Vanguard VSGF28NTD Скачать руководство пользователя страница 6

111149-01B

For more information, visit www.desatech.com

For more information, visit www.desatech.com

6

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space.
When ventilating to an adjoining unconfined space, you must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 3). You can also remove door into
adjoining room (see option 3, Figure 3). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion
and Ventilation
 for required size of ventilation grills or ducts.

Figure 4 - Ventilation Air from Outdoors

Figure 3 - Ventilation Air from Inside Building

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

;;;;;;

;;;;;;

;;;;;;

;;;;;;

;;;;;;

;;;;;;

;;;;;;

QQQQQQ

QQQQQQ

QQQQQQ

QQQQQQ

QQQQQQ

QQQQQQ

QQQQQQ

¢¢¢¢¢¢

¢¢¢¢¢¢

¢¢¢¢¢¢

¢¢¢¢¢¢

¢¢¢¢¢¢

¢¢¢¢¢¢

¢¢¢¢¢¢

;;;;

;;;;

;;;;

;;;;

QQQQ

QQQQ

QQQQ

QQQQ

¢¢¢¢

¢¢¢¢

¢¢¢¢

¢¢¢¢

;;

;;

QQ

QQ

¢¢

¢¢

;;;;;

;;;;;

QQQQQ

QQQQQ

¢¢¢¢¢

¢¢¢¢¢

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

AIR FOR COMBUSTION AND
VENTILATION

Continued

 WARNING: If the area in which the heater may be

operated is smaller than that defined as an uncon-
fined space or if the building is of unusually tight
construction, provide adequate combustion and ven-
tilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec-
tion 5.3 or applicable local codes.

4.

Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:

A.

Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See Ventilation Air From
Inside Building
.

B.

Vent room directly to the outdoors. See Ventilation Air From Outdoors.

C.

Install a lower Btu/Hr heater, if lower Btu/Hr size makes room
unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh
air ventilation.

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow for Heater Location (Cont.)
Ventilation Air

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for inlet or outlet air into

attic if attic has a thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.

f i r e - p a r t s . c o m

Содержание VSGF28NTD

Страница 1: ...i fied installer service agency or the gas supplier WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manualforcorrectinstall...

Страница 2: ...s are odorless An odor making agent is added to the gas The odor helps you detect a gas leak However the odor added to the gas can fade Gas may be present even though no odor exists Make certain you r...

Страница 3: ...keeps shutting off see Trouble shooting pages 18 through 20 11 Do not run fireplace where flammable liquids or vapors are used or stored under dusty conditions 12 Do not use this fireplace to cook fo...

Страница 4: ...oss out a vent or up a chimney Heat is generated by both realistic flames and glowing embers When used without the blower the fireplace requires no electricity making it ideal for emergency backup hea...

Страница 5: ...for combustion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is defined as construc tion where a walls and cei...

Страница 6: ...l amount of Btu Hr used __________________ Btu Hr maximum the space can support __________________ Btu Hr actual amount of Btu Hr used Example 51 200 Btu Hr maximum the space can support 73 000 Btu Hr...

Страница 7: ...a prop erly grounded three prong receptacle Do not cut or remove the grounding prong from this plug NOTICE This heater is intended for use as supple mental heat Use this heater along with your primar...

Страница 8: ...r cabinet mantel with hearth base accessories against a wall in your home see Accessories page 26 Follow the instructions below to install the fireplace in this manner Note The instructions below show...

Страница 9: ...rews Countersink screw heads and putty over 5 Route gas line through access hole in hearth base 6 Center cabinet mantel on hearth base see Figure 10 Make sure mantel is flush against wall 7 Break off...

Страница 10: ...4 1 Frame in rough opening Use dimensions shown in Figure 13 for the rough opening If installing in a corner use dimensions shown in Figure 14 page 10 for the rough opening The height is 33 which is...

Страница 11: ...ng gas pressure You must reduce incoming gas pressure to between 11 and 14 inches of water If you do not reduce incoming gas pressure heater regulator damage could occur Install external regulator wit...

Страница 12: ...ift fireplace screen up and pull out to remove 2 Remove screws that attach log base assembly to fireplace see Figure 19 Carefully lift up log base assembly and remove from fireplace see Figure 19 Note...

Страница 13: ...sure control knob of fireplace is in the OFF position 4 Check all joints from equipment shutoff valve to gas control valve see Figure 22 or 23 Apply noncorrosive leak detec tion fluid to all joints Bu...

Страница 14: ...mediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water WARNING If you do not follow these i...

Страница 15: ...l Lighting Procedure column 2 7 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob Note If pilot goes out repeat steps 3 through 7 This fire place h...

Страница 16: ...yellow tipping at top of blue flame WARNING If front burner flame pattern shows yellow tipping your fireplace could produce increased levels of carbon monoxide Follow instructions at bot tom of this...

Страница 17: ...unit including the pilot Allow the unit to cool for at least thirty minutes 2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt see Figure 34 3 Blow air through th...

Страница 18: ...r cable 5 Replace piezo ignitor 6 Replace pilot assembly 7 Replace pilot assembly 1 Turn on gas supply or open equipment shutoff valve 2 Turn control knob to PILOT position 3 Press in control knob whi...

Страница 19: ...r 1 Problem will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burners until air is removed from line Have gas line checked by lo cal na...

Страница 20: ...ly clogged 1 Gas leak See Warning statement above 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement above 1 Not enough combustion ventilation...

Страница 21: ...en calling DESA Heating Products have ready model number of your fireplace the replacement part number SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed igni...

Страница 22: ...on visit www desatech com 22 ILLUSTRATED PARTS BREAKDOWN LOG BASE ASSEMBLY MODELS VSGF28NTD AND VSGF28PTD 3 1 2 17 5 7 8 7 7 18 6 12 26 11 9 15 10 25 13 4 5 5 5 5 21 24 22 18 23 12 19 14 27 20 28 16 I...

Страница 23: ...109824 02 109824 02 Rear Burner Assembly 1 11 Base Assembly 1 12 098271 06 098271 06 Ignitor Cable 1 13 Firebox Bottom 1 14 098867 09 098867 10 Gas Regulator 1 15 101004 04 101004 15 Front Burner Inje...

Страница 24: ...n visit www desatech com 24 ILLUSTRATED PARTS BREAKDOWN FIREPLACE MODELS VSGF28NTD VSGF28PTD 1 2 3 4 16 16 6 12 18 10 10 7 13 16 26 24 16 23 25 20 24 24 21 16 16 7 17 14 5 16 16 15 8 9 19 22 11 11 11...

Страница 25: ...26 Hex Screw 10 57 17 098304 03 Phillips Pan Head Screw 8 4 18 101727 03 Screen Assembly 1 19 101398 03 Wire Harness 1 20 103650 01 Control Knob 1 21 103581 02 Blower Assembly 1 22 099123 01 Wire Clip...

Страница 26: ...ries Walnut Finished G3009U Series Unfinished G3010F Series Oak Finished The corner hearth base is designed for use with the corner mantels to create a handsome riser for the fireplace Dimensions WxHx...

Страница 27: ...ge Completed Graduate School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35 000 to 49 999 50...

Страница 28: ...49 01B For more information visit www desatech com For more information visit www desatech com 28 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 Postage Required TAPE TAPE fire parts...

Страница 29: ...________________________________________________ _______________________________________________________________________________________________ _______________________________________________________...

Страница 30: ...ravel diagnostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE...

Отзывы: