                                                                          Installation 

 

ITC-Series

 Inverter 

Page 16 

 

 

 

 

 

 

 

 

 

 10/07/05 

GenStart  

It should be noted that the Generator Start Operation is designed to minimize the generator run time, so at the 
present  set  points  there  is  no  Absorption  stage  per  se.    Therefore,  the  batteries  must  be  periodically 
conditioned by leaving the generator on, or charging them with another system. 

The GenStart feature is designed for use in installations where a generator is used to provide AC input power 
for  battery  charging.  The  GenStart  feature  provides  a  contact  closure  to  signal  the  generator  to  start  when 
battery  voltage  falls  below  the  „Generator  Start  Volts‟  11.0  (22)  VDC  setpoint.  The  GenStart  contacts  open 
when  bulk  charging  current  fall  below  the  „Generator  End  Amps‟  20  Amp  DC  setpoint.  The  Bulk  charging 
current is checked every 4 minutes, therefore the minimum generator ON time is 4 minutes. The contacts are 
NEC Class 2, rated 2 amps at 24 VDC. 

It should be noted that the GenStart contacts are shown in Figure 1.4-9 Customer Terminations, and likewise a 
similar set of Normally Open Contacts are available to indicate a “Low Battery” or “Fan On” condition. 

 

Caution 

The  battery  charging  process  will  be  affected  if  12  (24)  VDC  loads  are  being  powered  during  battery 
charging.

 The increased charger output, required to power those loads, may keep the charger from reaching 

the „Generator End Amps‟ setpoint. 

Charger and APM Programming 

The chart below shows the control switch settings for programming the ITC Charger and APM settings. 

NOTE

:  It  should  be  noted  that  the  power  switch  on  the  front  of  the  unit  must  be  cycled  to  read  in  the  new 

Control Switch settings into memory.  The new values will not be recognized until this takes place. 

The first 4 (1-4) switches program in the Maximum Charger Current and the next 4 (5-8) program in the APM 
Current Limit.  

The next switch (switch 9) is for selecting either Wet or Gel type batteries. 

The next switch (switch 10) is reserved for future expansion. 

The next switch (switch 11) is reserved for future expansion. 

The next switch (switch 12) is reserved for selecting a Master/Slave remote with multiple Control/Display Units. 

Note:

  The figure below is also available on the Rear of the Control/Display Unit. 

Содержание ITC24-360

Страница 1: ...anual 10 7 05 ITC Series Inverter Charger System Models ITC12 2100 and ITC12 3200 ITC24 3600 and SP00172 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 614 771 2718 1 800 ACPOWER www vann...

Страница 2: ...INCORPORATED ITC Series ITC Series Inverter Page 2 10 07 05 Notes...

Страница 3: ...CUSTOMER WIRING IDENTIFICATION 17 AC INPUT OUTPUT WIRING 18 DC BATTERY WIRING 18 FRONT PANEL CONTROL DISPLAY OUTLET 18 SYSTEM ON OFF SWITCH 19 REMOTE SIGNAL CONTACTS 19 INSTALLATION 19 BASIC GUIDELIN...

Страница 4: ...7 Figure 1 4 6 Suspended Dimensions in Inches 11 F 8 Figure 1 4 7 Bottom Mount Dimensions in Inches 11 F 9 Figure 1 4 8 Control Display Unit Dimensions in Inches 11 F 10 Figure 1 4 9 Customer Terminat...

Страница 5: ...he cover of this manual System Features and Specifications General Description The ITC Series system consists of a DC to AC true sine wave inverter a battery charger an automatic AC transfer switch an...

Страница 6: ...shutdown of the Inverter at 10 5 21 0 VDC The SP00172 offers a Fan On contact instead of the Low Battery contact for turning on an external fan or blower when the ITC s fan is on Remote Power Switch...

Страница 7: ...4 amps 3 amps No Load Inverter OFF 0 30 amps 0 30 amps Full power 208 amps 350 amps 195 amps INVERTER EFFICIENCY Nom 200 watts 77 77 500 watts 88 84 700 watts 88 87 1000 watts 88 89 1500 watts 86 89 2...

Страница 8: ...IDE VIEW 11 12 15 16 OPTIONS CABLE ENTRY CHASSIS GROUND ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 DESCRIPTION BATTERY TERMINAL ACCESS REMOTE CABLE INPUT CONTROL DISPLAY PANEL INVERTER ON OFF SWITCH CHARGE...

Страница 9: ...when enabled but not on 2 Inverter On Off Button Enables Disables Inverter Function 3 Charger Indicator Light Solid when on flashes when enabled but not on 4 Charger On Off Button Enables Disables Cha...

Страница 10: ...allowing access to user AC and control terminals through a removable front cover ACCESS PANEL REMOVABLE FROM FRONT WHEN UNDER TABLE MOUNTED DOCKED DISPLAY CONTROL PANEL DC TERMINATIONS POWER ON OFF S...

Страница 11: ...10 7 05 18 10 7 8 19 1 4 13 5 8 16 3 4 8 1 8 7 5 16 8 3 4 ITC DIMENSIONS FOR SUSPENDED MOUNTING F 7 Figure 1 4 6 Suspended Dimensions in Inches 19 1 4 18 10 7 8 16 3 4 13 5 8 7 5 16 8 ITC DIMENSIONS F...

Страница 12: ...HOT NEU GND AC INPUT P15 HOT NEU GND AC OUTPUT P6 P5 REMOTE MASTER AND SLAVE CONNECTORS REMOTE SWITCH REMOTE LED COM N O N O LOW BATT FAN ON COM GENSTART P3 BATTERY TEMP SENSOR P7 F 10 Figure 1 4 9 C...

Страница 13: ...Battery Shutdown 10 5 21 0 VDC setpoint the inverter will shut OFF Auto restart will restart the inverter after battery voltage rises above the Low Battery Warning 11 0 22 0 VDC setpoint after 5 minu...

Страница 14: ...rge Stage and begins the Absorption Charge Stage The charger will not enter the Bulk Stage again until shore power is re applied or until the charger or the system is turned ON again VOLTAGE CURRENT T...

Страница 15: ...harging by preventing the charging stages from reaching their trigger points or may cause the battery to run down even though the charger is ON T 1 Figure 2 2 2 Battery Charger Factory Setpoints Guide...

Страница 16: ...r Terminations and likewise a similar set of Normally Open Contacts are available to indicate a Low Battery or Fan On condition Caution The battery charging process will be affected if 12 24 VDC loads...

Страница 17: ...6 7 8 9 10 11 12 DIPSWITCH FUNCTION SWPOSITION OFF ON OFF ON OFF ON SLAVE MASTER Note After a new switch setting is set the power switch must be cycled on the main unit for the new setting to take eff...

Страница 18: ...d P15 NOTE The AC output voltage and the required AC input voltage of the ITC is 120 VAC 60Hz DC Battery Wiring A DC wiring compartment is located behind the wiring panel on the right side of the unit...

Страница 19: ...l to the circuit INSTALLATION Unpacking the Inverter Inspect the shipping container and equipment for loose or damaged parts If any damage is found immediately notify the freight carrier Basic Guideli...

Страница 20: ...ons do not use the vehicle chassis as the DC negative conductor Use a cable the same size as the DC positive to go directly from the inverter to the battery negative 4 Route the AC and DC power wiring...

Страница 21: ...rough separate strain reliefs located at the right front of the unit WARNING Never make electrical connections live Make the connections to the inverter first and the battery last Make certain the ON...

Страница 22: ...on lug style that will accept up to 10 AWG copper wire Model ITC12 3200 The 26 7 amp at 120 volt 3200 watt inverter output capability requires 10 AWG wire minimum is used for the AC output The AC tran...

Страница 23: ...installation s grounding system or to earth ground Step 4 Verify Installation Verify all connections are tight and secure for maximum performance System Start up and Testing Step 1 Completely install...

Страница 24: ...power This power can be used to operate various AC driven appliances Typical DC power sources include batteries that store electrical energy power generated from a vehicle alternator or renewable ener...

Страница 25: ...ly equal to watts and are obtained by multiplying volts times current produced or used by a device To properly determine an inverter size in watts for your application decide which AC loads you plan t...

Страница 26: ...recharge cycling that is typical of most inverter installations These batteries are available in the maintenance free style where the electrolyte does not need to be checked or replenished and they a...

Страница 27: ...gine The 24 volts is usually provided by connecting two 12 volt batteries in series and sometimes by connecting four 6 volt batteries in series The ratings of the series connected battery bank remain...

Страница 28: ...rting the engine and operating the inverter This is a common practice in a service vehicle where the engine runs all the time and allows the alternator to provide continuous charging for the battery I...

Страница 29: ...ing for lead acid batteries and 50 of the battery s C for gel cell batteries The C rate is numerically equal to the amp hour capacity for the battery For example a 280 amp hour battery has a C rate of...

Страница 30: ...corrosion free 2 Check air ventilation openings for dust and other obstructions 3 Examine receptacle indicators and switches for cracks and breaks in insulation material Trouble Shooting The Unit doe...

Страница 31: ...Page 31 Owner s Manual 10 7 05 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 1 800 AC POWER 1 800 227 6937 Tel 614 771 2718 Fax 614 771 4904 www vanner com e mail pwrsales vanner com Ma...

Отзывы: