Fuses and circuit breakers
The control device is able to protect the motor from overload by means of digital control of the absorbed
current with reference to the set nominal current.
It is therefore, not necessary to install any other overload protection device between the inverter and the
motor.
Instead, it is necessary to install upstream of the device overcurrent and short-circuit protection devices
such as fuses and circuit breakers. These intervene in the event of failure of a component inside the
device.
Supply voltage
Model
Recommended fuse
gC
Recommended circuit breaker
ABB MCB S200
3 x 380 - 460 VAC
PSDrive 11
10
S203-C10
3 x 380 - 460 VAC
PSDrive 22
10
S203-C10
3 x 380 - 460 VAC
PSDrive 40
16
S203-C16
3 x 380 - 460 VAC
PSDrive 55
20
S203-C20
3 x 380 - 460 VAC
PSDrive 75
25
S203-C25
3 x 380 - 460 VAC
PSDrive 110
30
S203-C32
3 x 380 - 460 VAC
PSDrive 150
35
S203-C40
3 x 380 - 460 VAC
PSDrive 185
50
S203-C50
3 x 380 - 460 VAC
PSDrive 220
63
S203-C63
Residual Current Devices (RCD)
For inverter devices with three-phase power supply, it is recommended to use RCD devices that are
sensitive to both alternating and direct current. The devices shown are:
• Type B, marked with the symbols
7.3. Connecting cables
WARNING
The connecting cables must comply with local regulations, have the appropriate cross-
section, and meet the requirements for voltage, current, and temperature.
7.3.1. Power cables
Model
Maximum section
of the input cable
with earth
Maximum section
of the output cable
with earth
Cable tightening
torque [Nm]
Ground cable
tightening torque
PSDrive 11
4 x 2,5 mm
2
4 x 2,5 mm
2
-
-
PSDrive 22
4 x 2,5 mm
2
4 x 2,5 mm
2
-
-
PSDrive 40
4 x 2,5 mm
2
4 x 2,5 mm
2
-
-
PSDrive 55
4 x 6 mm
2
4 x 6 mm
2
1
3
PSDrive 75
4 x 6 mm
2
4 x 6 mm
2
1
3
PSDrive 110
4 x 6 mm
2
4 x 6 mm
2
1,5
3
PSDrive 150
4 x 6 mm
2
4 x 6 mm
2
1,5
3
PSDrive 185
4 x 16 mm
2
4 x 16 mm
2
1,5
3
PSDrive 220
4 x 16 mm
2
4 x 16 mm
2
1,5
3