6

2. Mark two mounting screw locations on wall (see Figure 3).

INSTALLING HEATER TO WALL

Marking Screw Locations

1. Determine where you will locate heater.

Figure 3 - Mounting Screw Locations

Mounting

Screw

Locations

10 7/8"

Minimum To

Maintain 8"

Clearance
From Wall

7 3/4"

20 1/4"

Minimum To

Maintain 3"

Clearance

From Floor

FLOOR

JOINING WALL

!

WARNING ICON

G 001

WARNING

Maintain minimum clearances shown in Figure 3. If you can,
provide greater clearances from floor and joining wall.

36"

3"

FLOOR

CEILING

Minimum

Minimum To Top Surface 
Of Carpeting, Tile Or Other
Combustible Material

8"

Minimum
From
Sides Of
Heater

Right
Side

Left
Side

Figure 2 - Mounting Clearances As Viewed From Front of Heater

Содержание VN12

Страница 1: ...ny electrical switch do not use any phone in your building Immediatelycallyourgassupplierfrom a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the f...

Страница 2: ...ry or death from burns fire explosion and carbon monoxide poisoning WARNING ICON G 001 DANGER Carbon monoxide poisoning may lead to death Carbon Monoxide Poisoning Early signs of carbon monoxide poiso...

Страница 3: ...inches When used without fresh outside air heater may give off carbon monoxide gas 6 Never run heater in small closed room Open door into next room to help ventilate 7 Keep all air openings in front a...

Страница 4: ...2269 Heater Cabinet Grill Guard Burners Front Panel UNPACKING 1 Remove heater from carton 2 Remove all protective packaging applied to heater for shipment 3 Check heater for any shipping damage If hea...

Страница 5: ...heater is designed to be mounted on a wall WARNING ICON G 001 WARNING Maintain the minimum clearances shown in Figure 2 page 6 If you can provide greater clearances from floor ceiling and joining wall...

Страница 6: ...arance From Wall 7 3 4 20 1 4 Minimum To Maintain 3 Clearance From Floor FLOOR JOINING WALL WARNING ICON G 001 WARNING Maintain minimum clearances shown in Figure 3 If you can provide greater clearanc...

Страница 7: ...y is between screwhead and wall Attaching to wall anchor method Follow instructions below to attach mounting screws to hollow walls wall areas between studs or solid walls concrete or masonry 1 Drill...

Страница 8: ...f Heater Installing Bottom Mounting Screw 1 Locate bottom mounting hole This hole is near bottom on back panel of heater see Figure 9 2 Mark screw location on wall 3 Remove heater from wall 4 If insta...

Страница 9: ...where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong he...

Страница 10: ...to 10 5 W C Pressure PRESSURE TESTING GAS SUPPLY PIPING SYSTEM Test Pressures In Excess Of 1 2 PSIG 1 Disconnect heater and its individual manual shutoff valve from gas supply piping system Pressures...

Страница 11: ...at once PRESSURE TESTING HEATER GAS CONNECTIONS 1 Open manual shutoff valve see Figure 11 2 Open main gas valve located on or near gas meter 3 Make sure control knob of heater is in the OFF position 4...

Страница 12: ...the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician or gas supplier Force or attempted repair may result in a f...

Страница 13: ...knob pressed in and turn it counterclockwise C clockwise to the PILOT IGN position This will light pilot Note You will hear a loud click when the control knob reaches the PILOT IGN position If pilot d...

Страница 14: ...ure 15 Burner Patterns LOW OFF PILOT IGN HIGH OFF PILOT IGN OFF Control VN12 Knob Burners ON OFF PILOT IGN OFF Control VN6A Knob Burner WARNING ICON G 001 WARNING When running heater set control knob...

Страница 15: ...front panel TO TURN OFF GAS TO APPLIANCE Continued GRH OV 009 GOOD PILOT GRH OV 010 BAD PILOT Check pilot flame pattern and burner flame pattern often PILOT FLAME PATTERN Figure 16 shows a correct pil...

Страница 16: ...ontrol areas burner and circulating air passageways of heater clean Inspect these areas of heater before each use Have heater inspected yearly by a qualified service person Heater may need more freque...

Страница 17: ...lve 1 Turn on gas supply or open manual shutoff valve 2 Press in control knob while turning to PILOT IGN position 3 Continue holding down control knob Repeat ig niting operation until air is removed 4...

Страница 18: ...out This problem could be caused by one or both of the following A Low gas pressure B Dirty or partially clogged ODS pilot 6 Thermocouple dam aged 7 Control valve damaged Burner s does not lightafterO...

Страница 19: ...on 1 Ventilate room Stop us ing odor causing prod ucts while heater is run ning 2 Locate and correct all leaks see CHECKING GAS CONNECTIONS page 10 1 Open window and or door for ventilation 2 Contact...

Страница 20: ...CONNECTIONS page 10 POSSIBLE CAUSE 1 Gas leak See Warn ing statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warn ing statement at to...

Страница 21: ...ve ready your name your address model number of your heater how heater was malfunctioning type of gas used propane or natural gas purchase date Usually we will ask you to return the defective part to...

Страница 22: ...NUMBER DESCRIPTION QTY 13 099384 01 Control Valve 1 14 099057 01 Pressure Tap Fitting 1 15 098276 01 1 8 Pipe Plug 1 16 099468 03 Cabinet Assembly 1 17 099415 01 Gas Regulator 1 18 098303 02 Screw 6...

Страница 23: ...MBER DESCRIPTION QTY 13 099391 02 Tubing Regulator to valve 1 14 099385 01 Control Valve 1 15 099057 01 Pressure Tap Fitting 1 16 098276 01 1 8 Pipe Plug 1 17 099468 02 Cabinet Assembly 1 18 099415 01...

Страница 24: ...with warranty repairs are not reimbursable under this warranty and are the responsibility of the owner To the full extent allowed by the law of the jurisdiction that governs the sale of the product t...

Отзывы: