Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.

While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

PROVIDING ADEQUATE
VENTILATION

The following are excerpts from National
Fuel Gas Code, NFPA 54/ANS Z223.1, Sec-
tion 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three
following ventilation classifications:

1.

Unusually Tight Construction

2.

Unconfined Space

3.

Confined Space

The information on pages 5 through 7 will
help you classify your space and provide
adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.

Unusually tight construction is de-
fined as construction where:

a.

walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6x10

-11

 kg

per pa-sec-m

2

) or less with open-

ings gasketed or sealed 

and

b. weather stripping has been

added on openable windows and
doors 

and

c.

caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See 

Ventilation Air

From Outdoors, page 7.

If your home does not meet all of the
three criteria above, proceed to 

Deter-

mining Fresh-Air Flow For Heater Lo-
cation, page 6.

Confined and Unconfined Space

The National Fuel Gas Code, ANS Z223.1
defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000
Btu per hour (4.8 m

3

 per kw) of the aggre-

gate input rating of all appliances installed
in that space and an unconfined space as a
space whose volume is not less than 50
cubic feet per 1,000 Btu per hour (4.8 m

3

 per

kw) of the aggregate input rating of all
appliances installed in that space. Rooms
communicating directly with the space in
which the appliances are installed*, through
openings not furnished with doors, are con-
sidered a part of the unconfined space.

This heater shall not be installed in a con-
fined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

AIR FOR
COMBUSTION AND
VENTILATION

 WARNING: This heater shall

not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ven-
tilation air. Read the following in-
structions to insure proper fresh
air for this and other fuel-burning
appliances in your home.

Continued

Содержание VMH3000TNSA

Страница 1: ... electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed byaqualifiedinstaller serviceagency orthe gas supplier WARNING Improper installa tion adjustment alteration service or maintenance can caus...

Страница 2: ...ear the appliance Never place any objects on the heater Surface of heater becomes very hot when running heater Keep children and adults away from hot surface to avoid burns or clothing ignition Heater will re main hot for a time after shut down Allow surface to cool be fore touching Carefully supervise young chil dren when they are in same room with heater Make sure screen is in place be fore runn...

Страница 3: ...dko em kgo dki rlnf gpd fAS DF KIG LF JI als kdi dko em kgo dki rlnf gpd f AS DF KIG LF JI als kdi dko em kgo dki rlnf gpd fAS DF KIG LF JI als kdi dko em kgo dki rlnf gpd f AS DF KIG LF JI als kd idk oe mk go dk irln fgp d f AS DF KIG LF JI als kd idk oe mk go dk irln fgp d f AS DF KIG LF JI als kd idk oe mk go dk irln fgp d f AS DF KIG LF JI als kd idk oe mk go dk irln fgp d f AS DF KIG LF JI al...

Страница 4: ... on front of heater cabinet Attach on top and sides with four brass screws included in hard ware package see Figure 6 9 Reattach front panel to heater if you are going to mount the heater to the base Do not reattach front panel at this time if you are going to mount heater to wall Figure 5 Assembling Brass Trim Figure 6 Attaching Brass Trim to Heater Attaching Brass Front Trim to Front Panel 1 Loc...

Страница 5: ...per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to areas such as joints around window and door frames be tween sole plates and floors be tween wall ceiling joints be tween wall panels at penetra tions for plumbing electrical and gas lines and at other openings If your home meets all ...

Страница 6: ...e direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the space can support _________________ Btu Hr actual amount of Btu Hr used Example 51 200 Btu Hr maximum the space can support 60 000 Btu Hr actual amount of Btu Hr used T...

Страница 7: ...Inside Building Outlet Air Ventilated Attic Outlet Air Inlet Air Inlet Air Ventilated Crawl Space To Crawl Space To Attic Figure 8 Ventilation Air from Outdoors AIR FOR COMBUSTION AND VENTILATION Continued WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both spaces Ventilation Air From Outdoors ...

Страница 8: ...ave the items listed below piping check local codes sealant resistant to propane LP gas equipment shutoff valve ground joint union test gauge connection sediment trap tee joint pipe wrench An CSA design certified equipment shutoff valve with 1 8 NPT tap is an ac ceptable alternative to test gauge connec tion Purchase the optional CSA design certifiedequipmentshutoffvalvefromyour dealer See Accesso...

Страница 9: ...nters Attach mounting bracket to wall in one of two ways 1 Attaching to wall stud 2 Attaching to wall anchor Attaching To Wall Stud This method pro vides the strongest hold Insert mounting screws through mounting bracket and into wall studs Attaching To Wall Anchor This method allows you to attach mounting bracket to hollow walls wall areas between studs or to solid walls concrete or masonry Decid...

Страница 10: ...ed hole 8 Tighten both screws until heater is firmly secured to wall Do not over tighten Note Do not replace front panel at this time Replace front panel after making gas connections and checking for leaks see pages 12 and 13 Figure 15 Installing Bottom Mounting Screws Attaching To Wall Anchor Method For attaching mounting bracket to hollow walls wall areas between studs or solid walls concrete or...

Страница 11: ...all cut with a sharp knife at marked locations before drilling If securing to a wood floor drill a 3 4 deep hole using a 1 8 diameter drill bit Do not use anchors in wood floors If securing to a concrete floor drill a 1 3 8 deep hole using a 1 4 diameter concrete drill bit Completely insert an chors into each hole 3 Mount heater to hearth base following steps under Mounting Heater to Op tional Hea...

Страница 12: ...used in certain areas Check your local codes Use pipe of 1 2 or greater diameter to allow proper gas volume to heater If pipe is too small undue loss of pressure will occur Installation must include an equipment shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 18 IMPORTANT Installanequipmentshutoff valve ...

Страница 13: ...kPa 1 Close equipment shutoff valve see Fig ure 19 2 Pressurize supply piping system by either using compressed air or open ing main gas valve located on or near gas meter 3 Check all joints from gas meter to equipment shutoff valve see Figure 20 Apply mixture of liquid soap and water to gas joints Bubbles forming show a leak 4 Correct all leaks at once Pressure Testing Heater Gas Connections 1 Op...

Страница 14: ...er to Troubleshooting pages 16 through 18 Also contact a qualified service person or gas supplier for repairs Untilrepairsaremade lightpilotwith match To light pilot with match see Manual Lighting Procedure page 15 FOR YOUR SAFETY READ BEFORE LIGHTING Shutting Off Heater 1 Turn control knob clockwise to the OFF position Note Knobmustbedepressedslightly 2 Turn off all electric power to the ap plian...

Страница 15: ...g Instruc tions page 14 5 Replace front panel Figure 23 Correct Pilot Flame Pattern INSPECTING BURNER Figure 24 Incorrect Pilot Flame Pattern Check pilot flame pattern and burner flame pattern often PILOT FLAME PATTERN Figure23showsacorrectpilotflamepattern Figure 24 shows an incorrect pilot flame pattern Theincorrectpilotflameisnottouch ing the thermocouple This will cause the thermocouple to coo...

Страница 16: ...e 8 Replace control valve POSSIBLE CAUSE 1 Ignitor electrode positioned wrong 2 Ignitor electrode broken 3 Ignitor electrode not connected to igni tor cable 4 Ignitor cable pinched or wet 5 Piezo ignitor nut is loose 6 Broken ignitor cable 7 Bad piezo ignitor 1 Gas supply turned off or equipment shutoff valve closed 2 Control knob not in PILOT position 3 Control knob not pressed in while in PILOT ...

Страница 17: ...19 or replace burner orifice 1 Turn heater off when using furniture polish wax carpet cleaners or similar products TROUBLESHOOTING Continued OBSERVED PROBLEM Burner does not light after ODS pilot is lit Delayed ignition of burner Burner backfiring during combustion Yellow flame during burner combustion Slight smoke or odor during initial operation Heater produces a whistling noise when burner is l...

Страница 18: ... during combustion POSSIBLE CAUSE 1 Metal expanding while heating or con tracting while cooling 1 Heater burning vapors from paint hair spray glues etc see IMPORTANT statement above 2 Gas leak SeeWarning statement at top of page 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak SeeWarning statement at top of page 2 Control valve defective 1 Foreign...

Страница 19: ...ntact your local natural gas supplier SERVICE HINTS CLEANING BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE The primary air inlet holes allow the proper amount of air to mix with the gas This provides a clean burning flame Keep these holes clear of dust dirt lint and pet hair Clean these air inlet holes prior to each heating season Blocked air holes will cre ate soot We recommend that you clean t...

Страница 20: ...1 NATURAL GAS RESIDENTIAL HEATERS For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN VMH3000TNSA 1 2 9 10 10 12 13 14 15 17 19 20 23 24 25 6 26 6 7 1 1 3 1 28 5 16 18 4 22 1 1 1 21 11 8 27 ...

Страница 21: ...itor Cable 1 11 098249 01 Nut M5 2 12 107485 01 ODS Pilot Assembly 1 13 103447 01 Burner 1 14 099387 03 3 16 Pilot Tubing 1 15 103845 12 Injector 1 16 NJF 8C Nut Hex 1 17 099415 11 Pressure Regulator 1 18 103408 01 Burner Bracket 2 19 105293 01 3 8 Outlet Burner Tubing 1 20 105292 01 3 8 Inlet Tubing 1 21 107218 01 Deflector Baffle 1 22 107060 01 Log Strap 2 23 105291 01 Thermostat Gas Valve 1 24 ...

Страница 22: ...vice Department at 1 800 323 5190 You can also visit DESA International s technical service web site at www desatech com SPECIFICATIONS Btu Variable 15 000 30 000 Type Gas Natural Only Ignition Piezo Pressure Regulator Setting 3 W C Inlet Gas Pressure in of water Maximum 10 5 Minimum 5 Dimensions Inches H x W x D Heater 23 75 x 25 9 x 8 5 Carton 25 8 x 28 7 x 10 1 Weight pounds Heater 29 Shipping ...

Страница 23: ...llation instructions included EQUIPMENT SHUTOFF VALVE GA5010 Equipmentshutoffvalvewith1 8 NPTtap HEARTH BASE GHB802 Series For locating heater on the floor Includes brass trim Complete installation instruc tions included ACCESSORIES Purchasetheseheateraccessoriesfromyour local dealer If they can not supply these accessoriescallDESAInternational sSales Department at 1 800 458 2472 for infor mation ...

Страница 24: ...with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportationandanyandallsuchothercostsrelatedtorepairingadefect...

Отзывы: