Värmebaronen EK 13

Flow

The electric cartridge requires a constant adequate flow to work. If 

the heating system's valves are able to throttle circulation, an over-

flow valve must be installed.

The circulation pump must press the 

water through the cartridge with the 

flow direction shown in the figure.

Recommended flow: 0.3 litre/second, 

t = 10 °C.

Flow too low:  •  High difference between desired temperature 

and achieved temperature.

•  Irregular control with increased wear on the

electromechanical components, with reduced 

service life as a result.

•  Increased risk of the overheating protection

being triggered.

Flow too high:  •  Vibrations in the immersion heaters with noise 

and reduced service life as a result.

• Unnecessary wear on the system's components.

Pressure drop diagram

Freestanding heating unit

EK 13 must be connected to:

Open system:   

The expansion tank is connected in an unbroken, 

uninterruptible connection to the cartridge. The 

distance between the top of the highest radiator 

and the tank may not be less than 2.5 metres to 

avoid oxygenation of the heating system.

Closed system:   

The cartridge is connected to a closed expansion 

tank and in an unbroken, uninterruptible 

connection to a type-approved safety valve 

with maximum 3 bar opening pressure and an 

automatic vent valve.

Pipe installation

Installation must take place according to existing regulations 

and standards.
The cartridge must be located indoors in a suitable location.
The cartridge must be installed horizontal with the pipe 

connections vertical so that air that is released can escape.
The cartridge must be connected to an open or closed expan-
sion system.
A system with a closed expansion tank must undergo an 

installation inspection prior to first operation. The inspection 

must be carried out by a person who is qualified for the task. 

The electric cartridge or expansion tank may not be replaced 

without another inspection.

System principles

The system must be installed according to existing rules and 
standards.

Radiator system

A

G

C

F

B

D

E

H

D

Underfloor heating system

E

A

C

B

D

D

G

I

F

With boiler

A

D

C

B

H

C

J

A. EK 13

F. Drain valve

B. Expansion tank, open

G. Bypass/overflow valve

C. Circulation pump

H. Radiator system

D. Stop valves

I. Underfloor heating system

E. Filling valve

J. Boiler

Содержание EK 13

Страница 1: ...2 1 1 2 2 0 1 1 Installation and maintenance Electric cartridge EK 13...

Страница 2: ...External blocking Connection delay after power cut Limitation of power Load guard Electrical installation wiring diagram 7 Control panel 8 Operation and maintenance 8 General Operation Overheating pro...

Страница 3: ...3 V rmebaronen EK 13 Tel Notes Production number Installation date Installer Other To be completed when the cartridge is installed...

Страница 4: ...n free The system must be leakproof so that the water does not need to be replaced with new oxygen rich water and the water is not oxygenated during installation Water quality in respect of suitable t...

Страница 5: ...oxygenation of the heating system Closed system The cartridge is connected to a closed expansion tank and in an unbroken uninterruptible connection to a type approved safety valve with maximum 3 bar...

Страница 6: ...rating mode and open in idle mode 25 4 1 To external control unit Connection delay after power cut The electric cartridge has connection delayed power stages after a power cut according to the standar...

Страница 7: ...ower group three 3 kW 15 Indicator power stage two 16 Indicator power stage three 17 Thermostat power stages two and three 18 Printed circuit board 19 Relay group power stage two 20 Relay group power...

Страница 8: ...Otherwise it works in the same way as the thermostat for power stage one Overheating protection The electric cartridge has overheating protection that is triggered when the temperature exceeds approxi...

Страница 9: ...circuit is Take action Then reset the miniature circuit breaker Operating indicators for stages two and three off Stage one on Miniature circuit breaker on circuit board triggered Check where the sho...

Страница 10: ...e EK 13 1 1 160003 12 pole terminal block 1 160006 End plate 1 160009 2 pole bridge 2 160011 4 pole bridge 1 9 170046 Contactor 230 V 1 7 180021 Miniature circuit breaker 10 A 1 11 15 16 190002 Indica...

Страница 11: ......

Страница 12: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 Fax 46 44 22 63 58 www varmebaronen se www varmebaronen com info varmebaronen se...

Отзывы: