background image

VSD-1MC-20(40) 

Page 6 

Figure 3:  VSD-1MC-20(40) Faceplate 

 

 

1

Manual Speed Selector 

This selector is used to set the speed at which the variable output will run when 
the AUTO/MANUAL Switch is set to MANUAL. The variable output will shutoff is 
the Manual Speed Selector is turned completely counter clockwise (OFF).

 

 

2

AUTO/MANUAL Switch 

This switch is used to select if the variable output operates according to the 
Manual Speed Selector (MANUAL) or according to the input signal (AUTO). 

 

 

®

Varifan

MANUAL

AUTO

OFF

1

2

3

4

5

6

7

8

9

10

MANUAL

SPEED

[

2

[

1

Содержание VSD-1MC-20

Страница 1: ...VSD 1MC 20 40 MANUAL 0 10V 4 20mA Variable Speed Module with Manual Override Installation User s Guide Varifan MANUAL AUTO OFF 1 2 3 4 5 6 7 8 9 10 MANUAL SPEED...

Страница 2: ...The VSD 1MC is offered in 3 different models which are VSD 1MC VSD 1MC 20 or VSD 1MC 40 This manual covers the VSD 1MC 20 and VSD 1MC 40 The module operates on 115 230V and 50 60Hz The VSD 1MC 20 40...

Страница 3: ...The variable output requires the same phase and same voltage as the controller to operate 4 Connect the power source to the 2 black terminal block identified as LINE as shown in figure 1 5 Set the JP...

Страница 4: ...on or troubleshooting a Make sure that the Voltage Selector switch is set to the correct voltage before powering up the module a The variable output requires the same phase and same voltage as the con...

Страница 5: ...the input signal is at its minimum value 2 Dip Switches Input Range Switch and Shutoff 5 Switch Dip Switch 1 is used to select the Input Range ON 2 10 Volts 4 20 mA OFF 0 10 Volts 0 20 mA Dip Switch...

Страница 6: ...O MANUAL Switch is set to MANUAL The variable output will shutoff is the Manual Speed Selector is turned completely counter clockwise OFF 2 AUTO MANUAL Switch This switch is used to select if the vari...

Страница 7: ...of the differential Also refer to figure 2 for the location of the Shutoff 5 Switch Another switch also located on the electronic board will select if the input is a 0 10 Volts 0 20 mA or a 2 10 Volt...

Страница 8: ...E Switch 1 OFF 0 10 Volts or 0 20 mA Switch 2 OFF No shutoff at 5 Fan Speed 100 Minimum Speed 10 Volts or 20 mA Input 0 AUTO MODE Switch 1 ON 2 10 Volts or 4 20 mA Switch 2 OFF No shutoff at 5 Fan Spe...

Страница 9: ...2 ON Shutoff at 5 Fan Speed 100 Minimum Speed 10 Volts or 20 mA Input 0 0 7 Volts or 1 4 mA 0 5 Volts or 1 mA AUTO MODE Switch 1 ON 2 10 Volts or 4 20 mA Switch 2 ON Shutoff at 5 Fan Speed 100 Minimu...

Страница 10: ...VSD 1MC 20 40 Page 10 Figure 5 Logic Diagram Manual Mode MANUAL MODE Switch 1 and Switch 2 are not used in manual mode Fan Speed 100 Minimum Speed 10 100 Faceplate Potentiometer 0 0 7 7 0 5 5...

Страница 11: ...13 3 4 x 7 14 16 x 6 1 4 35 cm x 20 cm x 16 cm Warranty 2 years POWER SUPPLY Operational voltage range SW1 115V 92 to 125 VAC Operational voltage range SW1 230V 184 to 250 VAC Operational frequency ra...

Страница 12: ...f God flood fire hail or any other natural disaster Any unauthorized work modification or repair on this product automatically voids the warranty and disclaims the manufacturer from all responsibility...

Страница 13: ...VSD 1MC 20 40 VER 1 0 November 17 2011...

Отзывы: