Vanguard PENINSULA VPN36 Скачать руководство пользователя страница 10

10

55505

Figure 23

VRTL-10D

VSC-10

FLASHING

VFS-10DM

VFS-10DM

V30FS-10DM

V30E-10DM

MINIMUM

HEIGHT

15 FT.

MAXIMUM

HEIGHT

CHASE

TERMINATION

50 FT.

VRTL-10D

VETL-10D

MINIMUM CHIMNEY HEIGHT

The minimum chimney height (measured from bottom of firebox to
flue gas outlet-end of pipe) is 15 feet for a straight run, 16 feet min.
for a run with 1 elbow set (a set consists of one starter elbow and one
return elbow).

Uncommon circumstances such as neighboring hills, tall trees, or
strong wind areas can cause downdrafts in the chimney system. In
such cases going beyond the minimum recommended height would
be preferable to provide a better draw.

MAXIMUM CHIMNEY HEIGHT

The maximum height approved for any chimney run with this
firebox system is 50 feet measured from bottom of firebox to flue
outlet-end of pipe.

CHIMNEY MAINTENANCE

Have your chimney system cleaned and inspected regularly to
ensure safe and efficient operation. Refer to your Owner's
Manual for further guidelines on maintenance and operation.

Using Figure 24 and the chart below, determine the opening that will
be required for the pitch of your particular roof.

Figure 24

19" MIN.

(482.6mm)

2" MIN.

(50.8mm)

2" MIN.

(50.8mm)

2" MIN.

(50.8mm)

30" MIN.

(762mm)

OPENING

"A"

ROOF OPENING CHART

PITCH

OPENING "A" USE FLASHING NO.

FLAT

19

V6F10

6/12

23 

1

/

4

V6F10

(26.6 DEG. SLOPE)

12/12

30 

3

/

4

V12F10

(45 DEG. SLOPE)

Before cutting hole, temporarily remove shingles around area to be
opened. After preparing the opening on the roof, continue to add
sections of pipe until it extends a minimum of 30 inches above
highest point of roof cutout (see Figure 24).

With the termination the minimum height should add up 3 feet (see
10-Foot Rule and Figure 22).

Содержание PENINSULA VPN36

Страница 1: ...should be located out of traffic and away from furniture and draperies Do not place clothing or other flammable materials on or near the appliance NEVER leave children unattended when a fire is burni...

Страница 2: ...MNEY PIPE INSTALLATION PG 7 9 FINISHING YOUR CHIMNEY SYSTEM PG 9 10 TERMINATIONS PG 11 11 FINISHING YOUR FIREBOX PG 12 12 OPERATING GUIDELINES AND MAINTENANCE INSTRUCTIONS PG 13 13 REPLACEMENT ACCESSO...

Страница 3: ...or approved by DESA INTERNATIONAL in this wood burning firebox PROPER INSTALLATION is the most important step in ensur ing a safe and continuous operation of this firebox Although grounding may not b...

Страница 4: ...uld not be placed within 9 inches of the effective opening of this firebox The effective opening is considered the opening where actual heat output may occur Combustible material above and projecting...

Страница 5: ...opening except on the end where projection is 16 in min to the front and 20 in to the sides see Figure 10 page 6 1 2 MIN OVERLAP 1 2 MIN METAL SAFETY STRIPS SUPPLIED 1 2 MIN TO COMBUSTIBLES 2 MIN CLEA...

Страница 6: ...the outside air kit please refer to the instructions included with the kit For operating instruc tions please refer to your owner s manual GAS LINE INSTALLATION YOUR GAS SUPPLIER OR A QUALIFIED SERVI...

Страница 7: ...ill install an unvented gas log set ONLY UNVENTED GAS LOGSETSWHICHHAVEBEENFOUNDTOCOMPLYWITHTHE STANDARDFORUNVENTEDROOMHEATERS ANS IAS AGA Z21 11 2 ARE TO BE INSTALLED IN THIS FIREPLACE NOTE An appropr...

Страница 8: ...ramed opening into a living space above a firestop must be placed on the ceiling below Figure 16 Figure 16 When the pipe passes through a framed opening into an attic space above a firestop must be pl...

Страница 9: ...e 20 and Rise and Offset Chart Figure 20 A B Maximum length of pipe between supports is 6 feet of angled run Amaximumoftwo6footangledrunsectionsperchimneysystem see Figure 21 Figure 21 FINISHING YOUR...

Страница 10: ...50 feet measured from bottom of firebox to flue outlet end of pipe CHIMNEY MAINTENANCE Have your chimney system cleaned and inspected regularly to ensure safe and efficient operation Refer to your Own...

Страница 11: ...le termina tion only Figure 27 shows an VRTL 10D round top termination Figure 27 CAUTION DO NOT SEAL OPENINGS ON THE ROOF TOP FLASHING FOLLOW THE INSTALLATION IN STRUCTIONS PROVIDED WITH THE TERMINATI...

Страница 12: ...earances are adhered to refer to section on clearances and the firebox opening are not blocked or obstructed in any way see Figure 30 TOP SLOT UNDERNEATH FRAME ADJUSTMENT CLIP ADJUSTMENT CLIP SHORT PI...

Страница 13: ...ting a fire this provides adequate outside combustionair Closethemechanismwhennotinusetopreventcold air from entering the room Periodically check your outside air intake vent hood for any possible obs...

Страница 14: ...ANGLED RUN PIPE SUPPORT ASSEMBLY V12S 10DM OUTSIDE AIR KIT VAK4 900147 VENT HOOD EMBER PROTECTORS 5 VENT PLASTER COLLAR FRONT PANEL ASSEMBLY CABINET DOOR SET LEFT RIGHT VDGPN36 Cabinet Doors 2 sets an...

Отзывы: