VENT-FREE NATURAL GAS HEATER

®

Confined and Unconfined Space

The National Fuel Gas Code ANS Z223.1
defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000
Btu per hour (4.8 m3 per kw) of the aggre-
gate input rating of all appliances installed
in that space and an unconfined space as a
space whose volume is not less than 50
cubic feet per 1,000 Btu per hour (4.8 m3 per
kw) of the aggregate input rating of all
appliances installed in that space. Rooms
communicating directly with the space in
which the appliances are installed*, through
openings not furnished with doors, are con-
sidered a part of the unconfined space.

This heater shall not be installed in a con-
fined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

AIR FOR
COMBUSTION AND
VENTILATION

Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.

While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

PROVIDING ADEQUATE
VENTILATION

The following are excerpts from National
Fuel Gas Code. NFPA 54/ANS Z223.1, Sec-
tion 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three
following ventilation classifications:

1.

Unusually Tight Construction

2.

Unconfined Space

3.

 Confined Space

The information on pages 5 and 6 will help
you classify your space and provide ad-
equate ventilation.

Unusually Tight Construction

The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.

Unusually tight construction is de-
fined as construction where:

a.

walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6 x 10

-11

 kg

per pa-sec-m

2

) or less with open-

ings gasketed or sealed 

and

b. weather stripping has been

added on openable windows and
doors 

and

c.

caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See 

Ventilation Air

From Outdoors, page 6.

If your home does not meet all of the
three criteria above, proceed to 

De-

termining Fresh-Air Flow For Heater
Location, page 5.

 WARNING: This heater shall

not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ven-
tilation air. Read the following in-
structions to insure proper fresh
air for this and other fuel-burning
appliances in your home.

Содержание VN6D

Страница 1: ...qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater Itusesair oxygen fromthe roominwhichitisinstalled Provisions for adequate combustionandventilation...

Страница 2: ...utside air ven tilation to run properly This heater has an oxygen depletion sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion...

Страница 3: ...ing ap plied to heater for shipment 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bought heater PRODUCT FEATURES SAFETY PILOT This heater has a pilot wit...

Страница 4: ...ces This will insure proper venting of vented fuel burning appliances PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code NFPA 54 ANS Z223 1 Sec tion5 3 AirforCombust...

Страница 5: ...urning appliances in the space Vent free heater ________________ Btu Hr Gas water heater ________________ Btu Hr Gas furnace ________________ Btu Hr Vented gas heater ________________ Btu Hr Gas firep...

Страница 6: ...tticwillactivatethepowervent Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 12 12 Ventilation Grills into Adjoining Room Option 1 Figure 2 Ventilation Air...

Страница 7: ...From Floor FLOOR JOINING WALL INSTALLATION WARNING A qualified ser vice person must install heater Follow all local codes CHECK GAS TYPE Use only natural gas If your gas supply is not natural do not...

Страница 8: ...er tighten Note Do not replace front panel at this time Replace front panel after making gas connections and checking for leaks see pages 9 and 10 Figure 7 Popping Open Anchor Wings For Thin Walls Thi...

Страница 9: ...mall undue loss of pressure will occur Installationmustincludeaequipmentshutoff valve ground joint union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be up s...

Страница 10: ...ther using compressed air or opening main gas valve located on or near gas meter 3 Check all joints from gas meter to equip ment shutoff valve see Figure 14 Ap ply mixture of liquid soap and water to...

Страница 11: ...this heater for the first time after hook ing up to gas supply If so the con trol knob may need to be pressed in for 30 seconds This will allow air to bleed from the gas system If control knob does no...

Страница 12: ...Figure 19 turn heater off see To Turn Off Gas to Appliance page 11 see Troubleshooting pages 13 through 15 INSPECTING BURNER Figure 19 Incorrect Pilot Flame Pattern Figure 18 Correct Pilot Flame Patt...

Страница 13: ...Turn on gas supply or open equipment shutoff valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILOT position 4 Continue holding down control knob Repeat igniting operation...

Страница 14: ...local natural gas company 3 Replace burner 4 Replace gas regulator 1 Replace burner 2 Contact local natural gas company 3 Turn control knob until it locks at de sired setting 1 Problem will stop after...

Страница 15: ...ionnoticedonwindows POSSIBLE CAUSE 1 Heater burning vapors from paint hair spray glues etc See IMPORTANT statement above 2 Gas leak See Warning statement above 1 Not enough fresh air is available 2 Lo...

Страница 16: ...7 2 098594 01 Ignitor Electrode 1 8 099884 01 Burner Assembly 1 9 099056 04 Injector 1 10 099390 01 Tubing Valve to burner 1 11 099387 05 Pilot Tubing Valve to pilot 1 12 099391 02 Tubing Regulator to...

Страница 17: ...7 2 098594 01 Ignitor Electrode 1 8 099884 02 Burner Assembly 1 9 099056 06 Injector 2 10 099390 02 Tubing Valve to plaque A 1 11 099387 05 Pilot Tubing Valve to pilot 1 12 099392 01 Tubing Valve to p...

Страница 18: ...eplaced under warranty PARTS UNDER WARRANTY Contact authorized dealer from whom you purchased this product If they cannot sup ply original replacement part s call DESA International s Technical Servic...

Страница 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 20: ...o repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY...

Отзывы: