OPERATING INSTRUCTIONS AND DATA SHEET 

 

FOR SAFETY CONTROLLER REA3 

 

 

Safety switch REA3

,     

  

Date:  

17.08.2017

,    

 

             

Page 8 of 12 

Variotech GmbH, Gewerbeweg 5, 2230 Gänserndorf, Tel +43 2282 60310, http://variotech.com

 

Variotech GmbH, Gewerbeweg 5, 2230 Gänserndorf, Tel +43 2282 60310, http://variotech.com

 

Therefore, the monitoring of the reset button works in the following manner: 

  A blocked reset button is recognised immediately  

  The error is recorded  

  The “ON” LED goes out to indicate the error.  

  The safety switch does not deactivate and the lift travel can continue.  

  The safety switch deactivates on the next status change, with participation of the safety relay 

(activate/deactivate current, magnetic switch error, relay error, voltage drop or overvoltage 
detection, UCM error). 

 

Supply voltage monitoring: 

General information

:   

The supply voltage must be 24V. A tolerance range of 1.5V above (25.5V) and 

below (22.5V) is possible and does not have any limiting effect on function or reliability. 
In case of higher voltage, however, the relay heats up, which should generally be avoided. 
Most 24V mains adapters have the capability of adjusting the voltage in a range of +/- 10% with a 
regulator. The correct voltage should be checked with a multimeter prior to commissioning. 
The safety switch can be tested for correct operation of the activate and deactivate function by briefly 
pressing the “Test button”.

 

 

Voltage drop recognition: 

The safety switch tests the supply voltage on each activation and with each status change of the UCM 
safety relay. If the supply voltage is less than 18V, the switch can no longer start. 

 

Overvoltage recognition

The safety switch checks the supply voltage continuously. With a supply voltage of more than 27V, the 
safety switch deactivates automatically.  
If the voltage returns to the range of 24V, the safety switch re-activates. 

Short-circuit protection on the output contacts of the safety relay: 

Each of the outputs is protected with a fuse (2A flink). 
In case of a short-circuit with 230VAC mains voltage at both outputs of the safety switch, the fuse 
interrupts the current circuit.  
In the process, none of the parts of the safety switch are damaged.  
The safety switch operates again after replacement of the fuse. 

 

 

Содержание REA3

Страница 1: ...the protective device itself is not part of this safety switch and or description and must be provided on the lift system by the customer Devices that have been tested according to the regulations of...

Страница 2: ...escription 4 Layout and connections 4 Ambient conditions 5 Usage conditions 5 Installation fastening 5 Connections and terminal designation 5 Possible sources of error 7 Monitoring of the magnetic swi...

Страница 3: ...e symbol gives warning of impending dangers which could even cause serious bodily injuries and death ATTENTION This notice alludes to a source of danger and gives information about suitable precaution...

Страница 4: ...d in the intended manner if any damage can be traced back to a failure to observe the operating manual or if installation and operating personnel are not properly qualified or trained Intended use The...

Страница 5: ...itions The REA3 safety switch must only be used when the following requirements are fulfilled a The brake element of the protective device must be type tested b Suitable self monitoring of the ordinar...

Страница 6: ...ay contact This contact is always closed during operation and opens in case of UCM The relay contacts can be used for a maximum current of 2A and a maximum voltage of 24VDC or 250VAC It is also safegu...

Страница 7: ...wn due to the recorded error when the next safety circuit opens Therefore deactivation in case of a magnetic switch error does not take place during travel and only occurs after travel when the cabin...

Страница 8: ...elay heats up which should generally be avoided Most 24V mains adapters have the capability of adjusting the voltage in a range of 10 with a regulator The correct voltage should be checked with a mult...

Страница 9: ...ircuit is open the SK LED must not illuminate In case a check yields a negative result you have to assume there is capacitively coupled interference It must be eliminated by the customer The lift can...

Страница 10: ...by pressing the TEST button Redundant double execution encoders and sensors for safety functions are subject to testing for plausibility in the REA3 safety switch The functional test is carried out f...

Страница 11: ...ating duration of 20 years or 3 5M journeys because the stated product life cycle of the safety relay has then been reached Disposal and recycling Unusable or irreparable devices as well as those whic...

Страница 12: ...rail installation including magnetic switch REA3 V2MS REA3 safety switch Installed in a plastic housing for top hat rail installation without Magnetic switch REA3 V2XX Matching IP65 industrial housin...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Отзывы: