible and insert them in the sensor tube until 

they reach the bottom. The capillary tubes must be handled care-

fully. In the event of damage, the thermostat/overheating protec

-

tion must be replaced.

Electrical installation

Component

art. no.

1

Terminal block

2

Indicator light

19 00 01

3

All-pole switch

13 00 05

4

 Thermostat/ 
overheat protection 
Thermostat dial

12 00 01

 

 

12 00 05

5

Heating  element 230/400V 

VB 1510

 

VB 2210

 

VB 9010

 

11 00 02

 

11 00 04

 

11 00 21

6

Heating  element 400V 

VB 3010

 

VB 4510

 

VB 6010

 

VB 6010L

 

VB 6010 CU

 

11 00 07

 

11 00 11

 

11 00 16

 

11 00 64
11 00 46

Auto matic control cabinet, 

complete 

VB 1510

 

VB 2210

 

VB 3010

 

VB 4510

 

VB 6010

 
 

199 01

 

199 02

 

199 03

 

199 04

 

199 05

VB 1510 - 9010 400V 3~

VB 1510 - 2210, 230 V

12

22

32

11

21

31

STB

TR

12

22

32

11

21

31

STB

TR

6.  Connect the cables to the immer-

sion heater. Check at the same time that 

the cable lugs are firmly clamped to the 

immersion heater connections.

7. Tighten the cover to the bottom section.

The capillary tubes must not be in contact with any live parts! 

Before the screws to the cover are tightened fully, check that 

no cables or capillary tubes are trapped between the bottom 

section and cover or lying in an unsuitable position within the 

automatic control cabinet! 

To obtain a good electrical connection, a loosened flat cable 

lug must always be clamped together before it is reassembled!

26

25

27

28

21

15

Electrical installation must be carried out in accordance with 

the applicable regulations, by an authorised electrical installer 

or by someone who is covered by the company's self-inspection 

programme!
All electrical connection must be with high-voltage insulated cable.
The immersion heater must be mounted horizontally.
Installation must be performed so the automatic control cabinet 

is not exposed to damaging heat radiation e.g. blazing flames 

from the door to insert wood.

The immersion heater is installed in a 2" sleeve on the boiler, 

storage tank or K-060 tank.
The immersion heater is not suitable for heating water (oxygen-

ated water).

Due to galvanic corrosion, a stainless steel immersion heater 

must not be installed in a copper vessel.

Alkalinity ≥ 60 mg/l to avoid corrosion.

Carbonic acid content > 25 mg/l increases the risk of corrosion.
Sulphate content > 100 mg/l may accelerate corrosion. If the 

sulphate content is higher than the alkalinity, there is a risk of 

copper corrosion.
Hard water causes boiler scale and is not suitable in a heating 

system.

Very soft water may cause corrosion damage.
Chloride levels above 100 mg/l make the water aggressive, es

-

pecially in combination with lime deposits.
Low pH values may cause corrosion damage. The pH value 

should be 7.5- 8.5.
The presence of carbonic acid in combination with low pH and 

hardness values makes the water aggressive.
The water must not contain sludge or other contaminants.