Vanguard VP5D Скачать руководство пользователя страница 5

OWNER’S MANUAL

5

104273

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, Section 5.3, or applicable local codes.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: 

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_____________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

__________________ Btu/Hr

Gas water heater*

__________________ Btu/Hr

Gas furnace

__________________ Btu/Hr

Vented gas heater

__________________ Btu/Hr

Gas fireplace logs

__________________ Btu/Hr

Other gas appliances*

+ __________________ Btu/Hr

Total

= __________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

55,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Example:

Gas water heater

45,000

Btu/Hr

Vent-free heater   +

10,000

Btu/Hr

Total                    =

55,000

Btu/Hr

Continued

Содержание VP5D

Страница 1: ...y a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxy gen from the room in which it is installed Provisionsforadequate combustion and...

Страница 2: ...etween locked positions Poor combustion may result 6 This heater needs fresh outside air ven tilation to run properly This heater has an oxygen depletion sensor ODS pi lot light safety system The ODS...

Страница 3: ...with care Follow all localcodes Intheabsenceoflocalcodes use the latest edition of National Fuel Gas Code ANS Z223 1 also known as NFPA 54 Available from American National Standards Institute Inc 143...

Страница 4: ...s to breathe Fresh air must enter your home All fuel burning appliances need fresh air for proper com bustion and ventilation Exhaustfans fireplaces clothesdryers and fuel burning appliances draw air...

Страница 5: ...ter __________________Btu Hr Gas water heater __________________Btu Hr Gas furnace __________________Btu Hr Vented gas heater __________________Btu Hr Gas fireplace logs __________________Btu Hr Other...

Страница 6: ...cts WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both spaces Figure 2 Ventilation Air from In...

Страница 7: ...re 4 Ifyoucan providegreaterclear ancesfromfloor ceiling andjoin ing wall WARNING Never install the heater in a bathroom VP10A only in a recreational vehicle where curtains furniture clothing or other...

Страница 8: ...ued Figure 8 Tightening Anchors Thin or Thick Wall thick wall shown Solid Wall 1 16 Space Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place larg...

Страница 9: ...menttrapinsupplylineasshown in Figure 13 Locate sediment trap where it is within reach for cleaning Locate sedi ment trap where trapped matter is not likely to freeze A sediment trap traps moisture an...

Страница 10: ...ust be lighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is he...

Страница 11: ...0 seconds after lighting pilot After 10 seconds release control knob Note If pilot goes out repeat steps 3 through 7 OFF PILOT IGNITOR LOW HIGH TO SELECT HEATING LEVEL 1 Slightly press in control knob...

Страница 12: ...ean Inspect these areas of heater before each use Have heaterinspectedyearlybyaquali fied service person Heater may need more frequent cleaning due to excessive lint from carpeting bedding material pe...

Страница 13: ...itor cable if pinched by any metal or tubing Keep ignitor cable dry 5 Tighten nut holding piezo ignitor to heater cabinet Nut is located inside heater cabinet at top 6 Replace ignitor cable 7 Replace...

Страница 14: ...Contact local propane LP gas company 3 Replace burner 4 Replace gas regulator 1 Replace burner 2 Contact local propane LP gas company 3 Turn control knob until it locks at de sired setting 1 Problem w...

Страница 15: ...ing Gas Connections page 10 2 Replace control valve 1 Take apart gas tubing and remove for eign matter 2 Locate and correct all leaks see Check ing Gas Connections page 10 1 Refer to Air for Combustio...

Страница 16: ...ex 8 x 1 4 9 7 099059 03 ODS Pilot Assembly 1 7 1 098514 01 Thermocouple 1 7 2 098594 01 Ignitor Electrode 1 8 099884 01 Burner Assembly 1 9 099056 01 Injector 1 10 099390 01 Tubing Valve to burner 1...

Страница 17: ...ulator to valve 1 PARTS LIST This list contains replaceable parts used in your heater When ordering parts follow the instructions listed under Replacement Parts on page 18 of this manual ODS PILOT ILL...

Страница 18: ...TechnicalServiceDe partment at 1 800 323 5190 for referral in formation When contacting your dealer or DESA In ternational have ready your name your address model and serial numbers of your heater how...

Страница 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 20: ...y does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects...

Отзывы: