Pumped Manifold (PVST) [1/3]
Fixed value control station for surface heating
with existing main pump
HEATING. COOLING. COMFORT.
e980313
Consumers
with
presettable
flow rate
Temperature limiter
Factory setting 60 °C
Immersion sleeve with
flow temperature sensor
with heat transfer paste
(Safety data sheet: www.variotherm.at)
Fixed value regulator
with remote sensor
Heat generator
e.g. gas, oil, solid
fuel boiler, remote
heating and buffer
Room
thermostat
PIANO H
Regulating valve
Setting the fixed value regulator
1
2
3
4
5
6
7
20 °C
28 °C
37 °C
45 °C
53 °C
62 °C
70 °C
• The boiler flow temperature must be at least 10 K higher than the set
flow temperature of the surface heating .
• The temperature can be continuously adjusted between 20 and 70 °C.
The scale of 1-7 on the handwheel gives the following target
temperatures (guideline):
Boiler circuit
Surface heating circuit
2-14 heating circuits
230V AC, 50 Hz,
provided connection cable: 3 x 0,5 mm² (max. 3 A),
please note the electrical protection!
Boiler flow:
3/4" female thread
Boiler return:
3/4" female thread
Surface heating flow:
3/4" Eurocone
Surface heating return:
3/4" Eurocone
Check valve
Main pump
Caution!
Observe the required capacity (pipe diameter).
Primary pressure required!
The flow rate in the boiler circuit is adjusted using the regulating
valve when the fixed-value regulator is fully opened (
)
Flushing ball valve
close when flushing
h = 385 mm / 405 mm with servomotor
Installation depth PVST:
125 mm